background image

Brivis 

Evap AC IM

READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.

Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, 

property damage, personal injury and/or death�

WARNINGS: WHEN IGNORED, CAN RESULT IN SERIOUS INJURY OR DEATH.

CAUTIONS: WHEN IGNORED, CAN RESULT IN MINOR INJURY OR PRODUCT DAMAGE.

SHALL/MUST/

IMPORTANT: 

INDICATES A MANDATORY REQUIREMENT OF THIS MANUAL.

SHOULD: INDICATES A RECOMMENDED REQUIREMENT OF THIS MANUAL.

Any deviations from these instructions may, at the discretion of Rinnai, void 

the warranty. As a result, the customer and/or installer may be charged a fee for 

product non-warranty related call outs. Also, note that failure to comply with 

these instructions may preclude Rinnai from being able to service the unit.

DISCLAIMER: This document is a guide only. Laws, regulations and industry standards can 

vary between States and Territories. 
Accordingly, this guide MUST BE read in conjunction with, and subject to, all 

laws, regulations and industry standards applicable in the State or Territory in 

which the products are installed. 
You MUST ensure that the installation of the products will comply with those 

laws, regulations and standards, and that the products recommended to 

customers are fit for the purpose for which they are intended.

WARNING

REGULATORY / INSTALLATION / SAFETY

This appliance 

SHALL BE

 installed in accordance with:

Manufacturer’s Installation Instructions�
Current  AS/NZS 3000 (electrical codes)�
Local Regulations and Municipal Building Codes including local OH&S requirements�
Local water authority regulations

Duct fixing regulations, EPA guidelines and AS HB276-2004 “A Guide to Good Practice”

ALWAYS 

comply with the following precautions to avoid dangerous situations and to ensure optimum 

performance�
This appliance 

MUST BE

 installed, maintained and removed by an Authorised Person�

DO NOT 

place any articles on or against this appliance

DO NOT

 use or store flammable materials near this appliance

DO NOT 

spray aerosols in the vicinity of this appliance while it is in operation

DO NOT 

modify this appliance

This appliance is 

NOT

 intended for use by persons (including children) with reduced physical, sensory 

or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or 

instruction concerning use of the appliance by a person responsible for their safety�
Children should be supervised to ensure that they 

DO NOT 

play with the appliance�

IMPORTANT

MODELS COVERED IN THIS MANUAL

Brivis Contour Series

L36

L46

L56

L66

L76

Brivis Promina Series

P36

P46

P56

P66

P76

Brivis Advance Series

F36D

F56D

F76D

Brivis Advance Plus* 

F46DS

F66DS

F86DS

Brivis AD Series

AD66 / AD66D

AD86 / AD86D

Brivis AD BAL Series

AD56 / AD56D AD66 / AD66D

AD 86 

* Brivis Contour and Brivis Advance Plus are fitted with a Motorised Winter-Seal.

IMPORTANT

WARNINGS AND IMPORTANT INFORMATION

Содержание AD BAL AD56

Страница 1: ...Evaporative Air Coolers Installation Manual Brivis Models Contour Series Promina Series Advance Series AD Series by ...

Страница 2: ...AS NZS 3000 Local Regulations and Municipal Building Codes including local OH S requirements This appliance must be installed maintained and removed only by an Authorised Person For continued safety of this appliance it must be installed and maintained in accordance with the manufacturer s instructions ...

Страница 3: ... Cooler 11 6 Installation Brivis Advance 12 6 1 Brivis Advance Series Dropper Duct Specific 12 6 2 Fitting Brivis Advance Series Optional Winter Seal 12 6 3 Fitting the Brivis Advance Unit 12 7 Network Connection 13 7 1 Wiring Connection Brivis Networkers 13 7 2 Installing Dual Brivis Networkers 13 7 3 Dual Brivis Networkers 13 7 4 Master and Slave Addressing 14 7 5 Wiring the Programmable or Manu...

Страница 4: ...d Off 23 12 4 Brivis AD Bleed Rate Settings 23 12 5 Brivis AD Bleed Setting Instructions 24 12 6 Brivis AD Optional Dump Valve Functions 24 13 Brivis AD Timing Cooler Functions 25 13 1 Start up Brivis AD Model Standard 25 13 2 Start up Brivis AD Model with Optional Dump Valve 25 13 3 Pre Wet 25 13 4 Programmable Wall Control Models in auto mode 25 13 5 Shut down Times Optional Dump Valve 25 14 Com...

Страница 5: ...ON SAFETY This appliance SHALL BE installed in accordance with Manufacturer s Installation Instructions Current AS NZS 3000 electrical codes Local Regulations and Municipal Building Codes including local OH S requirements Local water authority regulations Duct fixing regulations EPA guidelines and AS HB276 2004 A Guide to Good Practice ALWAYS comply with the following precautions to avoid dangerou...

Страница 6: ... be installed within a 5m 6m in W A radius of a sanitary vent 1 5m radius from a gas appliance flue terminal and 3m horizontal radius from a wood stove flue terminal 1 4 WEATHER PROOFING All ductwork electrical cables and water pipes MUST BE flashed and sealed to prevent water entry into the building Exposed ductwork MUST BE weatherproofed and coated with reflective aluminium paint 1 5 INSULATION ...

Страница 7: ...gh lock up pressures or freezing water in pipes may occur For the owner s convenience an additional isolating valve may be provided at ground level to isolate the water supply The water supply pipe MUST BE supported and secured so as not to place strain on the Cooler s water connection fittings or cause water hammer noise Water quality should be checked and filtration fitted where necessary e g ta...

Страница 8: ...ak should be fitted with an additional water diverting channel on the dropper duct high side that extends beyond the dropper duct sides by at least 50mm see diagram below NOTE This diagram is for Brivis Promina and Brivis Contour Series Models 3 4 DROPPER DUCT INSTALLATION GUIDELINES The dropper duct on which the Cooler is mounted MUST BE properly secured to the roof structure or timbers Ensure th...

Страница 9: ...g the location of an evaporative cooler Ensure there is a clear pathway from the roof access point to cooler Remain clear of solar panels or other roof mounted fixtures that would adversely affect the required service clearances or safe access to the cooler For Multi Storey Flat Roof Maintain a safe distance from a fall edge 3m Consider installing a roof hatch to avoid extension ladders or two per...

Страница 10: ...eas the 100mm template position is used with the templates placed on the roof tile batten Clamp the templates in position or use a screw or rivet through the template hole provided to securely hold them to the dropper duct Insert the dropper duct between the roof rafters see diagram Ensure the template levelling bracket is positioned on the high roof side of the dropper duct Rest the templates equ...

Страница 11: ... the cooler Lock the other side into place ensuring that they have been placed in the correct direction and that they are both free moving Then proceed with the mounting of the cooler into the dropper duct 5 3 FITTING THE BRIVIS PROMINA BRIVIS CONTOUR SERIES COOLER The Cooler should now be mounted into position Insert the Cooler s air outlet fully into the dropper duct Ensure the Cooler base sits ...

Страница 12: ...ies 5 Winter Seal Installation Instructions provided with the Brivis Series 5 6 Winter Seal kit This Procedure MUST BE completed before the Cooler is mounted onto the dropper duct preferably before the Cooler is lifted up onto the roof Gently lift the unit up so that you can see the Cooler s air outlet On the Winter Seal blades is an orange sticker indicating the bottom This sticker should be faci...

Страница 13: ...ther on a system The Brivis Networkers should be wired in parallel never in series see diagram of typical wiring The two Brivis Networkers are identified as either Master or Slave All Brivis Networkers come set as Master by default and the slave Brivis Networker will need to be configured upon installation NOTE Both Brivis Networkers cannot be set as Master on a system otherwise it will malfunctio...

Страница 14: ...tworker will now become the Slave Brivis Networker and the installer parameters can no longer be accessed from this Brivis Networker The Master Brivis Networker MUST now be used to access the installer parameters 7 5 WIRING THE PROGRAMMABLE OR MANUAL WALL CONTROL After the Cooler s power supply and pre wired wall control leads are fed down from the base into the roof cavity connect the 20 metre wa...

Страница 15: ...ler is configured correctly to the Brivis Networker each Cooler MUST BE Given a different specific identification number starting at No 1 Designated to a zone refer to the Brivis Networker Advanced Programming Manual No 404 Each Cooler comes with the ID number set at number 1 To give it a new number first complete the installation and wiring of all the units as described previously and follow the ...

Страница 16: ...Cooler as shown below by unit number 2 Wait one minute before proceeding to allow for the programming change Press the Brivis Networker ON OFF button to exit the program Turn the power supply at the Cooler OFF to save the new ID number Repeat the sequence for each Cooler Then follow the Brivis Networker Advanced Programming Instructions to allocate the Coolers to their respective zones On Off Butt...

Страница 17: ...table water the manufacturer recommends that the outlet of the discharge pipe is separately drained to avoid any contamination of water intended for potable use If a discharge pipe is required the manufacturer recommends that the outlet is located such that water is adequately dispersed and does not cause nuisance or damage for example gutter overflow and accelerated corrosion Check requirements w...

Страница 18: ...r longer than 15 minutes it will begin with a 2 minute Pre wet then turn OFF the pump and start the fan Depending on the room conditions and the wall control setting the Cooler may perform another Pre Wet as described previously when the pump is turned ON again forcing the fan to turn OFF for that period 9 4 TANK WATER QUALITY AND REPLENISHMENT DURING OPERATION During the Cooler s operation with t...

Страница 19: ...NG THE SIDE PADS Remove the front and back pads as above then Disconnect the 19mm clear hose supplying water to the roof distribution spreader at the fitting in the cooler s base squeeze clip then pull to release Ensure that all thumb screws have been removed Remove the roof assembly Slide the filter pads up and out of their frames 10 3 DISMANTLING THE FRAMEWORK Complete all the steps above then F...

Страница 20: ... inside of the dropper duct Cut a 43 mm hole in the dropper duct below the roof line on the back left hand side on the high side of the roof to accept the wiring grommet This will allow the 3 pin plug and lead and the Wall Control Loom connection lead to be withdrawn from the duct into the roof cavity 11 2 INSTALLING THE DROPPER DUCT AND FITTING THE BRIVIS AD COOLER Place the Cooler on the dropper...

Страница 21: ...agram below Rotate the fold up corner up until the frame aligns with the marked lines allowing fitting tabs to jam tight against the dropper duct sides Check again that the large 45º fold up is in the correct corner as per previous instructions Align the top edge on the marked lines and drill through frame holes from inside to out Pop rivet or screw from outside to in making sure screw or rivet ta...

Страница 22: ... internal and can be accessed by removing a screw from the top of the control then removing the top access panel The Programmable Controller Route the wall control wire loom to the wall control mounting position ensure mount position is within reach of 20 m loom Remove cable puller from the loom Plug wire loom onto the back of the wall control and then fix control to mounting plate Mains Power Sup...

Страница 23: ...er level setting as water returns to the tank from the pads 12 3 BRIVIS AD BLEED OFF To ensure the water in the tank is clean and fresh a small amount continuously flows from the unit during operation This is called bleed off This prevents a build up of salts and minerals in the tank which can accelerate filter pad and component deterioration by constantly topping it up with fresh water The rate o...

Страница 24: ...empties the tank after the Cooler is turned OFF leaving it dry When using the Cooler again refilling the tank will take 4 minutes before Pre Wet begins When the Cooler is turned OFF at the end of use the Dump Valve will wait 45 minutes before turning OFF the water supply and draining the tank If the Cooler is in continuous operation the Dump Valve will flush the tank automatically after 35 hours o...

Страница 25: ... saturation and optimum cooling potential when the fan starts Pump OFF Time Pre wet Time Less than 10 minutes Pre Wet 1 minute Longer than 10 minutes Pre Wet 4 minutes Longer than 45 minutes Dump Model Only Tank has to be filled Therefore total time including Pre Wet is 8 minutes 13 4 PROGRAMMABLE WALL CONTROL MODELS IN AUTO MODE These models operate similar to Brivis Networker and Manual wall con...

Страница 26: ...only The isolating valve on the water supply is turned ON The water tank fills with water and the water inlet valve closes when the tank is full The water level is set correctly Brivis AD Models There is no foreign matter in the water tank or fan housing The pads are correctly located The pump operates when turned ON at the Wall Control The fan operates through the entire speed range For even wate...

Страница 27: ... is correctly located in the power socket For power at the power socket plug in another appliance and test The isolating switches at the unit and the supply power socket are turned ON The unit is turned ON at the Brivis Networker Wall Control The pump is not in a delay due to ServoSeal damper or tank filling operation Brivis Promina Brivis Contour Brivis Advance Brivis AD Dump Models The filter ba...

Страница 28: ...ber of average size windows doors suggestions only Highest Fan Setting Lowest Fan Setting Contour Series Promina Series Advance Series Advance Plus AD Series L36 P36 F36D One door and a hinged window 1 9 m2 1 1 m2 L46 P46 P56 F56D F46DS AD56BAL AD56DBAL Three sliding windows or one door two hinged windows 2 3 m2 1 4 m2 L56 P66 F66DS AD66 BAL AD66D BAL Four sliding windows or one door and four hing...

Страница 29: ... s which are no longer Networker compatible Angle of Dropper Box Dropper Box Size Minimum Dropper Box Length Fan Impellor Blades Water Connection nk acity es Dump Drain Connection 2 315 2 4 6 Flexible hose connection with 1 2 BSP thread with 1 2 BSP thread with 1 2 BSP thread with 1 2 BSP thread with 1 2 BSP thread with 1 2 BSP thread with 1 2 BSP thread with 1 2 BSP thread with 1 2 BSP thread wit...

Страница 30: ...rogrammable or Manual wall control except AD s which are no longer Networker compatible Angle of Dropper Box Dropper Box Size Minimum Dropper Box Length Fan Impellor Blades Water Connection k city s Dump Drain Connection 315 2 4 6 Flexible hose connection with 1 2 BSP thread with 1 2 BSP thread with 1 2 BSP thread with 1 2 BSP thread with 1 2 BSP thread with 1 2 BSP thread with 1 2 BSP thread with...

Страница 31: ...Brivis 31 Evap AC IM NOTES ...

Страница 32: ... higher from mobile or public phones For further information visit www rinnai com au or email enquiry rinnai com au Rinnai has a Service and Spare Parts network with personnel who are fully trained and equipped to give the best service on your Rinnai appliance If your appliance requires service please call our National Help Line Rinnai recommends that this appliance be serviced every 2 years With ...

Отзывы: