About the control panel.

 

3

This water heater defaults to the Hybrid 

operating mode.  Available modes are listed 

below and can be selected using the MODE 

button.

Heat Pump (Only) Mode

—RECOMMENDED 

FOR MAXIMUM SAVINGS
Heat Pump is the most energy-efficient mode 

for this water heater. It takes heat from the 

surrounding air to heat the water. The time 

it takes to heat the water is longer in this 

mode, so it may not be sufficient if you have 

a high-demand situation such as a large 

household or company.

Hybrid Mode

Hybrid mode combines the energy 

efficiency of Heat Pump (Only) with the recovery speed 

and power of the Electric (Only) mode in most water usage 

situations.  Hybrid mode will allow the unit to perform like 

a standard electric water heater while providing significant 

energy savings. 

Cold Climate Efficiency setting (CCE)

For installations where ambient conditions may be considered 

cold, an available Cold Climate Efficiency (CCE) setting can be 

activated in the control to achieve additional energy savings 

in Hybrid mode. 
In some regions, rebates may be available which require 

this setting to be used to qualify [e.g. compliance with NEEA 

Northern Climate specification Tier 3 requirements]. Check 

with your local utility for available rebates and requirements. 
The CCE setting is activated by pressing and holding the 

DOWN arrow and the Filter button at the same time for 5 

seconds. “CCE” will display temporarily when CCE settings 

have been activated [“dUC” may display on some models]. To 

deactivate the CCE setting, press and hold the same buttons 

[DOWN arrow & Filter button] at the same time for 5 seconds. 

“Std” will display temporarily when CCE settings have been 

deactivated and the water heater has returned to normal 

operation of the selected mode. 
A ducting kit is also available for use with your heat pump 

water heater if desired. [see www.BradfordWhite.com for 

details]. 
Ducting kits may be installed to achieve directed flow of 

inlet and outlet air for heat pump operation independent of 

whether the CCE setting is activated. Ducting kits may also 

be installed to allow water heater installation in rooms less 

than 700cu.ft. or without louvered doors, as specified in the 

installation instructions.

NOTE: 

 

Energy Guide unit performance, energy consumption 

and savings are based on non-ducted installations in Hybrid 

mode operation at a temperature setting of 135°F (57°C).

Electric (Only) Mode

This mode uses only the upper and lower heating resistance 

elements to heat the water, stopping the cool air discharge 

during heat pump operation. The time it takes to heat the 

water is less in this mode, but it is the LEAST energy-efficient 

mode.
Follow these steps to set Electric (Only) mode:
1. Select Electric (Only) mode using the Mode button.
2.  Input the total days to remain in Electric (Only) mode using

the UP arrow, or remain in Electric (Only) mode indefinitely

by selecting “---”.

3.  Press ENTER
At the end of the selected time period, the unit will switch 

back to the previously selected more energy-efficient mode.

NOTE:

 

 In this mode the green LED light will flash after 48 

hours as an indication that the unti is not operating in the 

most energy efficient mode.  The unit will continue to operate 

in this mode and does not indicate an operating issue.

NOTE: 

 With the CCE setting active, Electric (Only) mode can 

be set for 1-7 days.

Vacation

This feature is used when you will be away from the home for an 

extended period of time and hot water is not needed. In this mode, 

the unit will drop the water temperature down to 50ºF (10°C) and 

will use the most efficient heating mode to conserve energy while 

the heater is sitting idle. The unit will automatically resume heating 

one day before your return, so that hot water will be available. 
For example if you will be gone 14 days, follow these steps:
1. Select VACATION by using the Mode button
2. Input total days you will be gone (in this example, 14) by pressing

the UP arrow button (the default is 7 days)

3. Press ENTER.
The unit will drop the water temperature down to 50ºF (10°C) for 

one day less than you will be gone (in this example, for 13 days). At 

the end of the day before you return (in this example, the 13th day), 

it will automatically return to the previous operating mode and 

heat the water to the original temperature setting so hot water is 

available upon your return.

To access any of these modes:

1.  Press the MODE button on the control to the desired operating

mode.

2.  The green light will be illuminated on the chosen mode.

To Adjust the Temperature

Follow these steps:
1. Press the UP or DOWN arrow on the control panel key pad to

desired temperature.

2. Press ENTER to accept the new setting.

Note:

 To change between °F and °C, press and hold MODE.

In winter months, the water heater will take longer to heat 

incoming water to a preset point due to the colder temperature of 

the incoming water.

Содержание RE2H50S*-1NCWT Series

Страница 1: ...mmended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected to the hot water system If hydrogen is present there will be an unus...

Страница 2: ...igated by a qualified service technician and corrective action must be taken before placing the water heater in service again To reset the temperature limiting control 1 Turn off the power to the wate...

Страница 3: ...ybrid mode operation at a temperature setting of 135 F 57 C Electric Only Mode This mode uses only the upper and lower heating resistance elements to heat the water stopping the cool air discharge dur...

Страница 4: ...ION DRAIN TUBE CLEANING THE FILTER In the Hybrid Heat Pump and High Demand Boost modes the heater moves air through the system and out the back of the unit The filter is in place to protect the evapor...

Страница 5: ...a device that periodically cuts power to the water heater the accuracy of the anode rod depletion sensing feature may become compromised and anode rod inspection every 2 3 years is recommended If the...

Страница 6: ...interfere with the removal of the filter If a separate ducting kit is purchased additional space is required above and to the rear of the water heater for installation Consult the ducting kit manual f...

Страница 7: ...ief valves The BTUH rating of the relief valve must not be less than the input rating of the water heater as indicated on the rating label located on the front of the heater 1 watt 3 412 BTUH Connect...

Страница 8: ...lting from the use of such unauthorized devices If local codes require external application of insulation blanket kits the manufacturer s instructions included with the kit must be carefully followed...

Страница 9: ...lean the heating elements This should only be done by a qualified service personnel The heater is beeping and the display says F11 The water heater has not been filled with water before power ing up P...

Страница 10: ...10 Notes...

Страница 11: ...chauffe un incendie une inondation ou des dommages physiques B Ne rallumez pas le chauffe eau s il n est pas rempli pas d eau C Ne rallumez pas le chauffe eau si le robinet d alimentation d eau froide...

Страница 12: ...avant la remise en service du chauffe eau Pour r initialiser la commande de limitation de temp rature 1 Coupez l alimentation lectrique du chauffe eau 2 Retirez le s panneau x d acc s et l isolation...

Страница 13: ...d pourvues de portes persiennes tel qu indiqu dans les instructions d installation REMARQUE Le rendement de l appareil la consommation et les conomies d nergie selon le Guide de l nergie valent pour...

Страница 14: ...e eau d place l air dans le syst me et le fait ressortir l arri re de l appareil Le filtre est en place pour prot ger l vapora teur de la salet et la poussi re Un filtre air propre est n cessaire pour...

Страница 15: ...e tige d anode peut tre compromise et nous recommandons d inspecter la tige d anode chaque 2 ou 3 ans Si le chauffe eau est inactif pendant une longue p riode de temps et qu il ne peut pas tre vidang...

Страница 16: ...et l arri re du chauffe eau a in de pouvoir installer La trousse de r partition d air sera achet e et un espace additionnel est requis au dessus et l arri re du chauffe eau a in de pouvoir l installer...

Страница 17: ...a valeur nominale d entr e du chauffe eau comme ceci est inscrit sur l tiquette l avant du chauffe eau 1 watt 3 412 Btu h Branchez la sortie de la soupape de s curit une bonde ouverte de telle fa on q...

Страница 18: ...et le chauffe eau ne fournit pas une conduction suffisante pour une masse ad quate La tuyauterie non m tallique les raccords di lectriques ou flexibles etc peuvent isoler lectriquement le chauffe eau...

Страница 19: ...eau tableau N E C 310 16 167 F 75 C 208V 240V 277V 480V 3 000 12 12 14 14 4 000 10 10 12 14 4 500 10 10 10 14 5 000 10 10 10 14 5 500 8 10 10 14 6 000 8 8 10 12 8 000 8 8 8 10 9 000 8 8 10 10 000 8 10...

Страница 20: ...vec de l eau Appuyer sur ENTER pour teindre l alarme puis alimenter le cycle lorsque le r servoir a t rempli Si le r servoir plein d eau a t confirm et que le code F11 appara t il est possible que le...

Страница 21: ...Remarques 21...

Страница 22: ...ado en su totalidad por personal calificado del servicio t cnico Precauciones de Seguridad A Apague el suministro de energ a del calentador de agua si ste sufri un sobrecalentamiento incendio inundaci...

Страница 23: ...ratura alta deber ser investigada por un t cnico calificado del servicio o se deber realizar una acci n correctiva antes de volver a poner en uso el calentador de agua Para reiniciar el control de l m...

Страница 24: ...n puertas de celos a como se especifica en las instrucciones de instalaci n NOTA Tanto el rendimiento de Energy Guide Gu a de Uso de Energ a como el consumo y el ahorro de energ a est n basados en ins...

Страница 25: ...brido Heat Pump only Bomba de Calentami ento solamente y High Demand Boost Alta Demanda Incrementar el calentador mueve aire a trav s del sistema y hacia afuera por la parte trasera de la unidad El fi...

Страница 26: ...varilla del nodo cada 2 o 3 a os Si el calentador de agua estar inactivo por un per odo de tiempo prolongado y el calentador de agua no puede ser drenado se recomienda dejar activado el encendido con...

Страница 27: ...compra un kit de tuber as de aparte se requerir espacio adicional en la parte superior y trasera del calentador de agua para la instalaci n Para acceder a instrucciones espec ficas consulte el manual...

Страница 28: ...do purgado del sistema V LVULA DE ALIVIO ADVERTENCIA Riesgo de da o sobre la unidad El ndice de presi n de la v lvula de alivio no debe superar los 150 PSI 1 03 kPa la m xima presi n de funcionamiento...

Страница 29: ...dos para uso como conductor de conexi n a tierra incluir n un conductor separado para la conexi n a tierra Deber a estar adjunto a las terminales de conexi n a tierra del calentador de agua y la caja...

Страница 30: ...ressor turns on The water heater is operat ing in Hybrid mode Quick ly provides initial amount of hot water then switches to efficient heat pump for majority of heating 30 Soluci n de Problemas Antes...

Страница 31: ...Encendido por Ciclos cuando el tanque haya sido llenado Si la unidad fue confirmada para su llenado con agua y se experimenta un c digo F11 es posible que el c digo sea una falsa indicaci n debido a c...

Страница 32: ...Notas 32...

Отзывы: