background image

- 5 -

Unit Check Points:

___  Power connected, no ventilation call - Both fans are

off, frost control damper (if equipped) closes off
fresh air from outside.

___  Power connected, low speed call - Both fans on low

speed, internal frost control damper (if equipped)
opens fresh air from outside. If equipped with recir-
culation module, the internal frost control damper
closes recirculation opening.

___  Power connected, high speed call - Both fans on

high speed, frost control damper opens fresh air
from outside. If equipped with recirculation module,
the internal frost control damper closes recirculation
opening.

___  Power connected, occupied timer/sensor connec-

tion open (unoccupied mode) - Both fans are off,
frost control damper closes fresh air from outside. If
equipped with recirculation module, the internal frost
control damper opens recirculation opening.

___  Power connected, FF control contacts close during

unit ventilation or frost control cycle.

Frost Control

The unit functions are controlled by integrated controls

in the unit which may include Exhaust Only Defrost or
Recirculation Defrost (via the recirculation module - 600
cfm and 1200 cfm units only). In cold temperatures, frost
control cycles will remove frost from the heat exchanger
to maintain good operation. 

Exhaust Only Defrost

(Optional)

Frost removal occurs when the supply blower de-ener-

gizes, the supply air damper and the heat exchange
damper close and the exhaust fan continues to circulate
only warm inside air through the flat plate heat exchang-
er to maintain ventilation. This process prevents the build
up of ice in the heat exchanger. Frost control is tempera-
ture initiated at 23°F to -22°F [-5°C to -30°C] and time
based.

Recirculation Defrost Module

The Recirculation Defrost Module is only available with

the 600 cfm and 1

15

0 cfm units. The frost control cycle is

electronically controlled in response to the outside
temperature 23°F to -22°F [-5°C to -30°C]. On a call for
frost control, the supply air damper in the recirculation
module closes, exhaust fan is de-energized and the sup-
ply fan continues to recirculate warm air through the flat
plate heat exchanger. It is possible to extend the frost con-
trol times during very cold weather by removing the jumper
JU1-F on the circuit board. For dimension and weight

changes to the 600 cfm and 1

15

0 cfm models with the

recirculation defrost module, see Appendix B-2 and B-4.

Remote Wall Control

(Optional)

Remote mounted wall control options are solid state

controls that can be used to control the ventilators from a
remote location. The connection from the ventilator to the
control is low voltage and requires a 4 conductor (24
gauge minimum) LVT cable. Models are available with a
dehumidistat control and speed switching. The following
three options are available:

Standard Wall Control

Dehumidistat to engage high speed exchange. Slide

switch operation supporting continuous low exchange
and continuous high exchange.

Xtra Wall Control

Dehumidistat to engage high speed exchange.

Electronic push button operation supporting intermittent
(stand-by) ventilation, continuous low exchange, continu-
ous high exchange, maintenance indicator light and
exchange indicator light.

AquaAir Wall Control

Ideal for pool dehumidification. Dehumidistat to engage

high speed exchange. Electronic push button operation
supporting intermittent (stand-by) ventilation, continuous
low exchange, continuous high exchange, maintenance
indicator light and exchange indicator light.

Airflow Measurement and Balancing

Once installation is complete, the supply and exhaust

airflows should be balanced to ensure proper operation
and a good quality installation. A well designed duct
system with properly sized duct runs and equal static
pressure losses of both the supply and exhaust will aid in
balancing the unit. However, it will be necessary to take
flow measurements with the proper equipment to ensure
a balanced system. Magnehelic gauges and Flow
Measuring Stations (FMS) are available for 14" x 8" [356
x 203mm] or 20" x 8" [508 x 203mm] rectangular duct and
a range of round duct sizes. Please ask your supplier for
more information.

Flow Station Positions

Whether flow stations are permanently installed or used

temporarily, the position they are placed in is very impor-
tant to ensure accuracy as shown in Appendix C. The
best locations for mounting the FMS is in the long straight
sections of ducting where airflow has stabilized across
the area of the duct. This position will provide the most
accurate measurements.

The next best location for the FMS is immediately

before or after a 90 degree elbow and 12" [305mm] from
any damper. In straight sections of pipe, the FMS should
be installed at least 30" [762mm] from any fan outlet. This
applies to the "Supply Air Opening" connection on the
heat recovery ventilator and the "Exhaust Air Opening"
connection.

WARNING

A negative building pressure may develop during the
frost control cycle with possible backdrafting fumes from

combustion equipment.

Содержание HRV1150

Страница 1: ...Installation Operation and Maintenance Instructions HRV650 HRV700 HRV1150 HRV1150...

Страница 2: ...t and Balancing Flow Station Positions 5 Balancing Procedure 6 System Service Bi Monthly Maintenance 6 Annual Maintenance 6 Appendix A Mounting Diagrams 8 Appendix B Unit Dimensions 9 Appendix C Flow...

Страница 3: ...talling the unit keep in mind that access to the control panel may be required Supply and exhaust ducts to outside may have 1 to 2 25 to 51mm of insulation on them Rubber vibration isolation may be re...

Страница 4: ...s to be used ensure not to solder to the 3 4 19mm coupler while it is attached to the plastic drain fitting as deformation may occur Ensure adequate slope is present to allow good drainage minimum 1 4...

Страница 5: ...Remote Wall Control Optional Remote mounted wall control options are solid state controls that can be used to control the ventilators from a remote location The connection from the ventilator to the...

Страница 6: ...able Under normal conditions it is recommended that they be cleaned every two months More frequent cleaning may be required under extremely dirty operating conditions Use a vacuum cleaner to remove th...

Страница 7: ...rol functions are not working properly Ensure that power is reaching the board Test the blower motors and damper actuators for operation when directly connected to the appropriate power voltage If the...

Страница 8: ...connection of drain lines with adequate slope for drainage Wooden Curb Supplied by others Bolt to Floor Rubber Vibration Isolator Supplied by others U Channel Supplied by others 3 8 10mm Threaded Rod...

Страница 9: ...uction is required for removal of heat recovery cores fans etc The access door can be removed from the cabinet with only 2 000 51 of clearance CONTROL PLATE ACCESS DOOR HEAT RECOVERY CORE REVERSED DOO...

Страница 10: ...15 000 381 clearance from any obstruction is required for removal of heat recovery cores fans etc The access door can be removed from cabinet with only 2 000 51 of clearance 8 000 203 8 000 203 14 10...

Страница 11: ...ruction is required for removal of heat recovery cores fans etc The access door can be removed from the cabinet with only 2 000 51 of clearance EXHAUST AIR SUPPLY AIR LEFT SIDE VIEW Dimensions in are...

Страница 12: ...81 clearance from any obstruction is required for removal of heat recovery cores fans etc The access door can be removed from cabinet with only 2 000 51 of clearance REVERSED DOOR OPTION EXHAUST AIR T...

Страница 13: ...203 15 250 387 2 000 51 LINE VOLTAGE IN NOTE A minimum of 12 000 305 clearance from any obstruction is required for power hook up low voltage remote connection and control panel access NOTE A minimum...

Страница 14: ...Option Exhaust Air From Building Fresh Air From Outside Min 8 203mm Optional Canvas Vibration Isolator Min 12 305mm Min 12 304mm Flow Measuring Station FMS Balancing Damper not supplied Canvas Vibrati...

Страница 15: ...1 25mm Min 3 76mm Plastic Drain Fitting To Drain Copper or Plastic Pipe Min 3 76mm Min 1 25mm 3 4 NPT Coupler Water Trap Plastic Hose To Drain NOTE All hose pipe and couplers to be supplied by others...

Страница 16: ...12 VDC Low Voltage Controls All other terminals are dry contacts Low voltage terminal control consists of the following Wall Control 4 wire LVT 24 gauge minimum Occupied Night Setback Timer Sensor 24...

Страница 17: ...trol and 24VAC power supply Use of 24VAC circuit requires isolating contacts ex thermostat to prevent interconnection of Class 2 outputs Occupancy control is achieved by connection to the terminal int...

Страница 18: ...PJ2003 PJ2014 PJ1007 PJ1001A UCB1021 CR1029 CR1023 1 2 3 4 5 6 A B COM NC NO PJ2011 PJ1001 CR1024 CR1026 1 0 4 8 2 6 1 0 4 8 2 6 FILTRAN NOTE Low speed motor selection may be replaced by medium speed...

Страница 19: ...472 9 9 14 1 15 7 7 4 11 7 13 3 5 0 9 3 10 9 2 6 6 9 8 5 0 2 4 4 6 1 900 425 8 5 12 4 13 8 6 4 10 2 11 7 4 3 8 1 9 6 2 2 6 0 7 5 0 1 3 9 5 4 800 377 7 0 10 4 11 7 5 2 8 6 9 9 3 4 6 8 8 2 1 7 5 0 6 4...

Страница 20: ...st air Check filters and heat exchangers for blockage Check balance of airflows Outdoor temperature very cold Install electric duct heater if necessary Unit makes annoying noise Blower wheel out of al...

Отзывы: