Gaseous Fuel System

 

 

 

 

 

Before Installing Fuel System

Consult with the user regarding any technical considerations 

that might affect their installation plans. The entire flexible 

steel fuel line must be visible for periodic inspection and 

must not be concealed within nor contact or run through any 

wall, floor, or partition. The piping should be of a material 

that conforms to national rules and regulations of the 

respective country, rigidly mounted and protected against 

vibration.

Piping should be protected from physical damage where 

it passes through flower beds, shrub beds, and other 

cultivated areas where damage could occur.
1.   Install the flexible steel fuel line 

(B)

 (supplied) between 

the generator fuel inlet port 

(A) 

and rigid piping. This 

will prevent thermal expansion, contraction, or any 

generator movement from causing excessive stress on 

the piping material.

2.   A union 

(C)

 or flanged connection shall be provided 

downstream to permit removal of generator.

3.   A manometer port should be provided 

(D)

 to enable 

measurement of fuel pressure. A digital manometer, 

Part Number 19495, is available at your local Briggs & 

Stratton authorized service provider. When the initial 

test runs are completed, the manometer is removed and 

the port is plugged.

4.   The termination of hard piping should include a 

sediment trap 

(F)

 where condensate is not likely to 

freeze. Where formation of hydrates or ice is known to 

occur, piping should be protected against freezing.

5.   A minimum of one accessible, approved manual shutoff 

valve

 (E)

 shall be installed in fuel supply line per 

national rules and regulations of the respective country.

Piping must be of the correct size to maintain the required 

supply pressures and volume flow under varying generator 

load conditions with all gas appliances connected to the fuel 

system turned on and operating. 
Use a pipe sealant or joint compound approved for use with 

NG/LPG on all threaded fittings to reduce the possibility of 

leakage.
Where local weather conditions include earthquake, 

tornado, unstable ground, or flood hazards, special 

consideration shall be given to increase strength and 

flexibility of piping supports and connections. 
Purge and leak test the installed piping in accordance with 

applicable national rules and regulations of the respective 

country.

INSTALLATION

 cont.

NOTICE 

Use the following information to plan the gaseous 

fuel system installation. This information 

DOES 

NOT

 override applicable national rules and 

regulations of the respective country. Consult with 

your local fuel supplier or Fire Marshall if questions 

or problems arise

D

A

F

E

B

C

*Illustration is reference only. Your installation may differ

 

Figure 12 

Gaseous Fuel System

*

NOTICE

 

The supplied flexible steel fuel line is not 

to be installed underground or in contact 

with the ground

WARNING

Propane and Natural Gas are 

extremely flammable and explosive, which could 

cause burns, fire or explosion resulting in death 

or serious injury. The slightest spark could ignite 

these fuels and cause an explosion. LP gas 

is heavier than air and will settle in low areas. 

Natural gas is lighter than air and will collect in 

high areas. Before installing and/or servicing 

fuel supply system:

DO
•  Do

 install fuel supply system according to 

applicable national rules and regulations of 

the respective country.

•  Do

 properly purge and leak test fuel system 

lines.

•  Do

 wipe up any oil spills immediately.

•  Do

 keep the area near the generator clean 

and free of debris.

DO NOT
•  Do not

 permit leakage.

•  Do not

 leave combustible materials in the 

generator compartment.

•  Do not

 operate engine if smell of fuel is 

present or other explosive conditions exist.

•  Do not

 smoke around generator.

•  Do not

 have any open flames around 

generator.

Содержание 14000 Series

Страница 1: ...o t f o r R e p r o d u c t i o n Generator Home Generator Systems Installation Instructions Series 14000 Copyright Briggs Stratton Corporation Milwaukee WI USA All rights reserved 80010856 Revision...

Страница 2: ...low the instructions completely Where to Find Us You never have to look far to find support and service for your generator Consult your Yellow Pages There are many Briggs Stratton authorized service d...

Страница 3: ...Consumption 22 LP Vapor Propane 22 Natural Gas 22 Fuel Pressure 22 Power Loss 22 Fuel Pipe Sizing 22 Fuel Conversion 22 System Connectors 23 Grounding the Generator 24 Generator Power Connection 24 U...

Страница 4: ...with a low level of risk which if not avoided could result in minor or moderate injury NOTICE The manufacturer cannot possibly anticipate every possible circumstance that might involve a hazard The wa...

Страница 5: ...on monoxide detectors cannot detect smoke Do allow sufficient room on all sides of generator for maintenance and servicing DO NOT Do not use with or substitute the flexible fuel line provided with any...

Страница 6: ...ing in water while barefoot or while hands or feet are wet In case of an accident caused by electrical shock immediately shut down the source of electrical power and contact the local authorities or e...

Страница 7: ...permit leakage Do not leave combustible materials in the generator compartment Do not operate engine if smell of fuel is present or other explosive conditions exist Do not smoke around generator Do n...

Страница 8: ...equipment Do not work on the equipment when you are physically or mentally fatigued 8 If connected devices overheat turn them off and disconnect them from generator 9 Do not modify generator in any wa...

Страница 9: ...freight bill and affix his signature under the consignor s memo of loss or damage If loss or damage is noted after delivery separate the damaged materials and contact the carrier for claim procedures...

Страница 10: ...mmendations Smoke alarms cannot detect carbon monoxide gas Smoke detector s MUST be installed and maintained indoors according to the manufacturer s instructions recommendations Carbon monoxide alarms...

Страница 11: ...l wiring is rated for 600V See Communication Connections Dipswitches in most transfer switches must be set to correspond to the wattage of the generator See Transfer Switch Operator Installation Manua...

Страница 12: ...N o t f o r R e p r o d u c t i o n 12 This page intentionally left blank...

Страница 13: ...ng requirements which must be satisfied before the instal lation is complete There are two equally important safety concerns in regards to carbon monoxide poisoning and fire There are also several gen...

Страница 14: ...ements INSTALLATION cont A Figure 3 Carbon Monoxide Detector F C D B G E Figure 4 Carbon Monoxide Gas entries The letters shown above in Figure 4 indicate POTENTIAL points of entry for Carbon Monoxide...

Страница 15: ...ng structure window doors ventilation intakes soffit vents crawl spaces open garage doors or other openings where exhaust gas could accumulate and enter inside or be drawn into potentially occupied bu...

Страница 16: ...ion over 0 3 m in height Do locate the weatherproof enclosure a minimum of 1 5 m overhead clearance from any structure overhang or trees Do ONLY use flexible fuel line provided Connect provided fuel l...

Страница 17: ...structure overhang or trees Standby Standby Standby Standby Exhaust Direction Exhaust Direction Exhaust Direction Exhaust Direction 46 cm min 46 cm min 46 cm min NOTICE DO NOT place weatherproof encl...

Страница 18: ...he electrical inlet This inlet may be enlarged or supplemented to accommodate a maximum conduit size of 38 mm Ensure that the installed conduit s enter the generator in the zone B shown in the figure...

Страница 19: ...fting pipes with a spreader bar The proper use of a spreader bar will prevent damage to the generator enclosure DO NOT touch the roof when lifting the generator Concrete Anchoring In areas prone to hi...

Страница 20: ...identical keys These keys fit in the lock on the front panel The roof must be unlocked in order for it to open To Open the Roof 1 Insert key into lock B of front panel Gently push down on roof above...

Страница 21: ...d conditions with all gas appliances connected to the fuel system turned on and operating Use a pipe sealant or joint compound approved for use with NG LPG on all threaded fittings to reduce the possi...

Страница 22: ...ea level and 1 for each 5 6 C above 25 C Fuel Pipe Sizing There are numerous on line or otherwise published references for fuel pipe sizing Consider the specific gravity of gas and compensate for a no...

Страница 23: ...00V 90 C copper wire Torque terminals to 0 5Nm B Fault Contacts Use NO COM and NC to connect an alarm to alert user in case of a fault Contacts reverse state NO goes to NC and vice versa upon a fault...

Страница 24: ...e respective country When power on these leads is lost the generator will start Communication Connections Connect the applicable communication leads to the automatic transfer switch as shown in the ta...

Страница 25: ...y If you must work around a unit while it is operating stand on an insulated dry surface to reduce risk of shock hazard Despite the safe design of the generator operating this equipment imprudently ne...

Страница 26: ...ize internal temperatures shuts off the generator and waits for the next utility outage OFF Turns off running generator prevents it from starting and resets any detected fault conditions To reset serv...

Страница 27: ...D RESETS ANY DETECTED FAULTS AUTOMATIC MODE NORMAL OPERATING POSITION PRESS AND HOLD BUTTON TO PUT GENERATOR INTO AUTOMATIC MODE IF A UTILITY POWER OUTAGE IS SENSED THE SYSTEM WILL START THE GENERATOR...

Страница 28: ...r or or DAY OF WEEK FLASHING HOURS FLASHING MINUTES FLASHING AM PM FLASHING SET EXERCISE CYCLE EVENT LOG Display will scroll last service code event date time and ambient temperature of when the event...

Страница 29: ...l scroll across the digital display and then move to the next item Run time Date Time Exercise Cycle date and start time Press the LEFT ARROW or RIGHT ARROW at any time to move to the next item Press...

Страница 30: ...ator for the first time For advanced menu items press and hold the left arrow right arrow and escape key for 3 seconds Follow the prompts as outlined below INSTALLATION cont NOTICE In the Advanced Set...

Страница 31: ...API SJ of viscosity 5W30 is required Battery The installer must supply and install a rechargeable starting battery The starting battery MUST conform to the specifications shown below in the chart Bat...

Страница 32: ...r 2 Connect an accurate frequency meter to line side of generator s main circuit breaker 3 Set generator s main circuit breaker to ON closed position 4 Verify manual shutoff valve is open 5 Install 15...

Страница 33: ...r conditions may be related to an electronic governing system issue Service Codes ENGINE DOES NOT START ENGINE OVER SPEED LOW FREQUENCY GENERATOR SENSE FAULT Fault Conditions Unstable no load engine c...

Страница 34: ...3 seconds Follow prompts shown in Figure 19 General Set Up Screen Setting Exercise Timer The generator is equipped with an exercise timer During the exercise period the generator runs for 20 minutes...

Страница 35: ...erates are between 10 to 20 off the LP gas rating ENGINE SPECIFICATIONS Displacement 993 cc Bore 85 5 mm Stroke 86 5 mm Spark Plug Gap 0 51 mm Spark Plug Torque 20 Nm Armature Air Gap 0 13 0 20 mm Int...

Страница 36: ...N o t f o r R e p r o d u c t i o n 36 SCHEMATIC DIAGRAM...

Отзывы: