5.  If you are using one extension cord for more than 

one tool, add the nameplate

 

amperes and use the 

sum to determine the required minimum cord size.

6.  If you are using an extension cord outdoors, make 

sure it is marked with the suffix “W-A” (“W” in 
Canada) to indicate it is acceptable for outdoor use.

7.  Make sure the extension cord is properly wired 

and in good electrical condition.  Always replace 
a damaged extension cord or have it repaired 
by a qualified electrician before using it.

8.  Protect the extension cords from sharp objects, 

excessive heat, and damp or wet areas.

TABLE A:  RECOMMENDED 

MINIMUM WIRE GAUGE FOR 

EXTENSION CORDS* (120 VOLT)

NAMEPLATE

AMPERES

(at full load)

EXTENSION CORD 

LENGTH

25´

50´

75´ 100´ 150´

0 – 2.0

18

18

18

18

16

2.1 – 3.4

18

18

18

16

14

3.5 – 5.0

18

18

16

14

12

5.1 – 7.0

18

16

14

12

12

7.1 – 12.0

16

14

12

10

-

12.1 – 16.0

14

12

10

-

-

16.1 – 20.0

12

10

-

-

-

* Based on limiting the line voltage drop to five volts at 

150% of the rated amperes.

Symbology

Double Insulated

VAC

Volts Alternating Current

A

Amperes

WARNING marking concerning Risk 
of Eye Injury.  Wear ANSI-approved 
safety goggles with side shields.

Read the manual before 
set-up and/or use.

WARNING marking 
concerning Risk of Fire.  
Do not cover ventilation ducts.
Keep flammable objects away.
WARNING marking concerning 
Risk of Electric Shock.  
Properly connect power cord 
to appropriate outlet.

Specifications

Electrical Rating

120VAC / 60Hz

Содержание 64800

Страница 1: ...ference 19c When unpacking make sure that the product is intact and undamaged If any parts are missing or broken please call 1 888 866 5797 as soon as possible Copyright 2019 by Harbor Freight Tools A...

Страница 2: ...location 3 Do not obstruct walkways or common areas with the cord 4 This product is not intended for use in a residence or to be mounted in a cabinet This product is not suitable for recessed install...

Страница 3: ...se Electromagnetic fields in close proximity to heart pacemaker could cause pacemaker interference or pacemaker failure In addition people with pacemakers should Avoid operating alone Properly maintai...

Страница 4: ...Prong Plug and Outlet 3 The Light must be plugged into an appropriate outlet properly installed and grounded in accordance with all codes and ordinances The plug and outlet should look like those in...

Страница 5: ...et areas TABLE A RECOMMENDED MINIMUM WIRE GAUGE FOR EXTENSION CORDS 120 VOLT NAMEPLATE AMPERES at full load EXTENSION CORD LENGTH 25 50 75 100 150 0 2 0 18 18 18 18 16 2 1 3 4 18 18 18 16 14 3 5 5 0 1...

Страница 6: ...SAFETY INSTRUCTIONS section at the beginning of this manual including all text under subheadings therein before setup or use of this product 1 Position the LED work light near the work Loosen Knob an...

Страница 7: ...UT OF HIS OR HER REPAIRS TO THE ORIGINAL PRODUCT OR REPLACEMENT PARTS THERETO OR ARISING OUT OF HIS OR HER INSTALLATION OF REPLACEMENT PARTS THERETO Parts List and Diagram Part Description Qty 1 Clamp...

Страница 8: ...sion or limitation of incidental or consequential damages so the above limitation of exclusion may not apply to you THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUD...

Отзывы: