45
DIAGNOSTIC CODES ON THE TEMPERATURE CONTROL DISPLAY
The Bradford White EverHot
tankless water heaters have the ability to monitor and display any operating
faults on the control display. The diagnostic codes will display on the monitor and will assist in servicing
the water heater. The following is a listing of the diagnostic codes, which may flash on the monitor in
case of a malfunction with the water heater. Please quote the code displayed when calling for service.
Code
Code Description
Remedy
02
No burner operation
during freeze
protection mode
Service Call
03
Power interruption
during Bath Fill (Water
will not flow when
power returns).
Turn off all hot water taps. Press ON/OFF twice.
10
Air Supply or Exhaust
Blockage
Check that nothing is blocking the flue inlet or exhaust.
Check all vent components for proper connections.
Ensure vent length is within limits.
Ensure condensation collar was installed correctly.
Verify dip switches are set properly.
Check fan for blockage.
11
No Ignition
Check that the gas is turned on at the water heater, gas meter, or cylinder.
Ensure gas type and pressure is correct.
Ensure gas line, meter, and/or regulator is sized properly.
Bleed all air from gas lines.
Verify dip switches are set properly.
Ensure water heater is properly grounded.
Disconnect Manifold Electronic Controls to isolate the problem.
Ensure igniter is operational.
Check igniter wiring harness for damage.
Check gas solenoid valves for open or short circuits.
Remove burner cover and ensure all burners are properly seated.
Remove burner plate and inspect burner surface for condensation or debris.
12
Flame Failure
Check that the gas is turned on at the water heater and gas meter. Check for
obstructions in the flue outlet.
Ensure gas line, meter, and/or regulator is sized properly.
Ensure gas type and pressure is correct.
Bleed all air from gas lines.
Ensure condensation collar was installed properly.
Ensure vent length is within limits.
Verify dip switches are set properly.
Ensure water heater is properly grounded.
Disconnect keypad.
Disconnect Manifold Electronic Controls to isolate the problem.
Check power supply for loose connections.
Check power supply for proper voltage and voltage drops.
Ensure flame rod wire is connected.
Check flame rod for carbon build-up.
Disconnect and reconnect all wiring harnesses on unit and PC board.
Check for DC shorts at components.
Check gas solenoid valves for open or short circuits.
Remove burner plate and inspect burner surface for condensation or debris.
14
Thermal Fuse
Check gas type of unit and ensure it matches gas type being used.
Check for restrictions in air flow around unit and vent terminal.
Check for low water flow in a circulating system causing short-cycling.
Ensure dip switches are set to the proper position.
Check for foreign materials in combustion chamber and/or exhaust piping.
Check heat exchanger for cracks and/or separations.
Check heat exchanger surface for hot spots which indicate blockage due to scale build-
up. Refer to instructions in manual for flushing heat exchanger.
Measure resistance of safety circuit.
Ensure high fire and low fire manifold pressure is correct.
Check for improper conversion of product.
Содержание EverHot TG-150E-N
Страница 20: ...20 Figure 6 Recommended Piping for a Basic Installation...
Страница 21: ...21 Figure 7 Recommended Piping for a Circulation Systems...
Страница 25: ...25 Figure 9 Recommended Piping for Combination Water and Space Heating Applications...
Страница 31: ...31 Figure 11 Wiring Diagram for TG 150E N X TG 180E N X and TG 199E N X Models...
Страница 32: ...32 Figure 12 Wiring Diagram for TG 237E N X and TG 237E N X A Models...
Страница 51: ...51 SECTION IX PARTS LIST TG 150E TG 180E and TG 199E Models...
Страница 53: ...53...
Страница 55: ...55...
Страница 57: ...57...
Страница 59: ...59 TG 237E Models...
Страница 61: ...61...
Страница 63: ...63...
Страница 65: ...65...
Страница 70: ...70 NOTES...
Страница 71: ...71 NOTES...