4.4 FLOOR PROTECTOR
The stove must be placed on solid concrete, solid masonry, or when installed on a combustible
fl
oor, on a
fl
oor protector. The
fl
oor
protector is required to provide heat, live ember, and ash protection and must be of a non-combustible, continuous solid surface to
protect against in
fi
ltration of live embers and ash. The stove must be placed on solid concrete, solid masonry, or when installed on a
combustible
fl
oor, on a Type 2
fl
oor protector listed to standard UL 1618 with a minimum R value of 1.03 and a minimum thickness
of 1/2” or equivalent.
Dimension
Inch
mm
H*
Front
15
381
J
Flue rear
2
51
K**
Left
6
204
L**
Right
6
204
M
Flue Side
2
51
⃰
Canadian installations require 18” (457mm)
⃰
⃰
Canadian installations require 8” (203mm)