Brigantia 240DVRS25N Скачать руководство пользователя страница 20

24-DVRS25N

 

20

 

1.  Remove the surround. 
2.  The pressure test taps are located on the valve. The taps are located in the gas valve front face. 

The inlet is marked ‘

IN

’ 

and the outlet is marked ‘

OUT

’.

 See Fig.1.   

3.  Loosen the set screw inside the tap with a screwdriver. 
4.  Connect a 1/4” (6 mm) rubber tube to the tap post and a manometer. 
5.  Verify that the readings obtained are within specs (as shown on the appliance rating plate) 
6.  Be sure to tighten the set screw inside the tap after you have finished taking pressure readings. 
7.  Check for leaks. 

CHECKING INLET AND OUTLET GAS PRESSURE 

CHECKING AND ADJUSTING PILOT 

The flame should not have yellow tips but should engulf the 
sensor. It can be adjusted by turning the screw marked 
“pilot” on the control valve (see above). 

Sensor 

Ignitor 

The pilot flame should have the characteristic as shown in 
the illustration to the right.  

Содержание 240DVRS25N

Страница 1: ...u cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier This appliance may be installed in an a...

Страница 2: ...spector of the side wall horizontally vented gas fueled equipment shall not approve the instal lation unless upon inspection the inspector observes carbon monoxide detectors and signage installed in a...

Страница 3: ...ciencies of any Direct Vent gas fireplace which means that it is less expensive to operate Adjustable Flame The flame aesthetics and heat output can be adjusted to suit the owner s liking and heating...

Страница 4: ...Gas Connections Conversion Kit Instructions Final Installation Check and Initial Operation First Fire and Lighting Instructions CAUTION Lighting Instructions on Rating Plate Remote Control Setup and...

Страница 5: ...and at least annually by a professional service person More frequent cleaning may be required due to excessive lint from carpeting bedding materials etc It is imperative that the control compartments...

Страница 6: ...factured Home Construction and Safety Standard Title 24CFR Part 3280 or when such a standard is not applicable the Standard for manufactured Home Installations ANSI NCSBCS A225 1 or Standard for Gas E...

Страница 7: ...cal connections and grounding must be in accordance with local codes if any if none follow the current CAN CSA C22 1 in Canada and ANSI NFPA 70 in the US This appliance is certified for installation i...

Страница 8: ...24 DVRS25N 8 APPLIANCE DIMENSIONS Surround Installed Surround Removed...

Страница 9: ...pening to dimensions shown 26 1 2 wide x 39 1 2 high X 5 1 2 deep Unit must be min 4 up from combustible floor Installation Instructions When installing on an exterior wall you must include the exteri...

Страница 10: ...fts See figure 4 Figure 4 Install the nailing flanges provide by screwing them to the side of the outer shell using the hole required for the facing material Then place the fireplace into the framed o...

Страница 11: ...ments below are from the edge of door unless otherwise noted Clearance to Combustibles Clearance to combustible floor must maintain clearances from the top surface of carpet flooring etc Nailing Flang...

Страница 12: ...0v circuit must be electrically grounded in accordance with the local codes or in absence of local codes with the National Electrical Code ANSI NFPA 70 or the Canadian Electrical Code CSA C22 1 Electr...

Страница 13: ...tations evenly spaced around the pipe These indentations are designed to slide over the male section of the pipe and fully lock by a clockwise quarter turn Vent Restrictors Due to the extra flow produ...

Страница 14: ...andoff and the terminal Attach the terminal to the exterior wall using four wood screws through the holes in the corner of the vent terminal Complete the terminal installation and apply a bead of mast...

Страница 15: ...ing joists roof rafters or other framing will obstruct the vent system You may have to use 45 elbows to navigate around any obstacles When passing through a flat ceiling install a Box Wall thimble Cut...

Страница 16: ...corner 9 23 cm Note Clear ances are to be in accordance with local installation codes and the requirements of the gas supplier G Do not install above a meter regulator assembly within 3 feet 90 cm ho...

Страница 17: ...ntal Use restrictor setting No 1 Example C 17ft vertical rise 1 90 elbow 5ft horizontal Use restrictor setting No 2 Maximum horizontal elbows allowed 3 Note if more than 1 90 elbow is used hori zontal...

Страница 18: ...e fireplace Separate wires to disable CPI activation from remote The SIT Control Module is powered by 120V with an internal transformer for the valve This is pre wired to the factory installed electri...

Страница 19: ...individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa Failure to do so will damage the appliance s gas v...

Страница 20: ...fy that the readings obtained are within specs as shown on the appliance rating plate 6 Be sure to tighten the set screw inside the tap after you have finished taking pressure readings 7 Check for lea...

Страница 21: ...24 DVRS25N 21 Contemporary Panels ITEM PART NUMBER DESCRIPTION QTY 1 311 6381 FB PANEL REAR 1 2 311 6382 FBR SIDE PANEL RIGHT 1 3 311 6283 FBL SIDE PANEL LEFT 1 4 311 6284 FBT PANEL TOP 1...

Страница 22: ...on the bottom Surround clip receivers will push on to these buttons Release the latch located on the bottom of door To release pull forward then press down Remove the door by pulling the bottom out t...

Страница 23: ...s unit with the customer the installer must ensure that the appliance is firing correctly and that the electrical system is in working order This will include 1 Perform leak tests of supply line gas c...

Страница 24: ...24 DVRS25N 24 LIGHTING INSTRUCTIONS ON RATING PLATE...

Страница 25: ...t cover of this manual 3 Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control syst...

Страница 26: ...24 DVRS25N 26 REMOTE CONTROL SETUP AND OPERATION...

Страница 27: ...24 DVRS25N 27 REMOTE CONTROL SETUP AND OPERATION cont...

Страница 28: ...24 DVRS25N 28 REMOTE CONTROL SETUP AND OPERATION cont...

Страница 29: ...24 DVRS25N 29 REMOTE CONTROL SETUP AND OPERATION cont Note When the fireplace is started in Smart Thermostat mode the fan will come on 5min after ignition and shut down 12min after fire is turned off...

Страница 30: ...24 DVRS25N 30 REMOTE CONTROL SETUP AND OPERATION cont...

Страница 31: ...PERATION cont The unit is shipped from the factory with the ability for IPI CPI selection active To disable the Continuous Pilot selection ability cut one of the wires blue or white shown in the pictu...

Страница 32: ...24 DVRS25N 32 REMOTE CONTROL SETUP AND OPERATION cont...

Страница 33: ...venting system if the vent pipe or seal is found to be defective replace and or reseal follow the instructions found in the venting instructions section Clean and remove any lint accumulations or deb...

Страница 34: ...ustments and orifice sizing IMPORTANT For high altitude installations above 4500 ft 1372 meters consult local gas distributor or the authority having jurisdiction for proper de rating methods WARNING...

Страница 35: ...24 DVRS25N 35 CONVERSION KIT INSTRUCTIONS CONT VALVE CONVERSION...

Страница 36: ...s Test fire the fireplace to confirm correct operation Reinstall door assembly and surround Run through a complete firing cycle to confirm correct operation KIT NUMBERS 35 CKELP for LP gas and 24 CKEN...

Страница 37: ...ould be conducted with the appliance cold All replacement parts must be authorized by Brigantia for suitability Before servicing read the terms and conditions of the Brigantia warranty at the back of...

Страница 38: ...fice Main Burner Orifice Drill to 43 DMS for Natural Gas EA Orifice Main Burner Orifice Drill to 54 for LP Gas EA 308 0119 Pilot Assembly conv PSE IPI EA 824 0050 Burner EA 24 CKELP Conversion Kit NG...

Страница 39: ...This is a normal sound Q I hear a ticking cracking or pinging sound when my fireplace is running and after it is turned off A The different gauges of steel used to manufacture your fireplace will exp...

Страница 40: ...24 DVRS25N 40 NOTES...

Страница 41: ...carried out by an unqualified person s Only original Brigantia parts may be used Please consult your Brigantia dealer or representative if in doubt about a replacement part s OBTAINING WARRANTY SERVI...

Страница 42: ...Name Address City State Prov ZIP Phone _____ Why did you choose this product Thank you for purchasing our product and filling out this warranty card mm dd yyyy POSTAGE FOLD DOWN AT LINE FOLD DOWN AT...

Страница 43: ...ARCHGARD FIREPLACES 7116 Beatty Drive Mission B C V2V 6B4 Canada Website www archgard com...

Отзывы: