background image

To change the "Fresh Air From Outside" from the side

to the top use the following directions. For port locations
see Appendix B.

Remove the cover of the damper motor with a flat screw

driver. Reverse the Orange and Red wires by moving the
Orange from terminal #2 to terminal #3 and moving the
Red wire from terminal #3 to terminal #2. The end result,
in order to have the "Fresh Air From Outside" connection
to the top port, will be; #1 - White, #2 - Red, #3 - Orange.

Internal Grilles and Diffusers

Locate exhaust grilles and supply diffusers to provide

effective ventilation and avoid short circuiting of airflows.
Adjustable dampers should be provided at every grille
and diffuser location to make balancing of the system
possible.

A proper selection of style and size of grilles and dif-

fusers is required to minimize pressure drop. The velocity
of the airflow should not exceed 400 ft/min [2 m/sec] for
normal applications.

The duct system should be designed according to the

high speed flow rate of the unit. In order to keep the noise
and pressure drop to a minimum, a maximum air velocity
of 1100 ft/min [5.6 m/sec] should be used in calculations
in duct design. The duct runs should be kept as short as
possible with the minimum amount of elbows and transi-
tions. The manufacturer recommends the use of smooth
radius elbows or square elbows with turning vanes to
achieve maximum performance.

Drains

The drain fittings provided with the unit will accept a

3/4" [19mm] NPT coupler (supplied by others). The drain
line for the unit must be fabricated on-site and connected
to the building main. A loop in the hose or trap in the cop-
per or plastic pipe must be provided to prevent sewer
gases from entering the unit when connecting to a drain
as illustrated in Appendix D.

NOTE: 

Consult local building code for plumbing require-
ments in your area. If copper pipe is to be used,
ensure not to solder to the 3/4" [19mm] coupler
while it is attached to the plastic drain fitting as
deformation may occur. Ensure adequate slope is
present to allow good drainage (minimum 1/4"/foot
or 6mm/305mm).

Electrical Connections

Power

A terminal block and strain relief bushing or a junction

box is provided for line voltage to make the necessary
power connections.

The electrical requirements are as follows:

Control Box Access For Low Speed Setting 

(600 cfm/1

150

 cfm only)

Disconnect power to the unit. Remove the four screws

securing the cover plate as shown in Appendix F. Lift off
the control cover plate and switch the red wire as shown
in Appendix F.

Controls

General Information

Fan Interlock Switch 

(FF)

External fan control can be achieved by connecting an

external fan source (G) through dry contacts (FF). These
contacts are closed on a call for ventilation or frost control.

Speed Selection

(600 cfm/1

150

 cfm only)

There are three speed settings available with the con-

trols, only two of which can be functional at any one time.
The units are factory set to use the low and high speed
taps on the blower motors. If necessary, the medium
speed tap can be used instead of the low speed tap. See
Appendix F for instructions on how to make this change.
Units without the remote wall control option can be shut
off by opening the contact between LOW - COM or HIGH
- COM as shown in Appendix E-2.

Sequence of Operation

Before start-up, check the unit for obstructive packaging,

objects near or in blowers, dampers, heat exchangers, etc.
Once installation is complete, check all modes of operation
to ensure that the unit is working properly. Close the doors
and check for operation on LOW, COM and HIGH. Use a
wall control or the dry contact switching to run fan speeds
as shown in Appendix E-2.

The 700 cfm unit is two speed. Low speed can be initi-

ated by creating a closure across LOW - COM or high
speed can be initiated by creating a closure across HIGH
- COM.

VOLTAGE

120V

120V

120V

MCA

8.6

5.6

13.3

MOP

12

8

15

600 cfm

700 cfm

1

150

 cfm

- 4 -

Содержание HRV1150

Страница 1: ...Installation Operation and Maintenance Instructions HRV650 HRV700 HRV1150 HRV1150...

Страница 2: ...t and Balancing Flow Station Positions 5 Balancing Procedure 6 System Service Bi Monthly Maintenance 6 Annual Maintenance 6 Appendix A Mounting Diagrams 8 Appendix B Unit Dimensions 9 Appendix C Flow...

Страница 3: ...talling the unit keep in mind that access to the control panel may be required Supply and exhaust ducts to outside may have 1 to 2 25 to 51mm of insulation on them Rubber vibration isolation may be re...

Страница 4: ...s to be used ensure not to solder to the 3 4 19mm coupler while it is attached to the plastic drain fitting as deformation may occur Ensure adequate slope is present to allow good drainage minimum 1 4...

Страница 5: ...Remote Wall Control Optional Remote mounted wall control options are solid state controls that can be used to control the ventilators from a remote location The connection from the ventilator to the...

Страница 6: ...able Under normal conditions it is recommended that they be cleaned every two months More frequent cleaning may be required under extremely dirty operating conditions Use a vacuum cleaner to remove th...

Страница 7: ...rol functions are not working properly Ensure that power is reaching the board Test the blower motors and damper actuators for operation when directly connected to the appropriate power voltage If the...

Страница 8: ...connection of drain lines with adequate slope for drainage Wooden Curb Supplied by others Bolt to Floor Rubber Vibration Isolator Supplied by others U Channel Supplied by others 3 8 10mm Threaded Rod...

Страница 9: ...uction is required for removal of heat recovery cores fans etc The access door can be removed from the cabinet with only 2 000 51 of clearance CONTROL PLATE ACCESS DOOR HEAT RECOVERY CORE REVERSED DOO...

Страница 10: ...15 000 381 clearance from any obstruction is required for removal of heat recovery cores fans etc The access door can be removed from cabinet with only 2 000 51 of clearance 8 000 203 8 000 203 14 10...

Страница 11: ...ruction is required for removal of heat recovery cores fans etc The access door can be removed from the cabinet with only 2 000 51 of clearance EXHAUST AIR SUPPLY AIR LEFT SIDE VIEW Dimensions in are...

Страница 12: ...81 clearance from any obstruction is required for removal of heat recovery cores fans etc The access door can be removed from cabinet with only 2 000 51 of clearance REVERSED DOOR OPTION EXHAUST AIR T...

Страница 13: ...203 15 250 387 2 000 51 LINE VOLTAGE IN NOTE A minimum of 12 000 305 clearance from any obstruction is required for power hook up low voltage remote connection and control panel access NOTE A minimum...

Страница 14: ...Option Exhaust Air From Building Fresh Air From Outside Min 8 203mm Optional Canvas Vibration Isolator Min 12 305mm Min 12 304mm Flow Measuring Station FMS Balancing Damper not supplied Canvas Vibrati...

Страница 15: ...1 25mm Min 3 76mm Plastic Drain Fitting To Drain Copper or Plastic Pipe Min 3 76mm Min 1 25mm 3 4 NPT Coupler Water Trap Plastic Hose To Drain NOTE All hose pipe and couplers to be supplied by others...

Страница 16: ...12 VDC Low Voltage Controls All other terminals are dry contacts Low voltage terminal control consists of the following Wall Control 4 wire LVT 24 gauge minimum Occupied Night Setback Timer Sensor 24...

Страница 17: ...trol and 24VAC power supply Use of 24VAC circuit requires isolating contacts ex thermostat to prevent interconnection of Class 2 outputs Occupancy control is achieved by connection to the terminal int...

Страница 18: ...PJ2003 PJ2014 PJ1007 PJ1001A UCB1021 CR1029 CR1023 1 2 3 4 5 6 A B COM NC NO PJ2011 PJ1001 CR1024 CR1026 1 0 4 8 2 6 1 0 4 8 2 6 FILTRAN NOTE Low speed motor selection may be replaced by medium speed...

Страница 19: ...472 9 9 14 1 15 7 7 4 11 7 13 3 5 0 9 3 10 9 2 6 6 9 8 5 0 2 4 4 6 1 900 425 8 5 12 4 13 8 6 4 10 2 11 7 4 3 8 1 9 6 2 2 6 0 7 5 0 1 3 9 5 4 800 377 7 0 10 4 11 7 5 2 8 6 9 9 3 4 6 8 8 2 1 7 5 0 6 4...

Страница 20: ...st air Check filters and heat exchangers for blockage Check balance of airflows Outdoor temperature very cold Install electric duct heater if necessary Unit makes annoying noise Blower wheel out of al...

Отзывы: