2.2 U
SING THE
P
LATINUM
M
AIN
C
ONTROL
(
CONT
’
D
)
13
H
OW TO SET THE RELATIVE HUMIDITY
(RH)
LEVEL AND CHOOSE BETWEEN
OFF
IN STANDBY OR
RECIRCULATION
IN STAND
-
BY
Setting the relative humidity level allows to select the maximum desired indoor humidity
level (in percentage). This value will be used to start the dehumidistat override (air
exchange in high speed).
Press and hold OK for 3 sec. to access the settings
menu. The backlight will be activated during all the
procedure.
The Relative humidity arrow and value will flash (default
setting: 45%).
Use UP or DOWN arrow to change the value.
The value changes by 1% increments. Lower
value: 30%. Upper value: 55%. Still flashing.
Press OK button to accept the new value and go to next
settting.
Two lines are flashing to show that OFF¹ is in stand by
(default configuration setting).
OR
Recirculation arrows are turning and rE flashes to show
that RECIRCULATION² is in standby.
Press OK button to accept and quit
setting menu.
OR
Use UP or DOWN
arrow to change to
RECIRCULATION
in standby.
OR
Press OK button to accept and quit setting menu.
1OFF
IN STAND BY
:
On 20
MIN
/
H
mode, the ventilation unit is OFF during 40 minutes
and exchange air with the outside on low speed during the
remaining 20 minutes of the hour. This is the default value.
2RECIRCULATION
IN STAND BY
: On 20
MIN
/
H
mode, the ventilation unit recirculates
the inside air for 40 minutes on high speed and
exchange air with the outside on low speed during
the remaining 20 minutes of the hour.