APPENDIX 1: FUSE REPLACEMENT
Fuse should be replaced with properly rated fuse: 2 AMP @ 240VAC max.
Do not replace fuse with live power applied to Centipede 2
®
.
Only authorized personnel should replace fuse.
1. Remove power from unit.
2. Replace the blown fuse with a new one of the specified amperage.
3. Apply power to unit.
4. If replacement fuse immediately fails, contact BriskHeat for more information
concerning your issue.
Left Side View
Fuse Location