Installation 

S45-1986, S45-1987, S45-1989, S45-1990

Bradley Corporation • 215-1444 Rev. E; ECM 10-05-062A 

10/25/10

Maintenance

The Freeze protection and scald protection valves should be inspected each year. The following field test 

should be performed once a year to ensure proper opening and closing of valve:

To Test the Freeze Protection Valve

Cool the valve with CO2 or ice and water slurry. The valve will start to drip until warm water reaches the 

actuator.

To Test the Scald Protection Valve

Heat the inlet line and valve with an electric heat gun or torch (if explosion hazard permits). Heat until the 

valve flows to purge hot water.

Troubleshooting

PROBLEM

CAUSE

SOLUTION

Freeze protection valve 

is flowing water

Water supply is too cold

Make sure the unit is supplied with tempered water

Defective freeze valve [if the 

water temperature from the 

valve  is above 45°F (7°C)]

Replace the freeze valve

NOTE:  A water supply that is at least 45°F (7°C) or 
colder will hold the freeze bleed valve open. To close 
the valve, 

increase the surface temperature of the 

valve to above 45°F (7°C) by immersing the valve in 
hot water.

Scald protection valve 

is flowing water

Defective scald valve [if the 

water temperature from the 

valve is below 80°F (27°C)]

Replace the scald valve

Direct sunlight or high ambient 

temperature

Cool the unit

Содержание S45-1986

Страница 1: ...ra en una ducha Valve Kit shown on Eyewash Kit de vanne illustr sur douche oculaire El kit de v lvula se muestra en un lavaojos Valve Kits shown on Combination Unit Kits de vannes sur combin Los kits...

Страница 2: ...weekly to verify proper operation This equipment should be inspected annually to ensure compliance with ANSI Z358 1 Workers who may come in contact with potentially hazardous materials should be train...

Страница 3: ...ownward to allow for drainage the flow should be in the direction shown on the valve s nameplate B Scald Valve Freeze Valve IMPORTANT To prevent an ice patch hazard Bradley recommends that discharge f...

Страница 4: ...ow for drainage the flow should be in the direction shown on the valve s nameplate B IMPORTANT To prevent an ice patch hazard Bradley recommends that discharge from the valve be directed through a hos...

Страница 5: ...40 1 Tee 1 NPT x 1 NPT x NPT 4 113 006LN 1 1 NPT Close Nipple 5 113 006LG 1 NPT Close Nipple 6 145 204 1 Compression Fitting 7 269 783M 1 Tube Supply 96 8 269 147 1 Cable Tie Item Part No Qty Descript...

Страница 6: ...be and piping but not overtightened For best results units should be top supplied when using scald and freeze valves Item Part No Qty Description 1 S45 1703 1 Freeze Protection Valve S45 1702 1 Scald...

Страница 7: ...h if explosion hazard permits Heat until the valve flows to purge hot water Troubleshooting PROBLEM CAUSE SOLUTION Freeze protection valve is flowing water Water supply is too cold Make sure the unit...

Страница 8: ...nt Notez les dates d inspection Ce mat riel doit tre inspect une fois par an pour assurer sa conformit la norme ANSI Z358 1 Les ouvriers susceptibles d entrer en contact avec des mati res potentiellem...

Страница 9: ...l coulement doit se faire dans le sens indiqu sur la plaque signal tique de la vanne B Vanne anti chaudage Vanne antigel IMPORTANT Pour viter tout risque de plaque de glace Bradley recommande de dirig...

Страница 10: ...ement doit se faire dans le sens indiqu sur la plaque signal tique de la vanne B IMPORTANT Pour viter tout risque de plaque de glace Bradley recommande de diriger le refoulement de la vanne par un tuy...

Страница 11: ...e 1 perc 3 169 840 1 T 1 NPT x 1 NPT x NPT 4 113 006LN 1 Raccord troit 1 NPT 5 113 006LG 1 Raccord troit NPT 6 145 204 1 Raccord de compression 7 269 783M 1 Tube alimentation 96 8 269 147 1 Attache de...

Страница 12: ...et de la canalisation sans pour autant tre trop serr es Pour obtenir les meilleurs r sultats possibles les unit s doivent tre fournies sur le haut lors de l utilisation de soupapes chaudage et gel Pi...

Страница 13: ...e permet Chauffer jusqu ce que la vanne coule pour purger l eau chaude D pannage PROBL ME CAUSE SOLUTION La vanne antigel coule de l eau L alimentation en eau est trop froide S assurer que l unit est...

Страница 14: ...equipo se debe inspeccionar probar y anotar semanalmente para mantener un funcionamiento adecuado Se debe revisar este equipo anualmente para asegurarse de que cumpla con la norma ANSI Z358 1 Los tra...

Страница 15: ...cci n que se muestra en la placa de identificaci n de la v lvula B V lvula contra quemaduras V lvula contra congelamiento IMPORTANTE Para evitar el peligro de formaci n de una capa de hielo Bradley re...

Страница 16: ...cci n que se muestra en la placa de identificaci n de la v lvula B IMPORTANTE Para evitar el peligro de formaci n de una capa de hielo Bradley recomienda que la descarga de la v lvula se dirija a trav...

Страница 17: ...x NPT de 4 113 006LN 1 Niple de rosca exterior NPT de 1 5 113 006LG 1 Niple de rosca exterior NPT de 6 145 204 1 Conexi n de compresi n 7 269 783M 1 Tubo de suministro de 96 8 269 147 1 Sujetacables...

Страница 18: ...agua tienda a estar est tica o estancada NOTA Apunte las v lvulas hacia abajo para dejar un margen para el desag e el flujo debe ser en la direcci n que se muestra en la placa de identificaci n de la...

Страница 19: ...sta que la v lvula fluya para purgar agua caliente Soluci n de problemas PROBLEMA CAUSA SOLUCI N Fluye agua por la v lvula de protecci n contra congelamiento El suministro de agua est demasiado fr o A...

Отзывы: