background image

4/6 

15756_r02 

 

 

 

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวัฒนา กทม. 10170. 
website: 

https://www.add-furnace.com/

 โทร: 02-888-3472 

Line ID: @add11  e-mail: [email protected] 

  A  ventilated  installation  environment  and  a  suitably  low 

temperature ensure the  longest  life  of  the  control  system.

  Before installing or replacing the unit, make sure that the type, 

code and times are correct.

  The  control  systems  specified  as  IP00  should  be  installed  in 

appliances  providing  adequate  protection  against  the  risk  of 
electric shock (at least IP20).

ELECTRICAL INSTALLATION 

  Respect  the  applicable  national  and    European    standards 

regarding electrical safety (e.g. EN 60335- 1/EN 50165).

  Connect 

live 

and 

neutral 

correctly.  The  non-observance  of 

live-neutral 

polarity  may  cause  a    dangerous  situation,  as 

internal  and  external  protection  and  safety  devices  may 
become  ineffective  in  case  the  connection  cables  of  the 
thermostats  and  the  valves  should  lose              their  insulation. 
Besides,  the  non-observance  of 

live-  neutral 

polarity  causes 

lockout at the end of the safety time at start-up.

  Before starting the system check the cables carefully. A wrong 

wiring  can  damage  the  unit  and  compromise  the  safety  of  the 
appliance.

  Make  sure  that  the 

earth 

terminal  of  the  control  system,  the 

metal frame of the burner and the 

earth 

of the mains supply are 

well connected.

  Avoid  placing  the  detection  cable  close  to  power  or  ignition 

cables.

  Use  heat  resistant  detection  cables  and  electrodes,  and  make 

sure  that  they  are  well  insulated  to 

earth 

and  protected  from 

possible moisture or water in general.

  Keep  the  ignition  cable  as  short  and  straight  as  possible  and 

place  it  far  from  other  conductors  to  reduce  the  emission    of  
electromagnetic  interference  (max   length

<2m and insulation voltage >25kV). 

In case of a 

live-neutral 

network with 

unearthed neutral 

or a 

live-

live 

network  (with 

unearthed 

star  centre),  the  control  unit  can 

operate  as  well  thanks  to  an  inbuilt  resistor;  however,  in  these 
cases we recommend using our step-up transformer type AR1. 
In case of bad insulation between 

live 

and  

earth

,  the  voltage on 

the  ionization  probe  can  be  reduced  until  it    causes  the  lockout  of 
the control unit. 

CHECKING AT START-UP 

Check  the  control  system  before  the  first  start-up,  after  any 
overhaul  and  after  a  long  period  of  non-operation.  Before          any 
ignition  attempt  make  sure  that  the    combustion  chamber  is  free 
from gas, then check the following: 

  if the start-up attempt occurs without gas supply, the    control 

system should go to lockout at the end of the     safety time;

  when stopping the gas flow while the control system is running, 

the  power  supply  to  the  gas  valve(s)  should  be  interrupted 
within  1s,  and  the  control  system  should  proceed  to  lockout 
after a recycling attempt;

  operating  times  and  sequence  should  correspond  to  those 

declared for the type of control unit you are using;

  the level of the flame signal should be high enough (see  Fig.6 

for the measuring method to adopt);

  the ignition probe should be adjusted in the most stable way for 

a spark gap between 2-4 mm;

  the intervention of limiters or protection devices should cause a 

safety shutdown according to the type of application.

OPERATION 

At every start-up the control system performs  a  self-  checking of 
its own efficiency. During the waiting or pre-      purge time (TW) the 
internal  circuit  tests  the  correct    operation  of  the  flame  signal 
amplifier. Extraneous light or a 

fault in the amplifier leading to flame simulation prevent the control 
system from starting. 
In the types with fan control, before the beginning of the pre-purge 
time  the  air  pressure  switch  contacts  are  checked  to  prove  their 
"no-air-flow"  condition.  If  this  test  is  positive,        the  air  pressure 
switch detects the air flow  and consequently switches to "air-flow" 
position, allowing in this way the pre-purge time to begin. 
At  the  end  of  the  waiting  or  pre-purge  time,  the  gas  valve  is 
energized  and  the  ignition  device  is  operated.  In  this  way            the 
safety time (TS) begins. 
If  a  flame  signal  is  detected  during  the  safety  time,  the  ignition 
device  is  disabled  and,  in  some  models,  the  independent  auxiliary 
contact  (SM191N)  or  the  main  valve  control  switch  from  "off"  to 
"flame-on" position. 
Else, if no flame signal is detected during the safety time, at the end 
of  the  same  the  control  system  goes  to  lockout,  the  gas    valve  is 
closed,  the  ignition  device  disabled  and  the    lockout  signal 
energized. 
Flame failure during the safety time causes the ignition device to be 
re-activated within one second. 
Please  see  the  attached  operating  cycle  diagrams  to  better 
understand the operation of each control unit. 

RESETTING THE CONTROL UNIT 

In  case  of  lockout,  wait  at  least  10  seconds  before  trying  to  reset 
the  unit;  if  this  time  is  not  observed,  the  system  may        not  reset 
correctly.  In  general,  the  reset  push-button  should  be  visible  and 
placed near the appliance. Reset can only    occur by an intentional 
manual operation and not by means of any automatic devices such 
as thermostats or timers. 
In  the  appliance  it  is  possible  to  combine  the  reset  push-      button 
with the main switch; in this case, however, a light  alarm will have 
to be installed. 

 

 

Fig.6 

DETECTION 

ELECTRODE 

IGNITION 

ELECTRODE 

Отзывы: