background image

- 16 -

WALL CONTROL

CLASS 2 VOLTAGE

Black

OCCUPIED
TIMER/
SENSOR

F

F

LOW

COMMON

HIGH

Red

Green

Yellow

NOTE:

   

Connections are all dry 

contacts except wall control 
and 24VAC power supply.

   Use of 24VAC circuit 
requires isolating contacts 
(ex. thermostat) to prevent
interconnection of Class 2 
outputs. 

Wall

Control

JUMPER

WALL CONTROL

CLASS 2 VOLTAGE

Black

OCCUPIED
TIMER/
SENSOR

F

F

LOW

COMMON

HIGH

Red

Green

Yellow

NOTE:

   

Connections are all dry 

contacts except wall control 
and 24VAC power supply.

   Use of 24VAC circuit 
requires isolating contacts 
(ex. thermostat) to prevent
interconnection of Class 2 
outputs. 

A low voltage remote control wiring interface is

provided on the unit. The connections for the low voltage
remote wiring are located on two terminals adjacent to
the exhaust fan outlet (or adjacent to the supply fan out-
let on the 700 cfm unit). All field installed wiring must be
low voltage class II.

Remote Wall Control

Optional wall control requires a 4-wire LVT 24 gauge

(or equivalent). This remote wall control runs on 12 VDC.

Low Voltage Controls

All other terminals are dry contacts.

Low voltage terminal control consists of the following:

Wall Control

4-wire LVT 24 gauge minimum.

Occupied (Night Setback) Timer/Sensor

24 VAC, needs dry contact.

LOW - COM - HIGH

Remote fan switching requires a single pole, double

throw switch (SPDT).

Fan Interlock switch (FF)

Dry contact closes on ventilation or frost control. Used

to control external fan source (G).

Three types of remote wall controls are available:

1. 

Standard Wall Control

with fan switch and dehu-

midistat control.

2. 

Xtra Wall Control

with fan mode selection, dehu-

midistat control and maintenance indicator.

3. 

AquaAir Wall Control

with fan mode selection,

dehumidistat control and high speed recirculation
mode.

The remote wall controls work with the integrated elec-

tronic controls within the unit to control ventilation
sequences. Each wall control has different features and
requires 4-wire connection to the unit as shown below.
Without the wall control, fans can be operated with a
remote fan switch as shown in Appendix E-4.

NOTE: 

An occupied timer or sensor device 

cannot be

used

with the Xtra wall control.

Appendix E

Terminal Control Diagrams

E-1: Terminal Label

E-2: Wall Control Connection

Содержание HRV1150

Страница 1: ...Installation Operation and Maintenance Instructions HRV650 HRV700 HRV1150 HRV1150...

Страница 2: ...t and Balancing Flow Station Positions 5 Balancing Procedure 6 System Service Bi Monthly Maintenance 6 Annual Maintenance 6 Appendix A Mounting Diagrams 8 Appendix B Unit Dimensions 9 Appendix C Flow...

Страница 3: ...talling the unit keep in mind that access to the control panel may be required Supply and exhaust ducts to outside may have 1 to 2 25 to 51mm of insulation on them Rubber vibration isolation may be re...

Страница 4: ...s to be used ensure not to solder to the 3 4 19mm coupler while it is attached to the plastic drain fitting as deformation may occur Ensure adequate slope is present to allow good drainage minimum 1 4...

Страница 5: ...Remote Wall Control Optional Remote mounted wall control options are solid state controls that can be used to control the ventilators from a remote location The connection from the ventilator to the...

Страница 6: ...able Under normal conditions it is recommended that they be cleaned every two months More frequent cleaning may be required under extremely dirty operating conditions Use a vacuum cleaner to remove th...

Страница 7: ...rol functions are not working properly Ensure that power is reaching the board Test the blower motors and damper actuators for operation when directly connected to the appropriate power voltage If the...

Страница 8: ...connection of drain lines with adequate slope for drainage Wooden Curb Supplied by others Bolt to Floor Rubber Vibration Isolator Supplied by others U Channel Supplied by others 3 8 10mm Threaded Rod...

Страница 9: ...uction is required for removal of heat recovery cores fans etc The access door can be removed from the cabinet with only 2 000 51 of clearance CONTROL PLATE ACCESS DOOR HEAT RECOVERY CORE REVERSED DOO...

Страница 10: ...15 000 381 clearance from any obstruction is required for removal of heat recovery cores fans etc The access door can be removed from cabinet with only 2 000 51 of clearance 8 000 203 8 000 203 14 10...

Страница 11: ...ruction is required for removal of heat recovery cores fans etc The access door can be removed from the cabinet with only 2 000 51 of clearance EXHAUST AIR SUPPLY AIR LEFT SIDE VIEW Dimensions in are...

Страница 12: ...81 clearance from any obstruction is required for removal of heat recovery cores fans etc The access door can be removed from cabinet with only 2 000 51 of clearance REVERSED DOOR OPTION EXHAUST AIR T...

Страница 13: ...203 15 250 387 2 000 51 LINE VOLTAGE IN NOTE A minimum of 12 000 305 clearance from any obstruction is required for power hook up low voltage remote connection and control panel access NOTE A minimum...

Страница 14: ...Option Exhaust Air From Building Fresh Air From Outside Min 8 203mm Optional Canvas Vibration Isolator Min 12 305mm Min 12 304mm Flow Measuring Station FMS Balancing Damper not supplied Canvas Vibrati...

Страница 15: ...1 25mm Min 3 76mm Plastic Drain Fitting To Drain Copper or Plastic Pipe Min 3 76mm Min 1 25mm 3 4 NPT Coupler Water Trap Plastic Hose To Drain NOTE All hose pipe and couplers to be supplied by others...

Страница 16: ...12 VDC Low Voltage Controls All other terminals are dry contacts Low voltage terminal control consists of the following Wall Control 4 wire LVT 24 gauge minimum Occupied Night Setback Timer Sensor 24...

Страница 17: ...trol and 24VAC power supply Use of 24VAC circuit requires isolating contacts ex thermostat to prevent interconnection of Class 2 outputs Occupancy control is achieved by connection to the terminal int...

Страница 18: ...PJ2003 PJ2014 PJ1007 PJ1001A UCB1021 CR1029 CR1023 1 2 3 4 5 6 A B COM NC NO PJ2011 PJ1001 CR1024 CR1026 1 0 4 8 2 6 1 0 4 8 2 6 FILTRAN NOTE Low speed motor selection may be replaced by medium speed...

Страница 19: ...472 9 9 14 1 15 7 7 4 11 7 13 3 5 0 9 3 10 9 2 6 6 9 8 5 0 2 4 4 6 1 900 425 8 5 12 4 13 8 6 4 10 2 11 7 4 3 8 1 9 6 2 2 6 0 7 5 0 1 3 9 5 4 800 377 7 0 10 4 11 7 5 2 8 6 9 9 3 4 6 8 8 2 1 7 5 0 6 4...

Страница 20: ...st air Check filters and heat exchangers for blockage Check balance of airflows Outdoor temperature very cold Install electric duct heater if necessary Unit makes annoying noise Blower wheel out of al...

Отзывы: