5.08: 

Modifications to NFPA-54, Chapter 10

 

 (2) Revise 10.8.3 by adding the following additional requirements: 
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part 
for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is 
less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following 
requirements shall be satisfied:  
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled 
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-
up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe 
that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, build-
ing or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to 
secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors 
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon 
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. 
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a 
period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery 
operated carbon monoxide detector with an alarm shall be installed. 
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provi-
sions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.  
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of 
eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or 
equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, 

"GAS VENT DIRECTLY BELOW. KEEP 

CLEAR OF ALL OBSTRUCTIONS". 

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the instal-
lation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions 
of 248 CMR 5.08(2)(a)1 through 4.  
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:  
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as 
adopted by the Board; and  
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, 
building or structure used in whole or in part for residential purposes.  
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Prod-
uct Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the 
equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include: 
1. Detailed instructions for the installation of the venting system design or the venting system components; and 
2. A complete parts list for the venting system design or venting system.  
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a 
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies 
"special venting systems", the following requirements shall be satisfied by the manufacturer: 
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and  
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list 
and detailed installation instructions.  
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting in-
structions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at 
the completion of the installation.  

 

                                           

STATE OF MASSACHUSETTS  REQUIREMENTS 

 

For the State of Massachusetts, installation and repair must be done by a plumber or gasfitter li-

censed in the Commonwealth of Massachusetts. 

 

For the State of Massachusetts, flexible connectors shall not exceed 36 inches in length. 

 

The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance 

with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is 

installed. 

 

For the State of Massachusetts the appliances individual shut 

 off must be a t-handle type valve. 

Содержание 240DVRS25N

Страница 1: ...u cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier This appliance may be installed in an a...

Страница 2: ...spector of the side wall horizontally vented gas fueled equipment shall not approve the instal lation unless upon inspection the inspector observes carbon monoxide detectors and signage installed in a...

Страница 3: ...ciencies of any Direct Vent gas fireplace which means that it is less expensive to operate Adjustable Flame The flame aesthetics and heat output can be adjusted to suit the owner s liking and heating...

Страница 4: ...Gas Connections Conversion Kit Instructions Final Installation Check and Initial Operation First Fire and Lighting Instructions CAUTION Lighting Instructions on Rating Plate Remote Control Setup and...

Страница 5: ...and at least annually by a professional service person More frequent cleaning may be required due to excessive lint from carpeting bedding materials etc It is imperative that the control compartments...

Страница 6: ...factured Home Construction and Safety Standard Title 24CFR Part 3280 or when such a standard is not applicable the Standard for manufactured Home Installations ANSI NCSBCS A225 1 or Standard for Gas E...

Страница 7: ...cal connections and grounding must be in accordance with local codes if any if none follow the current CAN CSA C22 1 in Canada and ANSI NFPA 70 in the US This appliance is certified for installation i...

Страница 8: ...24 DVRS25N 8 APPLIANCE DIMENSIONS Surround Installed Surround Removed...

Страница 9: ...pening to dimensions shown 26 1 2 wide x 39 1 2 high X 5 1 2 deep Unit must be min 4 up from combustible floor Installation Instructions When installing on an exterior wall you must include the exteri...

Страница 10: ...fts See figure 4 Figure 4 Install the nailing flanges provide by screwing them to the side of the outer shell using the hole required for the facing material Then place the fireplace into the framed o...

Страница 11: ...ments below are from the edge of door unless otherwise noted Clearance to Combustibles Clearance to combustible floor must maintain clearances from the top surface of carpet flooring etc Nailing Flang...

Страница 12: ...0v circuit must be electrically grounded in accordance with the local codes or in absence of local codes with the National Electrical Code ANSI NFPA 70 or the Canadian Electrical Code CSA C22 1 Electr...

Страница 13: ...tations evenly spaced around the pipe These indentations are designed to slide over the male section of the pipe and fully lock by a clockwise quarter turn Vent Restrictors Due to the extra flow produ...

Страница 14: ...andoff and the terminal Attach the terminal to the exterior wall using four wood screws through the holes in the corner of the vent terminal Complete the terminal installation and apply a bead of mast...

Страница 15: ...ing joists roof rafters or other framing will obstruct the vent system You may have to use 45 elbows to navigate around any obstacles When passing through a flat ceiling install a Box Wall thimble Cut...

Страница 16: ...corner 9 23 cm Note Clear ances are to be in accordance with local installation codes and the requirements of the gas supplier G Do not install above a meter regulator assembly within 3 feet 90 cm ho...

Страница 17: ...ntal Use restrictor setting No 1 Example C 17ft vertical rise 1 90 elbow 5ft horizontal Use restrictor setting No 2 Maximum horizontal elbows allowed 3 Note if more than 1 90 elbow is used hori zontal...

Страница 18: ...e fireplace Separate wires to disable CPI activation from remote The SIT Control Module is powered by 120V with an internal transformer for the valve This is pre wired to the factory installed electri...

Страница 19: ...individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa Failure to do so will damage the appliance s gas v...

Страница 20: ...fy that the readings obtained are within specs as shown on the appliance rating plate 6 Be sure to tighten the set screw inside the tap after you have finished taking pressure readings 7 Check for lea...

Страница 21: ...24 DVRS25N 21 Contemporary Panels ITEM PART NUMBER DESCRIPTION QTY 1 311 6381 FB PANEL REAR 1 2 311 6382 FBR SIDE PANEL RIGHT 1 3 311 6283 FBL SIDE PANEL LEFT 1 4 311 6284 FBT PANEL TOP 1...

Страница 22: ...on the bottom Surround clip receivers will push on to these buttons Release the latch located on the bottom of door To release pull forward then press down Remove the door by pulling the bottom out t...

Страница 23: ...s unit with the customer the installer must ensure that the appliance is firing correctly and that the electrical system is in working order This will include 1 Perform leak tests of supply line gas c...

Страница 24: ...24 DVRS25N 24 LIGHTING INSTRUCTIONS ON RATING PLATE...

Страница 25: ...t cover of this manual 3 Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control syst...

Страница 26: ...24 DVRS25N 26 REMOTE CONTROL SETUP AND OPERATION...

Страница 27: ...24 DVRS25N 27 REMOTE CONTROL SETUP AND OPERATION cont...

Страница 28: ...24 DVRS25N 28 REMOTE CONTROL SETUP AND OPERATION cont...

Страница 29: ...24 DVRS25N 29 REMOTE CONTROL SETUP AND OPERATION cont Note When the fireplace is started in Smart Thermostat mode the fan will come on 5min after ignition and shut down 12min after fire is turned off...

Страница 30: ...24 DVRS25N 30 REMOTE CONTROL SETUP AND OPERATION cont...

Страница 31: ...PERATION cont The unit is shipped from the factory with the ability for IPI CPI selection active To disable the Continuous Pilot selection ability cut one of the wires blue or white shown in the pictu...

Страница 32: ...24 DVRS25N 32 REMOTE CONTROL SETUP AND OPERATION cont...

Страница 33: ...venting system if the vent pipe or seal is found to be defective replace and or reseal follow the instructions found in the venting instructions section Clean and remove any lint accumulations or deb...

Страница 34: ...ustments and orifice sizing IMPORTANT For high altitude installations above 4500 ft 1372 meters consult local gas distributor or the authority having jurisdiction for proper de rating methods WARNING...

Страница 35: ...24 DVRS25N 35 CONVERSION KIT INSTRUCTIONS CONT VALVE CONVERSION...

Страница 36: ...s Test fire the fireplace to confirm correct operation Reinstall door assembly and surround Run through a complete firing cycle to confirm correct operation KIT NUMBERS 35 CKELP for LP gas and 24 CKEN...

Страница 37: ...ould be conducted with the appliance cold All replacement parts must be authorized by Brigantia for suitability Before servicing read the terms and conditions of the Brigantia warranty at the back of...

Страница 38: ...fice Main Burner Orifice Drill to 43 DMS for Natural Gas EA Orifice Main Burner Orifice Drill to 54 for LP Gas EA 308 0119 Pilot Assembly conv PSE IPI EA 824 0050 Burner EA 24 CKELP Conversion Kit NG...

Страница 39: ...This is a normal sound Q I hear a ticking cracking or pinging sound when my fireplace is running and after it is turned off A The different gauges of steel used to manufacture your fireplace will exp...

Страница 40: ...24 DVRS25N 40 NOTES...

Страница 41: ...carried out by an unqualified person s Only original Brigantia parts may be used Please consult your Brigantia dealer or representative if in doubt about a replacement part s OBTAINING WARRANTY SERVI...

Страница 42: ...Name Address City State Prov ZIP Phone _____ Why did you choose this product Thank you for purchasing our product and filling out this warranty card mm dd yyyy POSTAGE FOLD DOWN AT LINE FOLD DOWN AT...

Страница 43: ...ARCHGARD FIREPLACES 7116 Beatty Drive Mission B C V2V 6B4 Canada Website www archgard com...

Отзывы: