TABLE 1 

 

 

BURNER 

OPTIONS 

RESET 

 

CONNECTION 

 

Si

n

g

le

 f

la

m

e

 

 

D

o

u

b

le

 f

la

m

e

 

 

At

m

o

s

ph

e

ric

 w

it

hout

 fa

n

 

At

m

o

s

ph

e

ric

 w

it

h

13

fa

n

 

 

A

u

x

il

iar

y

 c

on

tac

(1

 

Si

n

g

le

 e

le

c

tr

ode

 

 

E

xter

n

a

ig

n

it

io

n

 d

e

v

ic

e

 

 

Re

m

o

te

 

 

In

b

u

ilt

 

 

C

lass

if

icat

io

n

 acc

o

rd

in

g

 t

E

N

2

9

8

 (2

E

N

2

9

8

:2

0

0

3

 c

o

m

p

li

a

nt

 (3

 

So

cke

P

 

 

So

cke

R

 

 

So

cke

N

G

 

So

cke

MG

 

CM191N 

 

 

 

 

 

(B) 

(A) 

AMCLXN 

 

SM191N 

 

 

 

 

 

(A) 

AMCLXN 

 

 

 

SM192N 

 

 

 

 

 

(B) 

(A) 

AMCLXN 

 

CM381N 

 

 

 

 

 

(B) 

(A) 

FMCLXN 

 

CM391N 

 

 

 

 

 

 

(A) 

FMCLXN 

 

 

 

SM152N 

 

 

 

 

 

(B) 

(A) 

AMCLXN 

 

SM592N 

 

 

 

 

(B) 

(A) 

AMCLXN 

 

MM191N 

 

 

 

 

(B) 

(A) 

AMCLXN 

 

MM192N 

 

 

 

 

(B) 

(A) 

AMCLXN 

 

NOTE: (A) Box type xxxxxx.1 

– xxxxxx.2 

(B) Box type xxxxxx.3 

– xxxxxx.4 

 
 
 
 

TECHNICAL DATA 
Power supply: 

230V

 

50/60Hz 

on request: 

110/120V

 

50/60Hz 

Operating temperature range: 

   

-20

+60

Humidity: 

 

95% max at 40°C 

Protection degree: 

socket NG 

IP 40 (after installation) 

socket P/R 

IP 00 

Times: 

 

waiting/pre

-purge time 

(TW)

1,5..40 s

TW 

for type SM152N 

3..40 s 

 

safety 

time at start-up 

(TS)

3..60 s

 

response time in case of flame failure 

 

1 s 

The times appearing on the product label correspond to guaranteed 
values. Actual times may differ from declares  ones, as waiting and 
pre-purge time may be longer and safety time shorter than their 
nominal values.

Power consumption at start-up: 

atmospheric burner 

10VA 

atmospheric fan-assisted burner 

12VA 

Power consumption during operation: 

atmospheric 

burner 

7VA 

atmospheric fan-assisted burner 

9VA 

Max contact rating: 

Imax 

Thermostat: 

4A 

cos

 

≥    0.4 

- EV1: 

0.5A 

cos

 

≥    0.4 

- EV2: 

0.5A 

cos

 

≥    0.4 

- EVG: 

0.5A 

cos

 

≥    0.4 

Fan: 

1A 

cos

 

≥    0.4 

Lockout signal: 

0.5A 

cos

 

=    1 

Auxiliary contact: 

0.5A 

cos

 

≥    0.4 

External ignition device: 

1.5A 

cos

 

≥    0.2 

Max cable length for 
external components: 

1 m 

Internal fuse rating: 

5A 

slow-blow 

External fuse rating: 

3.15A 

fast-blow 

Flame monitoring: 

The flame detection device exploits the rectification property of the 
flame  (ionization);  the  device  is  not  provided  with  any  protection 
impedance  and  is  therefore  not  safe  against  the  risk  of  electric 
shock. 

(

1):  The  auxiliary  contact  is  not  type  SELV  (Safety  Extra  Low  Voltage)  and  is  therefore 

not suitable to control SELV circuits. 
(2): Flame failure during TS causes spark restoration. 
(3): Label showing the marking “EN298:2003 compliant” and part reference provided with 
suffix N. 

 

Min ionization current: 

0.5

on request: 

1.2

Recommended ionization current:   3

5 times the min one 

Max cable length: 

1 m 

Min insulation resistance of detection 

cable and electrode to earth: 

 

50M



Max electrode stray capacitance: 

 

1nF 

Max short-circuit current: 

 

200

A AC 

Max ionization current (230 V 50 Hz): 

8

A DC 

Ignition: 

Ignition voltage: 

8KV with 30pF load 

Spark repetition rate: 

25Hz 

Max cable length: 

2m 

Recommended spark gap: 

2-4mm 

Power consumption: 

2.5VA 

Spark energy: 

15mJ 

Weight: 

with socket P or R: 

220g 

with socket NG or MG: 

275g 

Control units for special applications: 

Upon  request  it  is  possible  to  meet  particular  requirements 
regarding  times,  spark  repetition  rate,  min  ionization  current  and 
operating cycle. 

 

 

CONSTRUCTION 

The  plastic  casing  protects  the  control  unit    from    any    damage 
resulting  from  impacts,  tampering,  dust  and  contact  with  the 
external environment. 
A  particular  construction  technique,  consisting  of  four  PCBs 
assembled  together  to  form  a  "box"  structure,  has  enabled      to 
considerably reduce the dimensions of the device. 
A varistor protects the control unit from  any  voltage  transients 
which may arise in the mains supply. 
An inbuilt fuse protects the internal relays of the unit in case of short 
circuit on the control outputs (valves,  fan  and  lockout signal). As 
this fuse is not accessible, the unit will   have to be protected by an 
external  fast-blow fuse suitable  to the loads connected and never 
exceeding 3,15A. 