background image

3

Legend

E = integrity 

I = thermal insulation 

S = fume seal 

V

e

 = vertical installation 

h

o

 = horizontal installation 

i

o = side exposed to fire indifferent

1. SPECIFICATIONS / GENERAL DESCRIPTION

Fire damper suitable for wall or ceiling installation (horizontal or vertical), made from zinc-plated steel pipes and 

components, shutter and thermal cutting in single calcium silicate sheets 30 mm thick with perimeter seals to ensure 

conformity with sealing requirements for both cold fumes and hot fumes. The control device (manual, with electroma-

gnetic or motorised release system) consists of a removable plate which can be replaced even after installation has 

been completed, on which all the elements required for correct intervention and operation of the fire damper are hou-

sed; the particular geometry of the control mechanism, prevents the pressure in the duct (up to 300 Pa) from opening 

the shutter unless the reset lever has been activated. When the element has been installed, the control unit will remain 

outside the masonry to make post-installation interventions easier. When installed following the instructions provided 

in this manual, it can be used in HVAC plant systems reinstating the partitioning between two area, ensuring heat 

insulation and perfect sealing of fumes. 

The installer is obliged to follow the installation and material utilisation 

procedures illustrated in this manual; this is mandatory in order to comply with the same conditions of the tested 

samples. Any inconsistency with the provided instructions may comprise the validity of the product certification 

and the declaration of correct installation.

2. REGULATORY FRAMEWORK

Fire dampers tested according EN 1366/2 and classified according to EN 13501/3.

RESISTANCE RATING

SUPPORTING ELEMENT

EI 120 S - 500 Pa EI 90 S - 500 Pa

EI 60 S - 500 Pa

NORMALISED BRICK WALLS  MIN. WIDTH 120

(V

e

 i 

 o)

from 200x200

to 1500x800

from 200x200

to 1500x800

LIGHT WALL MIN. WIDTH 125

(V

e

 i 

 o)

from 200x200

to 1200x800

from 200x200

to 1200x800

HORIZONTAL FLOOR MIN. WIDTH 150

(h

o

 i 

 o)

from 200x200

to 1200x800

from 200x200

to 1200x800

from 200x200

to 1200x800

Содержание MDF30EURO

Страница 1: ...making air better MDF30EURO INSTALLATION AND OPERATION MANUAL FIRE PROTECTION EN...

Страница 2: ...RK 3 3 HANDLING AND INSTALLATION WARNINGS 4 4 MAINTENANCE 4 5 INSTALLATION IN BRICK WALLS 5 6 INSTALLATION IN CONCRETE FLOORS 6 7 INSTALLATION IN LIGHTWEIGHT WALLS 7 8 CONTROL FUNCTIONS 8 9 REPLACING...

Страница 3: ...has been installed the control unit will remain outside the masonry to make post installation interventions easier When installed following the instructions provided in this manual it can be used in H...

Страница 4: ...ch could prevent the correct operations of the commands outside the duct itself Keep as much access clearance as possible on the control unit side so as to ensure the user and maintenance operators ha...

Страница 5: ...d to be installed with vertical axis Respect the dimensions shown fig 2 table 1 4 Fill in the space between the wall and the damper using fireproof cement material M10 cat or higher to reinstate resis...

Страница 6: ...inst the damper casing so that it is blocked in the correct position fig 2 5 The metal brackets are designed to be fastened to the floor fig 3 6 Fill in the space between the floor and the damper usin...

Страница 7: ...he side of the bracket supporting the damper does not protrude over the outer edge of the flange Use the threaded bolts supplied with the brackets to fix them in place fig 3 5 Position the damper insi...

Страница 8: ...lectromagnetic circuit breaker Reset Power up the electromagnet electrical wiring diagram on page 8 Raise the metal lever on the control unit casing fig 1 Remove the reset lever from the housing compa...

Страница 9: ...he key supplied with the delivery into the housing on the servomotor and turn it counter clockwise by half a turn to enable the spring return that will automatically move the servomotor into the close...

Страница 10: ...Switch technical data Casing Fibre glass reinforced thermoplastic Protection rating EN 60526 Standard IP65 Cable cross section diameter rigid 2 5mm flexible with ferrule 1 5 mm Operating temperature...

Страница 11: ...device consists of three fuses these make the fire damper shutters sensitive to the temperature inside the duct with Tf 2 and Tf 3 fuses which can be replaced and to ambi ent temperatures using the Tf...

Страница 12: ...rofer it INSTALLER 19 143 43 211 70 55 500 210 21 30 051 Fax 210 22 23 283 BROFER SRL Via Roma 66 31023 Resana TV Italy Tel 39 0423 716611 Fax 39 0423 716612 info brofer it www brofer it making air be...

Отзывы: