MODELS  MD6T • MD8T • MD10T

Page 2

OUTSIDE AIR INTAKE LOCATION
Proper design and location of the outside air intake location is critical in 

ensuring that the Damper can safely and reliably provide an opening for 

fresh air to enter the home.  The following requirements for the location 

of the outside air intake must be met:

-

pliance vents, chimneys, plumbing stacks, and bathroom or kitchen 

exhaust vents.  If local codes have more stringent separation re-

quirements, they shall apply.

TYPICAL INSTALLATIONS

Installations will vary according to the location in the home where the unit is installed and which model Damper is used. Use the following 

illustrations and notes as guidance for your own installation.  Always comply with local code requirements and in any instance where a detail 

shown below conflicts with local code, the local code provision shall apply.

Damper connected to return side of central duct system.

blockage from snow or other debris such as leaves, and at a mini-

mum of 1’ above grade.

-

rages, attics, adjacent dwelling units, or any enclosed part of the 

building.  The Damper should be installed to draw air directly from 

outdoors.

OUTSIDE AIR INTAKE OPENING PROTECTION
Because the Damper, together with the end cap and outside air duct 

which are installed with it, will allow outdoor air into the indoor environ-

ment, it is important to meet the following requirements:

caps include protective bird screens to keep out animals and out-

side debris. Clean screens often and do not remove.

must cover the entire opening of the outside air duct.  This screen 

for the protection of openings in exterior walls, including steps to 

prevent moisture intrusion around the opening.  

Note that the screen over the outside air opening is not a filter.  It is 

intended to prevent the intake of leaves, animals, or debris into the out-

side air duct.  A downstream filter is necessary to remove pollen, dust, 

and other airborne particles.  Potential filter locations are shown below 

in the Typical Installations section.

MINIMUM RETURN AIR TEMPERATURE REQUIREMENTS
HVAC equipment manufacturers may have minimum requirements for 

the air temperature in the return air plenum.  Introducing outdoor air to 

the return side of the central duct system may impact this temperature.  

The installer should adjust both the size of the outside air duct and the 

location of its connection to the return side of the central duct system in 

a manner so that minimum air temperature requirements are satisfied 

under design conditions.  

AIR HANDLER UNIT

AIR DISTRIBUTION FAN

THERMOSTAT

CENTRAL SYSTEM SUPPLY AIR

REGISTER BOX ADAPTED

WITH SLIDE-IN FILTER (optional)

AUTO. MAKE-UP AIR DAMPER

FIELD MEASUREMENT OF AVAILABLE

STATIC PRESSURE. (See “Install The

Damper” section on page 3 for damper

balancing instructions.)

FRESH AIR INLET WALL CAP

WITH BIRD SCREEN

INSULATED OUTSIDE

AIR DUCT (slope toward wall cap)

EXTERIOR WALL

VENTILATION AIR INTAKE

(locate away from pollutant sources)

CENTRAL SYSTEM RETURN AIR

CENTRAL DUCT SYSTEM FILTER

PLAN THE INSTALLATION

Planning the installation first requires selecting the most appropriate 

installation approach.  The chart below offers suggestions for the most 

effective installation approach by considering a few important factors. 

Further details on the two main types of installations are provided below.

 

Yes

House has central duct work?

Yes

Return-air side of duct work is 

accessible -either the return-air trunk 

or return- air plenum?

Damper connected to 

return side of central 

duct system

No

No

Damper  ducted directly 

to a ceiling, floor, or wall 

register

Содержание MD10T

Страница 1: ...oists and wall studs comply with code and manufacturer limitations on allowable modifications to these structural members 11 This unit is intended to be installed within the home in a location protect...

Страница 2: ...Note that the screen over the outside air opening is not a filter It is intended to prevent the intake of leaves animals or debris into the out side air duct A downstream filter is necessary to remove...

Страница 3: ...off The set screw can be used to adjust the damper opening thereby balancing the inside and outside air pressure when the range hood exhausts at high speed Wire the system as shown 20 GAUGE BELL WIRE...

Страница 4: ...to the home through cracks to replace air which is exhausted out i e a water heater or natural draft fireplace which are more susceptible to improper venting if depressurization occurs in the home In...

Страница 5: ...NO OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE During this one year period Broan NuTone will at its optio...

Страница 6: ...s devez encocher ou percer les solives d un plancher ou les montants d un mur veuillez respecter les codes et limitations du fabricant quant aux modifications acceptables de ces l ments de charpente 1...

Страница 7: ...er que le grillage de la prise d air ne constitue pas un filtre Il ne vise qu emp cher l entr e des feuilles des animaux ou des d bris dans le conduit Un filtre situ en aval est n cessaire pour enleve...

Страница 8: ...erm et alimentation est coup e L ouverture du clapet peut tre r gl e l aide de la vis d arr t en quilibrant la pression d air int rieur et ext rieur lorsque la hotte de cuisine expulse l air haute vit...

Страница 9: ...r l int rieur par les fentes et remplacer l air vacu l ext rieur l atmosph re par ex chauffe eau ou foyer tirage naturel qui sont plus susceptibles d tre mal ventil s si la maison subit une d pressuri...

Страница 10: ...xempts de vice de mat riaux ou de fabrication pour une p riode d un an compter de la date d achat original IL N Y A PAS D AUTRES GARANTIES EXPRIM ES OU IMPLICITES INCLUANT MAIS NON LIMIT ES AUX GARANT...

Страница 11: ...bleado el ctrico ni otros servicios ocultos 10 Al crear muescas o al perforar la estructura lo cual incluye apoyos para el piso vigas y montantes de pared cumpla con las limitaciones de los c digos y...

Страница 12: ...incluyendo pasos para prevenir que entre humedad alrededor de la abertura Tome en cuenta que la malla sobre la abertura de aire exterior no es un filtro Est dise ada para prevenir la entrada de hojas...

Страница 13: ...n vertical cuando se cierra y el poder est apagado Se puede usar el tornillo de fijaci n para ajustar la abertura del regulador con lo cual se balan cea la presi n de aire interior y exterior cuando l...

Страница 14: ...casa por las grietas para reemplazar el aire que se extrae es decir un calentador de agua o una chimenea con tiro natural que son m s susceptibles para mejorar la ventilaci n si la despresurizaci n o...

Страница 15: ...esidenciales de baja elevaci n el uso de un regulador de aire de repuesto La norma ASHRAE 62 2 2007 no requiere espec ficamente reguladores de aire de repuesto En algunas circunstancias limitadas esta...

Страница 16: ...MODELS MOD LES MODELOS MD6T MD8T MD10T Page P gina 16...

Отзывы: