S19-876 Installation

1/12/11 

Bradley Corporation • 215-1279 Rev. C; ECM 10-05-011A

Troubleshooting

Problem

Cause

Solution

Low water flow at drench 

shower and eyewash

Insufficient pressure 
Undersized supply piping

Minimum 30 GPM required
Increase pressure/pipe size

Low water flow at drench 

shower or eye wash

Debris in system

Disassemble the showerhead, clean and reassemble
Unscrew the eyewash heads from the yoke, clean and 

reassemble. If still clogged, replace the heads.

Freeze-protection valve is 

flowing water

Power supply is off [if the 

water temperature from the 

valve is below 45°F (7°C)]

Turn the power on.

Water supply is too cold

Make sure the unit is supplied with tempered water.

Defective thermostat [if the 

water temperature from the 

valve is below 45°F (7°C)]

Check continuity and replace if check fails activates at 50°F 

(10°C) (factory-set).

Defective freeze valve [if the 

water temperature from the 

valve is above 45°F (7°C)]

Replace the freeze valve

NOTE:  A water supply that is at least 45°F (7°C) or colder will 

hold the freeze bleed valve open. To close the valve:

1.  turn the water off temporarily or plug the valve until the 

heat trace unit’s heat warms the valve

2.  increase the surface temperature of the valve to above 

45°F (7°C) by immersing the valve in hot water

IMPORTANT:  Make sure that the heat trace unit is 

operating properly before plugging the freeze bleed valve. 

A plugged valve will not provide backup freeze protection 

should the heat trace unit fail.

Scald-protection valve is 

flowing water

Defective scald valve [if the 

water temperature from the 

valve is below 80°F (27°C)]

Replace the scald valve.

Direct sunlight or high 

ambient temperature

Cool the unit.

Defective thermostat

Check continuity and replace if check fails activates at 50°F 

(10°C) (factory-set).

Содержание S19-876

Страница 1: ...bradleycorp com Installation 215 1279 Rev C ECM 10 05 011A 2011 Bradley Corporation Page 1 of 16 1 12 11 S19 876 Drench Hose Service Retrofit Kit for Heat Trace Showers Table of Contents Pre Installation Information 2 Installation 3 Assembly of Components 3 Service Parts List 3 Troubleshooting 4 ...

Страница 2: ...l be made to prevent unauthorized shutoff The ANSI Z358 1 standard requires an uninterruptible supply of flushing fluid at a minimum 30 PSI 0 21 MPa flowing pressure Flushing fluid should be tepid per ANSI Z358 1 The inspection and testing results of this equipment should be recorded weekly to verify proper operation This equipment should be inspected annually to ensure compliance with ANSI Z358 1...

Страница 3: ...hat the upper right plastic shell can be pulled away from the unit or removed completely NOTE Other components may have to be disassembled to remove the shell 2 Expose the pipe plug by partially removing the insulation and then remove plug 3 Connect the drench hose parts as shown using pipe sealant on the threads Do not secure the flag handle permanently at this time 4 Operate the valve to ensure ...

Страница 4: ...nd replace if check fails activates at 50 F 10 C factory set Defective freeze valve if the water temperature from the valve is above 45 F 7 C Replace the freeze valve NOTE A water supply that is at least 45 F 7 C or colder will hold the freeze bleed valve open To close the valve 1 turn the water off temporarily or plug the valve until the heat trace unit s heat warms the valve 2 increase the surfa...

Отзывы: