24-DVRS25N
14
Installation Instructions Cont.
Horizontal Wall Vent Terminations
The position of the horizontal vent termination
must be positioned in such a way as to meet all
local building codes.
Attach the correct length of vertical section pipe
and an elbow fitting to the stove.
Mark the center line of the pipe facing the wall
(allowing for a 1/4” rise per foot of horizontal,
example 10ft of horizontal would require a rise
of 2.5”).
NOTE: ALLOWING THE VENT PIPE TO SLOP
DOWN TOWARDS THE VENT TERMINATION
COULD CAUSE POOR COMBUSTION AND/
OR HIGH TEMPERTURES THAT MAY PRE-
SENT A FIRE HAZARD.
Mark a 10” x 10” square around the center mark
(inside dimensions).
Cut and frame the exterior wall to accept the
Wall Thimble. Install the Wall Thimble shield
using wood screws. If the wall being penetrated
is constructed of non-combustible material con-
crete or block wall a 7” hole sufficient for the
vent pipe is acceptable.
Venting terminals must not be recessed
into wall or siding
C
L
C
L
10 X 11”
Rectangular
hole
When the termination is to be attached to vinyl siding
apply a bead of non-hardening mastic around the
outside edge to form a seal between the standoff
and the terminal. Attach the terminal to the exterior
wall using four wood screws through the holes in the
corner of the vent terminal.
Complete the terminal installation and apply a bead
of mastic around the outer edge of the vinyl standoff.
With the termination installed you can now connect
the completed vent assembly by sliding the unit back
towards the wall and carefully inserting the pipe into
the terminal.
Slide the pipe into the vent, making sure that at least
1¼” overlap between the pipe and the terminal.
To achieve the minimum vertical rise, a 14” or 36”
snorkel termination may be used. Do not install
where snorkel may be blocked by snow or sub-
merged in water. Ensure adequate space and
drainage.
Basement Installations
FOR PROPER VENTING
When planning your installation, it will be neces-
sary to select the proper length of vent pipe in-
stallations. For vertical installations, determine
the length of vent pipe required by measuring the
distance from the appliance flue outlet to the ceil-
ing, the ceiling thickness, the vertical rise in the
attic or second story, and allow for sufficient vent
height above the roof line. For two-story applica-
tions, fire-stops are required at each floor level. If
an offset is needed in the attic, additional pipe
and elbows will be required. Venting terminals
shall not be recessed into a wall or siding.
Содержание 240DVRS25N
Страница 8: ...24 DVRS25N 8 APPLIANCE DIMENSIONS Surround Installed Surround Removed...
Страница 24: ...24 DVRS25N 24 LIGHTING INSTRUCTIONS ON RATING PLATE...
Страница 26: ...24 DVRS25N 26 REMOTE CONTROL SETUP AND OPERATION...
Страница 27: ...24 DVRS25N 27 REMOTE CONTROL SETUP AND OPERATION cont...
Страница 28: ...24 DVRS25N 28 REMOTE CONTROL SETUP AND OPERATION cont...
Страница 30: ...24 DVRS25N 30 REMOTE CONTROL SETUP AND OPERATION cont...
Страница 32: ...24 DVRS25N 32 REMOTE CONTROL SETUP AND OPERATION cont...
Страница 35: ...24 DVRS25N 35 CONVERSION KIT INSTRUCTIONS CONT VALVE CONVERSION...
Страница 40: ...24 DVRS25N 40 NOTES...
Страница 43: ...ARCHGARD FIREPLACES 7116 Beatty Drive Mission B C V2V 6B4 Canada Website www archgard com...