INSTALLATION

 cont.

NOTICE 

If stepper motor does not move, check 

that electrical connections are secure

Figure 24 

Mixer Assembly

Figure 25 

Stepper Motor (In Battery Compartment)

Electronic Governor System

The engine electronic governor system allows for improved 

control and increased generator performance compared to 

mechanically governed systems. The system also reduces 

speed variations under engine loading and unloading and 

significantly reduces frequency fluctuation experienced 

when the engine is under higher loads. 

 

The electronic governor system is composed of: 

A. Throttle side linkage 

B. Stepper motor 

C. Stepper motor throttle control linkages
     See Figures 24 and 25. 

 

The control board contains a digital controller that  

processes engine speed information and sends 

appropriate commands to the stepper motor to control 

position of the engine throttle. 

 

Since the electronic governing system controls the engine 

throttle demand based upon generator load, the following 

service codes and/or conditions may be related to an 

electronic governing system issue. 

Service Codes:

•  ENGINE DOES NOT START

•  ENGINE OVER SPEED

•  LOW FREQUENCY

•  GENERATOR SENSE FAULT

Fault Conditions:

•  Unstable no-load engine control

•  Overload or short on generator output

•  Throttle linkage malfunction

•  Non-functional AVR (Automatic Voltage Regulator)

•  Generator sensing wire disconnection

While trouble shooting any of these codes or conditions, 

a verification of the electronic governor system can be 

initiated through the control panel - Advanced Menu options 

- Electronic Governor Check. See 

Advanced Settings 

Screen 

section.

Electronic Governing Check

The generator has an electronic governing check feature that 

will turn on the stepper motor and move the throttle linkage 

clockwise and counterclockwise within the throttle limits. The 

test will rotate the stepper motor and move the throttle arm 

between the wide open throttle and dead idle limits 4 times 

with a 2 second delay between each throttle sweep. This will 

allow visual verification that the stepper motor is functioning 

 

properly and the control linkages are connected. The 

engine will not attempt to start during this test. If the stepper 

motor does not move, or if a linkage binds, service may be 

required. 

Содержание 14000 Series

Страница 1: ...o t f o r R e p r o d u c t i o n Generator Home Generator Systems Installation Instructions Series 14000 Copyright Briggs Stratton Corporation Milwaukee WI USA All rights reserved 80010856 Revision...

Страница 2: ...low the instructions completely Where to Find Us You never have to look far to find support and service for your generator Consult your Yellow Pages There are many Briggs Stratton authorized service d...

Страница 3: ...Consumption 22 LP Vapor Propane 22 Natural Gas 22 Fuel Pressure 22 Power Loss 22 Fuel Pipe Sizing 22 Fuel Conversion 22 System Connectors 23 Grounding the Generator 24 Generator Power Connection 24 U...

Страница 4: ...with a low level of risk which if not avoided could result in minor or moderate injury NOTICE The manufacturer cannot possibly anticipate every possible circumstance that might involve a hazard The wa...

Страница 5: ...on monoxide detectors cannot detect smoke Do allow sufficient room on all sides of generator for maintenance and servicing DO NOT Do not use with or substitute the flexible fuel line provided with any...

Страница 6: ...ing in water while barefoot or while hands or feet are wet In case of an accident caused by electrical shock immediately shut down the source of electrical power and contact the local authorities or e...

Страница 7: ...permit leakage Do not leave combustible materials in the generator compartment Do not operate engine if smell of fuel is present or other explosive conditions exist Do not smoke around generator Do n...

Страница 8: ...equipment Do not work on the equipment when you are physically or mentally fatigued 8 If connected devices overheat turn them off and disconnect them from generator 9 Do not modify generator in any wa...

Страница 9: ...freight bill and affix his signature under the consignor s memo of loss or damage If loss or damage is noted after delivery separate the damaged materials and contact the carrier for claim procedures...

Страница 10: ...mmendations Smoke alarms cannot detect carbon monoxide gas Smoke detector s MUST be installed and maintained indoors according to the manufacturer s instructions recommendations Carbon monoxide alarms...

Страница 11: ...l wiring is rated for 600V See Communication Connections Dipswitches in most transfer switches must be set to correspond to the wattage of the generator See Transfer Switch Operator Installation Manua...

Страница 12: ...N o t f o r R e p r o d u c t i o n 12 This page intentionally left blank...

Страница 13: ...ng requirements which must be satisfied before the instal lation is complete There are two equally important safety concerns in regards to carbon monoxide poisoning and fire There are also several gen...

Страница 14: ...ements INSTALLATION cont A Figure 3 Carbon Monoxide Detector F C D B G E Figure 4 Carbon Monoxide Gas entries The letters shown above in Figure 4 indicate POTENTIAL points of entry for Carbon Monoxide...

Страница 15: ...ng structure window doors ventilation intakes soffit vents crawl spaces open garage doors or other openings where exhaust gas could accumulate and enter inside or be drawn into potentially occupied bu...

Страница 16: ...ion over 0 3 m in height Do locate the weatherproof enclosure a minimum of 1 5 m overhead clearance from any structure overhang or trees Do ONLY use flexible fuel line provided Connect provided fuel l...

Страница 17: ...structure overhang or trees Standby Standby Standby Standby Exhaust Direction Exhaust Direction Exhaust Direction Exhaust Direction 46 cm min 46 cm min 46 cm min NOTICE DO NOT place weatherproof encl...

Страница 18: ...he electrical inlet This inlet may be enlarged or supplemented to accommodate a maximum conduit size of 38 mm Ensure that the installed conduit s enter the generator in the zone B shown in the figure...

Страница 19: ...fting pipes with a spreader bar The proper use of a spreader bar will prevent damage to the generator enclosure DO NOT touch the roof when lifting the generator Concrete Anchoring In areas prone to hi...

Страница 20: ...identical keys These keys fit in the lock on the front panel The roof must be unlocked in order for it to open To Open the Roof 1 Insert key into lock B of front panel Gently push down on roof above...

Страница 21: ...d conditions with all gas appliances connected to the fuel system turned on and operating Use a pipe sealant or joint compound approved for use with NG LPG on all threaded fittings to reduce the possi...

Страница 22: ...ea level and 1 for each 5 6 C above 25 C Fuel Pipe Sizing There are numerous on line or otherwise published references for fuel pipe sizing Consider the specific gravity of gas and compensate for a no...

Страница 23: ...00V 90 C copper wire Torque terminals to 0 5Nm B Fault Contacts Use NO COM and NC to connect an alarm to alert user in case of a fault Contacts reverse state NO goes to NC and vice versa upon a fault...

Страница 24: ...e respective country When power on these leads is lost the generator will start Communication Connections Connect the applicable communication leads to the automatic transfer switch as shown in the ta...

Страница 25: ...y If you must work around a unit while it is operating stand on an insulated dry surface to reduce risk of shock hazard Despite the safe design of the generator operating this equipment imprudently ne...

Страница 26: ...ize internal temperatures shuts off the generator and waits for the next utility outage OFF Turns off running generator prevents it from starting and resets any detected fault conditions To reset serv...

Страница 27: ...D RESETS ANY DETECTED FAULTS AUTOMATIC MODE NORMAL OPERATING POSITION PRESS AND HOLD BUTTON TO PUT GENERATOR INTO AUTOMATIC MODE IF A UTILITY POWER OUTAGE IS SENSED THE SYSTEM WILL START THE GENERATOR...

Страница 28: ...r or or DAY OF WEEK FLASHING HOURS FLASHING MINUTES FLASHING AM PM FLASHING SET EXERCISE CYCLE EVENT LOG Display will scroll last service code event date time and ambient temperature of when the event...

Страница 29: ...l scroll across the digital display and then move to the next item Run time Date Time Exercise Cycle date and start time Press the LEFT ARROW or RIGHT ARROW at any time to move to the next item Press...

Страница 30: ...ator for the first time For advanced menu items press and hold the left arrow right arrow and escape key for 3 seconds Follow the prompts as outlined below INSTALLATION cont NOTICE In the Advanced Set...

Страница 31: ...API SJ of viscosity 5W30 is required Battery The installer must supply and install a rechargeable starting battery The starting battery MUST conform to the specifications shown below in the chart Bat...

Страница 32: ...r 2 Connect an accurate frequency meter to line side of generator s main circuit breaker 3 Set generator s main circuit breaker to ON closed position 4 Verify manual shutoff valve is open 5 Install 15...

Страница 33: ...r conditions may be related to an electronic governing system issue Service Codes ENGINE DOES NOT START ENGINE OVER SPEED LOW FREQUENCY GENERATOR SENSE FAULT Fault Conditions Unstable no load engine c...

Страница 34: ...3 seconds Follow prompts shown in Figure 19 General Set Up Screen Setting Exercise Timer The generator is equipped with an exercise timer During the exercise period the generator runs for 20 minutes...

Страница 35: ...erates are between 10 to 20 off the LP gas rating ENGINE SPECIFICATIONS Displacement 993 cc Bore 85 5 mm Stroke 86 5 mm Spark Plug Gap 0 51 mm Spark Plug Torque 20 Nm Armature Air Gap 0 13 0 20 mm Int...

Страница 36: ...N o t f o r R e p r o d u c t i o n 36 SCHEMATIC DIAGRAM...

Отзывы: