Centipede 2
®
Module System Instructions
4
BriskHeat
®
Corporation. All rights reserved
INTRODUCTION
Your Centipede 2
®
Temperature Control System supplies a complete network of
temperature control by providing a controller and sensor to EACH heater in a
system. A Centipede 2
®
Module Unit is a compact PID temperature controller
with RTD feedback. Multiple modules can be networked together with CAT5
communication cables. The Centipede 2
®
Touchscreen Interface Unit acts as a
Modbus master for up to 128 Centipede 2
®
Modules. This unit displays real-time
data for all zones and allows a user to modify the major settings, such as set-
point in the Centipede 2
®
Modules.
For successful operation of this system, read these instructions prior to use.
General Specifications
•
PID-auto-tuned control for each zone: Receives set-point through
communication link and stored in nonvolatile memory (retains settings if
power is interrupted)
•
Quickly and easily program the following parameters (individually or
globally across system): Temperature set-point, high-limit alarm
temperature, and low-limit alarm temperature
•
Operator interface displays actual temperature, power duty cycle of
heater, and time / date stamped alarm messages in real-time.
•
Automatically assigned zone addresses
•
Up to 3.5 Amps for UL (for C2MOD-C) @ 240VAC per control zone
•
Up to 2.0 Amps @ 100VAC to 240VAC for C2MOD-OI-7
•
Temperature sensor: RTD Platinum 100 ohm, DIN 385 curve, class B
•
Sensor accuracy: ±1.8°F (1.0°C)
•
Temperature control range: 0 to 320°C (Displayed in °C)
•
Maximum high-limit: 325°C
•
Capable of communication with a PLC or external computer
•
Ability for data streaming to a central monitoring system
•
Alarm latch safety feature: Optional setting for heaters to power off in
the event of an alarm condition. To reactivate, user unlatches heaters
through operator interface or PLC
•
Dry contact master alarm relay: NO or NC (Normally Open or Normally
Closed)
•
Environmental temperature: 35 to 131°F (2 to 55°C)
•
Storage temperature: -40 to 185°F (-40 to 85°C)
•
Ambient humidity: 5 to 95% (non-condensing)
•
C2MOD-OI-7 is a UL Listed Product on UL File E240000
SAVE THESE INSTRUCTIONS!
Additional copies of this manual are available upon request
Содержание C2MOD-OI-7
Страница 33: ...Centipede 2 Module System Instructions BriskHeat Corporation All rights reserved 33...
Страница 34: ...Centipede 2 Module System Instructions 34 BriskHeat Corporation All rights reserved...
Страница 35: ...Centipede 2 Module System Instructions BriskHeat Corporation All rights reserved 35...