E16521D-Manual_EN_Rev12 2021_JAN_14
Page 12 of 26
4
Description of Parameters and their Settings
Parameter Group P00.xx
Code Figure, Parameter Lock, Front side Reset of Alarms
Parameter No.
Meaning of Parameter
Setting Range of Parameter
Description of Parameters and their Settings
P00.00
Code Figure
Range: 0000 .. 9999
If the parameters are locked (see P00.02), the code figure must be entered
prior to any change of other parameters.
If the code figure is not correct, -E 1- is displayed.
Without code figure and P00.02 = 0 the values of all parameters may be in-
spected, but not changed.
P00.01
New Code Figure
Range: 0000 .. 9999
A new code figure may be set in P00.01. Then it replaces the previous one.
P00.02
Front side Parameter Lock
Range: 0 .. 1
Setting:
0 : Parameters are locked, front side change only possible with code
figure
1 : Parameters unlocked, front side change of parameter values possible
P00.03
Minimum Measuring Period
in milliseconds
Range: 0005 .. 9999
The measurement is based on a time interval measurement over a (variable)
number of input signal pulses. A programmable minimum measuring period
thus will be maintained, automatically including more input pulses into every
measurement with increasing input frequency. This establishes an averaging
over the programmed period of time, which helps to stabilize the
measurements, specifically with fluctuating variables. The setting of P00.03
defines the minimum measuring period of time, in terms of milliseconds,
within a range of 0005....9999 milliseconds. A setting less than 0005 is
possible, but minimum measuring time will still be 5 msec.
P00.04
Starter Time Period
Range: 000 .. 999
This step sets the starter time period (duration) in terms of seconds. The
starter condition state lasts from the beginning of the external starter signal
plus the programmed time elapse following its end. Valid for all setpoints with
the activated starter.