E16521D-Manual_EN_Rev12 2021_JAN_14
Page 9 of 26
3
Parameters
3.1
Summary of parameters and their default values as set on delivery
Param.
No.
Default
Value
Parameter Function
P00.xx
Code Figure, Parameter Lock, Minimum Measuring Period
P00.00
0000 Code figure
.01
0000 New code figure
.02
1 Front side Parameter Lock : 0 : yes / 1 : no
.03
0005 Minimum Measuring Period:
0005 … 9999
[ms]
.04
000 Starter Time Period in xxx [s]
P01.xx
Measurement Configuration, Reset, Sensor Monitoring
P01.00
0 Fix value 0
.01 10000 Nominal input frequency in [Hz]
.02
0 Fix value 0
.03 10000 Nominal speed in [RPM]
.04 00001 Low end of the speed measurement in [RPM]
.05
0 Reserved
.06
0 Reserved
.07
0 Reset necessary after power up: 0 : yes / 1 : no
.08
1 Sensor monitoring: 0 : off / 1 : on / 2 : on, latched
.09
0 Mode of sensor monitoring: see parameter description
.10
001 Fix value 001
P02.xx
Display
P02.00
0 Fix value 0
.01
0.3 Display updating sequence in x.x [s]
P03.xx
Analog Output
P03.00 10000 High end of analog output at speed in [RPM]
.01 00000 Low end of analog output at speed in [RPM]
.02
1 Zero level: 0 : dead zero / 1 : live zero
.03
1 Fix value 1
.04
0 Output level at sensor fault: 0 : no change / 1 : min / 2 : max
.05
0 Output direction: 0 : 0/4..20 [mA] / 1 : 20...4/0 [mA]
P04.xx
Speed Setpoint SP1 and Safety Output OR1
P04.00 01000 Speed setpoint SP1 in [RPM]
.01
05.0
Hysteresis bandwidth SP1: 00.1….99.9 %
.02
0 Hysteresis position: 0 : above SP1 / 1 : below SP1
.03
1 De-energized state OR1 at ' n > SP1 ' or ' n < SP1 ' : see parameter description
.04
0 OR1 also at ' n < SP2 ' : 0 : no, 1 : yes
.05
0 Reserved
.06
0 OR1 forced state at sensor fault: see parameter description
Continued on next page