Parameter Group P08.xx
Eddy Current sensor input and MPU input
Parameter No.
Meaning of Parameter
Setting Range of Parameter
Description of Parameters and their Settings
Eddy Current sensors must not be operated outside (by manufacturer)
specified limits of voltage level and supply current (see also P01.09).
P08.00
Input voltage upper limit
Range: 00.0 to 99.9
Input check:
input voltage upper limit in xx.x volts
P08.01
Input voltage lower limit
Range: 00.0 to 99.9
input voltage lower limit in xx.x volts
P08.02
Current drain upper limit
Range: 000 to 999
current drain upper limit in xxx mA
P08.03
Current drain lower limit
Range: 000 to 999
current drain lower limit in xxx mA
P08.04
EC and MPU
signal input hysteresis
Range: 0.0 to 2.5
Signal input hysteresis (sensitivity level) in x.x volts pp
Note: with setting 0.0 hysteresis is approx. 70 millivolts pp
P08.05
Reserved
Parameter Group P09.xx
Data Interface
Parameter No.
Meaning of Parameter
Setting Range of Parameter
Description of Parameters and their Settings
P09.00
Baud rate
Range: 0 .. 4
0 = 300 Baud
1 = 1200 Baud
2 = 9600 Baud
3 = 19200 Baud
4 = 38400 Baud
P09.01
Reserved
4.1
Default Values
If not specified otherwise, the unit is supplied with default values as listed in the summary of
parameters. In the process of installation, the setting of its parameters inevitably must be
adapted to the correct values according to its application.