E16521D-Manual_EN_Rev12 2021_JAN_14
Page 18 of 26
Parameter Group P06.xx
Speed Setpoint SP3 and Alarm Output OR3
Parameter No.
Meaning of Parameter
Setting Range of Parameter
Description of Parameters and their Settings
P06.00
Speed setpoint SP3
Range: 00001 .. 99999
Speed setpoint SP3 is set in RPM.
P06.01
Hysteresis bandwidth SP3
Range: 00.1 .. 99.9
The hysteresis is the margin between condition "excess" (>) and "no excess"
(<), defined by its bandwidth. The hysteresis bandwidth is set as a
percentage of the setpoint in steps of 0.1%.
P06.02
Hysteresis position SP3
Range: 0 .. 1
Setting:
0 : hysteresis above SP3 (recommended when monitoring n < SP3)
1 : hysteresis below SP3 (recommended when monitoring n > SP3)
P06.03
De-energized state OR3 at
' n > SP3 ' or ' n < SP3 '
Range: 0 .. 3
Without power supply the relays are de-energized (alarm condition). To
consider safety aspects of the application, this No-Power condition can be
assigned to alarm state n > SP3 or n < SP3 condition.
Setting:
0 : OR3 de-energized at ' n < SP3 '
1 : OR3 de-energized at ' n > SP3 '
2 : OR3 de-energized and latched at ' n < SP3 '
3 : OR3 de-energized and latched at ' n > SP3 '
P06.04
Starter effective for SP3
Range: 0 .. 1
The starter function may be effective for each setpoint individually. Thereby
it is possible, for instance, to disable a low-speed alarm during the starter
phase, whereas a high-speed alarm remains active all the time.
Setting:
0 : starter not effective for setpoint SP3
1 : starter effective for setpoint SP3
P06.05
OR3 state at starter condition
Range: 0 .. 1
At starter condition, the relay may be forced to state energized or
de-energized (if starter function is effective for the alarm).
Setting:
0 : OR3 de-energized
1 : OR3 energized
P06.06
OR3 in forced de-energized
state at
sensor fault condition
Range: 0 .. 2
At sensor fault, OR3 may be forced to de-energized state.
Setting:
0 : no forced state, state acc. to measured speed
1 : OR3 in de-energized state as if n > SP3 (if P06.03 is 1 or 3)
2 : OR3 in de-energized state as if n < SP3 (if P06.03 is 0 or 2)