12.  Enter the desired deviation alarm tolerance.  The deviation alarm is an 

alarm  point that changes with the temperature set point.  If this alarm point 
is  exceeded, the alarm horn sounds and ALARM displays in the zone 
operating  screen. 

13.  Enter the desired shutdown alarm tolerance.  The shutdown alarm is an 

alarm point that changes with the temperature set point.  If this alarm point 
is  exceeded, the alarm horn sounds and the controller aborts the cure cycle. 
A  notification of the cycle abort displays in the zone screen. 

14.  Enter the vacuum high and low alarm set points.  The alarm sounds and 

ALARM displays in the zone operating screen if either of these points are 
exceeded.  Exceeding either of the vacuum alarm points does not cause the 
controller to abort the cure cycle. 

15.  Specify active and inactive thermocouples.  Active thermocouples are 

indicated by a check mark in the check box next the corresponding 
thermocouple number.  Touch the check boxes to remove the check mark 
from the inactive thermocouples. 

16.  Press the CONTINUE TO STEP 3 button. 

© BriskHeat

®

 Corporation.  All rights reserved.

 

 

18 

ACR

®

3 MiniPRO™ Hot Bonder 

 

 

 

 

 

 

 

 

 

 

 

 

18.  Fill in all fields to the desired setting. Touch FINISH when complete.: 



Ramp Rate: 

the heat up rate in degrees per minute from starting 

temperature to Dwell Temperature. 



Dwell Temp: 

the temperature the program is to hold for the 

programmed length of time 



Dwell Time: 

the length of time to hold at the programmed Dwell 

Temperature. 



Cool Down Rate: 

the rate in degrees per minute from the last dwell 

temperature to the End of Cycle Temp. 

NOTE: Since the Hot Bonder cannot force an object to cool down faster than 

the  physical conditions will allow, both high temperature alarms are 
disabled  during the cool down phase. 



End of Cycle Temp: 

the temperature at which the cure is considered 

complete. 

NOTE: The end of cycle temperature must be above the ambient 

temperature for  it to complete. 

 

Содержание ACR 3 MiniPRO Hot Bonder

Страница 1: ...while Running 20 Change Program Password 20 System Menu 21 Save a Single Log File to USB Drive 21 Save All Log Files to USB Drive 22 Delete a Single Log File 22 Delete All Log Files 22 Save a Single...

Страница 2: ...ilure to observe these warnings may result in electric shock risk of fire and personal injury or death Inspect hot bonder before use Do not use hot bonder if damaged Do not repair damaged or faulty ho...

Страница 3: ...ply voltage fluctuations up to 10 of the nominal voltage Transient over voltages typically found on a Category II power source i e a lighting circuit Frequency 50 60Hz 20 amps maximum per zone Maximum...

Страница 4: ...insert The connectors are keyed to prevent improper connections 3 Turn the locking ring clockwise 1 2 turn to lock the cord into place The cord must be fully inserted and locked for proper operation R...

Страница 5: ...Version Number The newest version of the software can be found at www briskheat com Do not touch touchscreen with sharp objects or marking objects such as pens pencils markers etc These objects cause...

Страница 6: ...n displays 5 Enter the necessary repair data or skip by pressing ENTER 6 To enter the repair data touch the data field to be entered 7 Using the keyboard on the data entry screen enter the required da...

Страница 7: ...Corporation All rights reserved 14 ACR 3 MiniPRO Hot Bonder Alarms If all conditions are inside the programmed limits while a zone is running the zone tab is green If while running any condition exce...

Страница 8: ...hen ramps down DUAL The hot bonder ramps once to a first set point holds for the programmed length of time ramps to a second set point holds for the programmed length of time then ramps down TRIPLE Th...

Страница 9: ...uples Active thermocouples are indicated by a check mark in the check box next the corresponding thermocouple number Touch the check boxes to remove the check mark from the inactive thermocouples 16 P...

Страница 10: ...1 Access the PROGRAM menu 2 Select the program to delete by touching the drop down menu for STORED PROGRAM NAME 3 Touch DELETE button to delete program 4 Touch YES to confirm BriskHeat Corporation Al...

Страница 11: ...USB Drive This function saves all stored log files to a USB flash disk thumb drive This data can be transferred to a PC for analysis or archiving NOTE The ACR MiniPro Hot Bonder is capable of storing...

Страница 12: ...programs in its internal memory 1 Access the SYSTEM menu 2 Touch LOAD PROGRAMS FROM USB DRIVE button 3 Insert USB flash drive thumb drive in USB port located on the operator console Touch OK button 4...

Страница 13: ...NEW PASSWORD field A keyboard screen appears 8 Re type your new administrator password Touch the ENTER button when done 9 Touch the UPDATE ADMIN PASSWORD button NOTE System is in administrator mode un...

Страница 14: ...under this warranty shall be limited to the repair or replacement at BriskHeat s option of any parts of the product which may prove defective under prescribed use and service following BriskHeat s exa...

Отзывы: