Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
67
Cooler Operation
(cont.)
Water Inlet Solenoid Operation
(cont.)
Water inlet solenoid does not supply water into the tank (empty):
•
Check that the Cooler is turned ON calling for cooling (pump operation) and is not
in an operation delay period i.e. Servoseal delay.
•
Check the water supply tap is turned ON.
•
Check that the water supply pressure is within the operation range (300 kPa -
1000 kPa).
•
Check that an Error 50 (both High and Low Level Water Sensors are open circuit)
is not current.
Check that the water inlet solenoid is energised (240 Volt), at the water
INLET
SOLENOID-ACTIVE
and
INLET SOLENOID-NEUTRAL
terminals, on the service
compartment back wall.
OFF
10 A
V
COM
1000V- - -
750V
V
VOLTS
Multimeter
240
FUSED
INLET VALVE - NEUTRAL
INLET VALVE - ACTIVE