  5.   On the outside of the enclosure, loop and secure the 

antenna cable with a wire tie as shown in (Figure 3) to 

help prevent water from entering the unit. 

Figure 3

  6.  Route the antenna cable toward the intended mounting 

location of the cellular unit.

Mount Cellular Unit

Clean the mounting surface for the cellular unit with an 

alcohol wipe or other cleaning solution. Peel the covering 

from the adhesive strip on the back of the unit, then firmly 

press the unit in place. Connect the antenna cable at this 

time. 

Install Sensors

Before installing this detector, AC power should be 

disconnected (turned off) for all connection points.

NOTICE

  The sensor is designed to sense ONLY one (1) 

phase/leg of AC voltage. If the sensor is too close to another 

phase/leg the sensor may pick up the voltage from the other 

phase and cancel out the signal. Make sure to put the AC 

sensor on the opposite side of the conductor and away from 

any other phases.

AC Voltage Sensors Utility Voltage Sensing

  1.  Attach the AC voltage sensor to an insulated “hot” 

conductor that is supplying normal utility voltage. 

Typical connection points are the utility power source 

for the battery charger, the block heater, utility power 

sensing from the ATS or a load center in the generator 

enclosure. Put the sensor onto the outside of the 

conductor. Secure the sensor with electrical tape and 

zip tie the sensor wires as needed.

 

  DO NOT use zip ties directly on the sensor as it may 

damage the sensor board.

  2.  Connect the sensor to the cellular harness “utility” 

connector.

Generator Voltage Sensing

  1.  Attach the AC voltage sensor to an insulated “hot” 

conductor on the OUTPUT side of the generator main 

line circuit breaker. Put the sensor onto the outside of 

the conductor. Secure the sensor with electrical tape 

and zip tie the sensor wires as needed.

 

  DO NOT use zip ties directly on the sensor as it may 

damage the sensor board.

  2.  Connect the sensor to the cellular harness “generator” 

connector.

Fault Detection

  1.  Find the fault relay or contact that signals a fault on the 

generator. Consult the generator manual for fault relay’s 

location.

  2.  Find the blue “Fault Active High” (F-AH) and yellow 

“Fault Active Low” (F-AL) wires on the cellular harness.

  3.  Determine if the fault signal from the generator 

switches to GROUND or +12V.

 

  If GROUND, cut and strip the yellow “Fault Active Low” 

(F-AL) wire and connect it to the fault contact.

 

  If +12V, cut and strip the blue “Fault Active High” 

(F-AH) wire and connect it to the fault contact.

   NOTICE

  A second wire may be needed if the Fault 

Active Low (F-AL) is not connected to ground or if the 

Fault Active High (F-AH) is not connected to the other 

side of the fault contact to +12V.

  4.  Connect the ring terminals to the battery.

   •   

NOTICE

  for Briggs and Stratton© generators with a 

GC1031 controller connect the blue “Fault Active High” 

(F-AH) wire to pin 6 “DIG O/P D” on the back of the 

controller. Make sure the screw connection is tight on 

the connector.

Close Generator and Install Fuses

  1.  Use the supplied wire ties to organize the harness wires 

and to secure excess wire lengths.

  2.  Install all the components that were removed.
 3. Connect negative battery cable to negative battery 

terminal, indicated by NEGATIVE, NEG, or (

-

).

  4.  Install the fuses into the transfer switch.
  5.  Install the generator fuse.
  6.  Set generator circuit breaker to 

ON

.

  7.  Set generator system switch to 

AUTO/Standby

.

Not for 

Reproduction

Содержание infohub 6574

Страница 1: ...ll Technical Services 1 833 463 6482 Monday Friday 8 00 am to 5 00 pm Central Time 80080980 Revision A Copyright Briggs Stratton Corporation Milwaukee WI USA All rights reserved Wireless Monitoring For Standby Generators Model 6574 N o t f o r R e p r o d u c t i o n ...

Страница 2: ... Ties B Rubber Grommet C Cellular Unit D Harness E Voltage Sensor F Antenna G Washer H Tape J Splice Items needed to install the kit Drill with 3 8 inch bit Alcohol wipes or other cleaning solution Standard and Phillips screwdrivers Volt meter or multimeter Wire cutter stripper De burring Tool Rust Inhibitor B C D F G H E A J Figure 1 N o t f o r R e p r o d u c t i o n ...

Страница 3: ...wires or bare receptacles DO NOT use generator with electrical cords which are worn frayed bare or otherwise damaged DO NOT handle generator or electrical cords while standing in water while barefoot or while hands or feet are wet If you must work around a unit while it is operating stand on an insulated dry surface to reduce the risk of a shock hazard DO NOT allow unqualified persons or children ...

Страница 4: ...rom the main generator 4 Utility voltage is present at generator control panel Remove the fuses from the transfer switch to disconnect power before servicing the control panel 5 Disconnect negative battery cable from negative battery terminal indicated by NEGATIVE NEG or NOTICE Only existing wire harness holes should be used to route the InfoHub harness when possible Except for the antenna cable h...

Страница 5: ...insulated hot conductor on the OUTPUT side of the generator main line circuit breaker Put the sensor onto the outside of the conductor Secure the sensor with electrical tape and zip tie the sensor wires as needed DO NOT use zip ties directly on the sensor as it may damage the sensor board 2 Connect the sensor to the cellular harness generator connector Fault Detection 1 Find the fault relay or con...

Страница 6: ...egistration and activation support call the InfoHub support team at 1 833 463 6482 Prior to installation record the module ESN and P N in the spaces below This information is required to correctly assign the module to the equipment in the user portal InfoHub ESN P N Equipment Brand Equipment Type Model Number Serial Number Minimum System Requirements User Portal Supported Browsers and Versions Chr...

Страница 7: ...r Information THIS EQUIPMENT HAS BEEN TESTED AND FOUND TO COMPLY WITH THE LIMITS FOR A CLASS B DIGITAL DEVICE PURSUANT TO PART 15 OF THE FCC RULES THESE LIMITS ARE DESIGNED TO PROVIDE REASONABLE PROTECTION AGAINST HARMFUL INTERFERENCE IN A RESIDENTIAL INSTALLATION THIS EQUIPMENT GENERATES USES AND CAN RADIATE RADIO FREQUENCY ENERGY AND IF NOT INSTALLED AND USED IN ACCORDANCE WITH THE INSTRUCTIONS ...

Страница 8: ...ase receipt If you do not provide proof of the initial purchase date at the time warranty service is requested the manufacturing date of the product will be used to determine the warranty period Product registration is not required to obtain warranty service on Briggs Stratton products ABOUT YOUR WARRANTY Warranty service is available only through Briggs Stratton Authorized Service Dealers Most wa...

Страница 9: ...cnicos al 1 833 463 6482 De lunes a viernes de 8 00 a 17 00 horario central 80080980 Revisión A Derecho de autor Briggs Stratton Corporation Milwaukee WI EE UU Todos los derechos reservados Monitoreo inalámbrico para Generadores de Energía de Emergencia Modelo 6574 N o t f o r R e p r o d u c t i o n ...

Страница 10: ... C Unidad de celular D Arnés E Sensor de voltaje F Antena G Arandela H Cinta J Empalme Elementos necesarios para la instalación del kit Perforadora con broca de 3 8 pulgada Paños empapados en alcohol u otra solución de limpieza Destornilladores estándares y phillips Voltímetro o multímetro Cortador de cables Pelacables Herramienta para quitar rebabas Producto inhibidor de óxido B C D F G H E A J F...

Страница 11: ...O toque cables ni receptáculos sin aislamiento NO use el generador si tiene cables eléctricos gastados rotos pelados o dañados de cualquier forma NO manipule el generador ni los cables eléctricos si está en contacto con agua descalzo o si sus manos o pies están mojados Si debe trabajar cerca de una unidad mientras está funcionando párese en una superficie seca y aislada para reducir el peligro de ...

Страница 12: ...r en la posición de APAGADO 3 Retire el fusible del generador principal 4 El panel de control del generador recibe tensión del suministro eléctrico de la red pública Desconecte la energía eléctrica antes de realizar mantenimiento en el panel de control para esto retire los fusibles de la llave de transferencia 5 Desconecte el cable negativo de la batería del terminal negativo de la batería con la ...

Страница 13: ...r caliente aislado en el lado de SALIDA del disyuntor de circuito de línea principal del generador Coloque el sensor en el lado externo del conductor Asegure el sensor con cinta eléctrica y coloque precintos en los cables del sensor según sea necesario NO use precintos directamente sobre el sensor ya que podría dañar el panel del sensor 2 Conecte el sensor al conector de los cables de la unidad ce...

Страница 14: ...tivación llame al equipo de soporte de InfoHub al 1 833 463 6482 Antes de la instalación grabe el módulo ESN y P N en los espacios a continuación Esta información es necesaria para asignar correctamente el módulo al equipo del portal del usuario InfoHub ESN P N Equipo Marca Tipo de equipo Número de modelo Número de serie Requerimientos mínimos del sistema Portal de usuario Navegadores que soporta ...

Страница 15: ...rmación de usuario FCC ESTE EQUIPO FUE PROBADO Y SE CONFIRMÓ QUE CUMPLE CON LOS LÍMITES PARA UN DISPOSITIVO DIGITAL DE CLASE B EN CUMPLIMIENTO CON LA PARTE 15 DE LAS NORMAS FCC ESTOS LÍMITES ESTÁN DISEÑADOS PARA BRINDAR PROTECCIÓN RAZONABLE CONTRA INTERFERENCIAS DAÑINAS EN UNA INSTALACIÓN RESIDENCIAL ESTE EQUIPO GENERA USA Y PUEDE IRRADIAR ENERGÍA DE RADIOFRECUENCIA Y SI NO SE INSTALA Y USA CONFOR...

Страница 16: ...rde el recibo comprobante de compra Si no se proporciona una prueba de la fecha de compra inicial en el momento se solicitar servicio de garantía se utilizará la fecha de fabricación del producto para determinar el período de garantía No es necesario el registro del producto para obtener el servicio de garantía de los productos Briggs Stratton ACERCA DE LA GARANTÍA El servicio de garantía solo est...

Страница 17: ...hnique au 1 833 463 6482 du lundi au vendredi de 8 h à 17 h heure normale du Centre 80080980 Révision A Copyright Briggs Stratton Corporation Milwaukee WI États Unis Tous droits réservés Moniteur de surveillance sans fil pour groupe électrogène fixe Modèle 6574 N o t f o r R e p r o d u c t i o n ...

Страница 18: ...n caoutchouc C Appareil cellulaire D Faisceau E Capteur de tension F Antenne G Rondelle H Ruban J Épissure Articles nécessaires pour l installation de la trousse Perceuse avec une mèche de 3 8 pouce Tampon imbibé d alcool ou autre solution de nettoyage Tournevis à pointes plate et cruciforme Voltmètre ou multimètre Coupe fils dénudeur de fils Outil pour ébavurer Inhibiteur de rouille B C D F G H E...

Страница 19: ...N utilisez PAS la génératrice avec des rallonges électriques usées effilochées dénudées ou autrement endommagées NE PAS manipuler la génératrice ou les cordons électriques les pieds dans l eau ou les pieds nus ou lorsque les mains ou les pieds sont mouillés Si vous devez travailler aux environs d une unité alors qu elle est en marche placez vous sur une surface sèche isolée afin de réduire les ris...

Страница 20: ...fusible de la génératrice principale 4 De la tension de service est présente au tableau de commande de la génératrice Retirer les fusibles du commutateur de transfert pour déconnecter l alimentation avant d effectuer l entretien du tableau de commande 5 Débranchez le câble négatif de la batterie de la borne négative de la batterie marquée NEGATIF NEG ou AVIS Seuls les trous de faisceaux en place d...

Страница 21: ...solé sous tension sur le côté SORTIE du disjoncteur de la ligne principale de la génératrice Mettre le détecteur sur l extérieur du conducteur Fixer le détecteur avec du ruban électrique et attacher les câbles du détecteur avec un collier de serrage au besoin NE PAS utiliser de collier de serrage directement sur le détecteur ce qui risque d endommager la carte du détecteur 2 Connecter le détecteur...

Страница 22: ...ipe de soutien à la clientèle d InfoHub au 1 833 463 6482 Avant l installation inscrivez le ESN et le P N du module dans les espaces ci dessous Ces renseignements sont requis pour correctement attribuer le module à l équipement dans le portail d utilisateur InfoHUB ESN P N Équipement Marque Type d équipement Numéro de modèle Numéro de série Exigences système minimales Portail d utilisateur Navigat...

Страница 23: ...MITES D INTERFÉRENCES RELATIVES AUX APPAREILS NUMÉRIQUES DE CLASSE B DE LA SECTION 15 DU RÈGLEMENT DE LA FCC CES LIMITES SONT ÉLABORÉES DANS LE BUT DE FOURNIR UNE PROTECTION RAISONNABLE CONTRE LES INTERFÉRENCES NUISIBLES DANS UNE INSTALLATION RÉSIDENTIELLE CET ÉQUIPEMENT GÉNÈRE UTILISE ET ÉMET DES RADIOFRÉQUENCES ET PEUT CAUSER DES INTERFÉRENCES NUISIBLES AUX COMMUNICATIONS RADIO LORSQU IL N EST P...

Страница 24: ...adre de cette garantie Afin d assurer une couverture totale et rapide de la garantie enregistrez votre produit sur le site Web indiqué ci dessus ou sur www onlineproductregistration com Conservez votre reçu d achat comme preuve Si vous n avez pas de preuve de la date de l achat initial au moment de la demande d un service en vertu de la garantie la date de fabrication du produit sera utilisée pour...

Отзывы: