SECTION 4: ELECTRICAL HOOK-UP
BEFORE BEGINNING ANY WORK ON THIS INSTALLATION, CONFIRM THE ELECTRICAL
BREAKER IS “OFF” AND THAT ALL MOUNTING AND PLUMBING WORK HAS BEEN
COMPLETED PER THE STATED INSTRUCTIONS.
For use on an individual branch circuit only.
The heater shall be installed using insulated, UL listed, 2 wire cable (2
wire plus ground) of the appropriate size suitable for up to 75°C and protected by the correctly rated circuit breaker.
Refer to the chart below for recommended copper wiring for conductors with a temperature rating of 75°C:
Flow Controlled
Models
Thermostatic
Models
Voltage
Max
power
Max
current
Minimum
wire size
(AWG)
@75°C
(VAC)
(kW)
(A)
TEF024V120
—
120
2.4
20
14
TEF030V120
—
120
3
25
12
TEF035V120
—
120
3.5
29
10
TEF035V240
—
240
3.5
15
14
TEF048V240
—
240
4.8
20
14
TEF055V240
TET055V240
240
5.5
23
12
TEF065V240
TET065V240
240
6.5
27
10
TEF075V240
TET075V240
240
7.5
32
10
TEF095V240
TET095V240
240
9.5
40
8
—
TET115V240
240
11.5
48
8
TEF030V208
—
208
3
15
14
TEF041V208
—
208
4.1
20
14
TEF083V208
TET083V208
208
8.3
40
8
TEF030V277
—
277
3
11
14
TEF041V277
—
277
4.1
14.8
14
TEF060V277
TET060V277
277
6
22
12
TEF080V277
TET080V277
277
8
29
10
TEF090V277
TET090V277
277
9
33
10
TEF100V277
TET100V277
277
10
36
8
*Recommendation for special suffixed models (i.e. CA, ML), are identical to standard models.