OVERALL DIMENSIONS
The EUROBOX series burner control units can be provided with a
different casing according to the characteristics and fixing systems
required.
Casings are available with or without reset push-button and can be
equipped with lateral fixing brackets or not. Please note that the
units equipped with lateral fixing brackets can be fitted to sockets
type "P" or "R" only, as these are provided with suitable fixing
hooks. The numeric suffix in the part reference indicates the type of
casing:
1
with reset push-button;
with fixing brackets
2
with reset push-button;
without fixing brackets
3
without reset push-button;
with fixing brackets
4
without reset push-button;
without fixing brackets The
possibility of using casings without reset push-button is restricted to
the control units prearranged for remote reset. Fig.1 shows the
overall dimensions of the units.
CM381. Socket type P differs from type R on positions 8 and 10
for the availability of through holes to suit female fast-on terminals
of standard type.
As regards the connection of the control units, strain relieves and
a sufficient number of earth and neutral terminals should be
available in the appliance or in external connection boxes.
Fig.1
ACCESSORIES
The control units are usually supplied with inbuilt reset push-button;
versions with remote reset supplied with a suitable light reset push-
button are also available (see Fig.2).
The casings of the control units are prearranged for the use of
strain relieves/cable glands to be mounted on their sides; also
these accessories can be supplied upon request (see Fig.3).
RESET PUSH-BUTTON
DRILLING PLANE
Socket R Fig. 4
CODE 81020980
Reset 1
Lockout signal 2
3 Neutral
Fig.2
Fig.3
INSTALLATION DIRECTIONS
Socket NG Fig. 5
CONNECTION
For this series of burner control units, various interconnection
solutions are possible. In fact, different types of connecting
sockets can be used (see Fig.4 and Fig.5): types NG (code
18210094) and MG (code 18210113) are equipped with screw
terminal board, whereas types P (code 18210096) and R are
provided with a number of fast-on holders.
Socket type MG differs from type NG for the availability of an
auxiliary terminal requested for the control unit type
A regulation shutdown should occur every 24 hours to enable
the unit to check its own efficiency (systems for non-permanent
operation).
Ignition systems are safety devices; the manufacturer's
responsibility and guarantee are invalidated in case of
Customer's tampering with the product.
Connect and disconnect the control unit only after switching off
the power supply.
The unit can be mounted in any position.
Avoid exposure to dripping water.