Broan ERVS100S Скачать руководство пользователя страница 4

4

2 Unit Preparation

•  Inspect the exterior of the unit for shipping damage.
•  Unit should never operate while the building is still in construction.
•  Unit is shipped with its door covered with a cardboard for protection during construction. Leave the cardboard on until painting.

2.1 Choose an Appropriate Location for the Unit

•  Within an area of the house where the ambient temperature is kept between 50°F and 135°F;
•  Away from living areas (dining room, living room, bedroom), if possible to reduce noise level;
•  So as to provide easy access to the interior cabinet for maintenance;
•  Close to an exterior wall, so as to limit the length of the insulated fl exible ducts to and from the unit;
•  Away from hot chimneys, electrical panel and other fi re hazards;
•  Within 28" of a power source (standard outlet, ERVS100S unit only).

2.2 Electrical Connection Type (Cord Connected or Hardwired)

•  According to your needs and applicable codes, make sure you have the appropriate model (ERVS100S: cord connected unit 

and ERVS100S-HW: hardwired unit).

3 Installation

3.1 Positioning the Unit

• Unit can be installed between 24” on-center trusses, on top of 24” on-center trusses in reversed position or under the ceiling, 

using brackets. A set of 4 brackets is included in the hardware kit, along with the necessary screws.

• The unit shall be connected to a 15-amp electrical circuit. It is recommended to label the circuit to identify this system as the 

Fresh Air System. If cord connected (ERVS100S unit only), a standard 3-prong electrical outlet has to be available within 28” 
of the unit.

• Allow a 12” clearance for the door, core and fi lters to be removed for maintenance. 

3.1.1 Installation in the ceiling (between 24

 on-center trusses)

1.  Trace a level line on both trusses, at 1/2” or 1” from the bottom, for 

the unit bracket location (1/2” will allow the unit door perimeter to 
lay on ceiling material while 1” will result in flush mount installation; 
see 

A

 and 

in

 

next page). On one truss, screw half way on level line 

two no. 8 x 1½” provided screws, leaving 23” between each other.

2.  Mount the 4 brackets to the unit as illustrated at 

right, using two no. 10 x 5/8" screws provided for 
each bracket. 

 

TIP: Screw half way the screws to allow adjusment 
between trusses, see insets at right (left shows the 
minimum distance and right the maximum distance.

3.  Hang the lightest side of the unit on the screws mounted 

on the truss using the larger holes of the brackets.

4.  Lift the other side of the unit and secure it to the other 

truss using one no. 8 x 1½” screw per bracket, inserted 
through the smaller hole of the brackets.

VD0391A

VD0394

VD0390

Unit must be installed in the horizontal orientation as shown in section 3.1.

Содержание ERVS100S

Страница 1: ...LY VB0342 READ AND SAVE THESE INSTRUCTIONS INSTALLER LEAVE THIS MANUAL WITH HOMEOWNER Broan NuTone LLC 926 west State Street Hartford Wisconsin USA 800 558 1711 broan nutone com REGISTER YOUR PRODUCT...

Страница 2: ...ion or renovation of your house or when sanding drywall Certain types of dust and vapors may damage your system 2 Please read specification label on product for further information and requirements 3...

Страница 3: ...E OF CONTENTS 1 Safe Installation Zone 3 2 Unit Preparation 4 2 1 Choose an Appropriate Location for the Unit 4 2 2 Electrical Connection Type Cord Connected or Hardwired 4 3 Installation 4 12 3 1 Pos...

Страница 4: ...the hardware kit along with the necessary screws The unit shall be connected to a 15 amp electrical circuit It is recommended to label the circuit to identify this system as the Fresh Air System If c...

Страница 5: ...t be spread over the unit Installed unit area ambient temperature must be kept between 50 F and 135 F ZONE A CAUTION When installed in the ceiling in an unconditioned space e g attic above the unit in...

Страница 6: ...e 3 1 3 Installation under the ceiling in a conditioned space 1 Mount the brackets to the unit as illustrated above using two no 10 x 5 8 screws provided for each bracket 2 Secure unit to the ceiling...

Страница 7: ...doors with backdraft damper Fresh air from outdoors VH0113A ERV OPTION 2 OPTION 1 3 Installation cont d ERV VH0115A AHU supply ducting and grille to home Stale air from home connected to return ductin...

Страница 8: ...the ports Connecting insulated flexible ducts to the ports 1 Pull back the insulation to expose the flexible duct 2 Attach the flexible duct to the port using a tie wrap ensure tie wrap is tighten to...

Страница 9: ...nsition kit can be used instead of 2 exterior hoods An additional backdraft damper not included must be installed on the stale air to outdoors duct following common best practice Should the backdraft...

Страница 10: ...W B BLACK G GREEN R RED Y YELLOW B BLACK G GREEN G R B Y VE0357A G R B Y OL OC I VE0358A OL OC I ON ON CAUTION Ensure all unused wires are capped off Switch position Unit mode Dry contact ope ned Unit...

Страница 11: ...the ground wire from the flexible conduit to the GREEN ground screw inside the electrical compartment Using included wire nuts perform the hardwire connection as follows BLACK wire to BLACK wire WHIT...

Страница 12: ...overtighten such that the flexible metal conduit is damaged 6 Insert all the wires inside the electrical compartment 7 Reinstall and secure the electrical compartment cover taking care not to pinch wi...

Страница 13: ...changed by the installer after all construction work is over in order to comply to local building codes Should the user want to change the settings later on it should be done by an authorized servicer...

Страница 14: ...UTION VR0112 A VO0274 3 While holding the core if unit is installed in or under the ceiling loosen the wing nut and rotate the core retaining bracket shaded part in illustration at right Slide out the...

Страница 15: ...t unless the unit is accompanied by a copy of the original bill of purchase Please retain your original MISCELLANEOUS COSTS In each case the labor costs for the removal of a defective part and or inst...

Страница 16: ...INE V OLTAGE F ACTORY W IRING C LASS 2 L OW V OLTAGE F ACTORY W IRING C LASS 2 L OW V OLTAGE F IELD W IRING RH S ENSOR A2 S1 D OOR I NTERLOCK S WITCH 1 2 1 2 1 2 3 1 2 3 J4 J2 J3 A1 E LECTRONIC A SSEM...

Страница 17: ...uce the performance level of your unit which will result in premature failing Also Broan NuTone LLC recommends to contact a Broan NuTone LLC certified service depot for all replacement parts and repai...

Страница 18: ...sconnected Defective RH and temperature sensor Check the sensor harness connection ensure that connector is connected to its appropriate place the wires are not damaged and connector pins are not corr...

Страница 19: ...ONSERVE ESTAS INSTRUCCIONES INSTALADOR ENTREGUE ESTE MANUAL AL CLIENTE Broan NuTone LLC 926 west State Street Hartford Wisconsin USA 800 558 1711 broan nutone com REGISTRE SU PRODUCTO EN L NEA EN www...

Страница 20: ...sea m s restrictiva en materia de instalaci n o certificaci n dicha reglamentaci n prevalecer sobre las exigencias de este manual y el instalador acepta atenerse a dicha reglamentaci n y asumir los g...

Страница 21: ...unidad 4 2 1 Elecci n de una ubicaci n adecuada para el aparato 4 2 2 Tipo de conexi n el ctrica conectado con cable de alimentaci n o conectado con cableado local 4 3 Instalaci n 4 12 3 1 Colocaci n...

Страница 22: ...que los 4 soportes en la unidad como puede verse en la ilustraci n de la derecha utilice para ello dos tornillos n 10 x 5 8 por soporte provistos CONSEJO Atornille a mitad los tornillos para permitir...

Страница 23: ...mperatura ambiente donde se instala la unidad debe mantenerse entre 50 F y 135 F ZONA A PRECAUCI N Cuando se instala en el techo en un espacio acondicionado p ej un desv n sobre la unidad en zona B un...

Страница 24: ...del producto 3 1 3 Instalaci n debajo del techo en un espacio acondicionado 1 Coloque los soportes en la unidad como puede verse en la ilustraci n de arriba utilice para ello dos tornillos n 10 x 5 8...

Страница 25: ...y rejilla de la AHU hacia la vivienda VH0113E Aire viciado hacia el exterior con clapeta de retenci n Aire fresco del exterior ERV OPCI N 2 OPCI N 1 3 Instalaci n cont Aire viciado de la vivienda cone...

Страница 26: ...ertos Conexi n de conductos flexibles aislados a los puertos 1 Retire el aislante para que quede a la vista el conducto flexible 2 Sujete el conducto flexible al puerto con una tira de amarre verifiqu...

Страница 27: ...instalar un conjunto de cambio de secci n Tandem en lugar de 2 bocas exteriores Debe instalarse otra compuerta de contracorriente no incluida en el conducto que lleva el aire viciado al exterior de ac...

Страница 28: ...se a un interruptor de espera de contacto seco si se desea En tal caso la unidad permanece encendida pero se pone en modo de espera cuando se activa el interruptor Este ventilador de recuperaci n de e...

Страница 29: ...erra del tubo flexible al tornillo de tierra VERDE en el compartimiento el ctrico Usando los capuchones de conexi n incluidos realizar las conexiones como sigue hilo NEGRO al hilo NEGRO hilo BLANCO al...

Страница 30: ...tubo de metal flexible no sea da ado 6 Insertar todos los hilos en el compartimiento el ctrico 7 Reinstalar y sujetar la tapa del compartimento el ctrico teniendo cuidado de no atascar ning n hilo Re...

Страница 31: ...osdeconstrucci nconelfindecumplirconlosc digos de construcci n locales Si el usuario desea cambiar los par metros posteriormente deber a recurrir a un t cnico autorizado La unidad no deber a funcionar...

Страница 32: ...porte que retiene el n cleo parte sombreada de la ilustraci n de la derecha Saque el n cleo con sus filtros 4 Lave ambos filtros del n cleo con agua tibia y un jab n suave Enju guelos y deje que seque...

Страница 33: ...para las piezas de recambio y para solicitar un servicio FACTURA La garant a no cubrir ninguna reparaci n ni sustituci n sin la factura original de compra Le rogamos pues que la conserve debidamente...

Страница 34: ...ABLEADO DE BAJA TENSI N DE F BRICA DE CLASE 2 C ABLEADO DE BAJA TENSI N IN SITU DE CLASE 2 S ENSOR RH A2 S1 I NTERRUPTOR DE INTERBLOQUEO DE LA PUERTA 1 2 1 2 1 2 3 1 2 3 J4 J2 J3 A1 C ONJUNTO ELECTR...

Страница 35: ...ci n homologado por Broan NuTone LLC para todos los repuestos y reparaciones B C D F G I J K E H VL0083 N o DESCRIPCI N N o DE PIEZA CTD 1 PUERTA SV66548 1 2 PLACA DE CIRCUITOS IMPRESOS Y RESORTE DEL...

Страница 36: ...ctor est conectado en el lugar adecuado que los hilos no est n da ados y que las clavijas del conector no est n corro das Abra la puerta y presione el resorte del interruptor de la puerta para reinici...

Отзывы: