WVRC-4 Installation and Operation Manual
PROGRAMMING
Temperature alarm set points are set up in the analog (metering) “Alarms” menu sec-
tion. Item “9” sets the low and high set points. The entry is a four-digit number with
the first digit being the F or C designator. If the first digit is a “0” then the number
is assumed to be Fahrenheit. If the first digit is a “1” then Celsius is assumed.
Example:
To enter low and high alarm set points of 30F and 95F, enter 0030/0095.
To enter low and high alarm set points of 10C and 40C enter 1010/1040.
Do not
enter the “/”, it will be entered automatically.
Status Setup
When “6” is selected from the PGM Menu, the Status inputs are set up for either
Normally Open or Normally Closed and for the amount of DEBounce time the input
has to be in an “alarm” state for an alarm to be generated.
When “1” is selected from the menu: Make changes or press Escape to accept cur-
rent values. If changes are made, all four values must be entered.