7

3.  Operation

  

   

 

3.1    Maximum flow rates

  

 

The table below gives maximum flow rates for Charge Air Coolers in either single  

   

 

two or three pass configuration, using either sea water or fresh water cooling.

Max Recommended Flowrate (I/min)

Max Recommended Flowrate (I/min)

Max Recommended Flowrate (I/min)

EC range

50

80

170

FC range

80

120

230

FG range

110

170

320

GL range

200

290

560

GK range

300

450

900

JK range

400

600

1200

PK range

650

1000

2000

RK range

900

1400

2800

Max Recommended Flowrate (I/min)

Max Recommended Flowrate (I/min)

Max Recommended Flowrate (I/min)

EC range

75

120

255

FC range

135

200

380

FG range

180

270

530

GL range

320

470

900

GK range

460

690

1400

JK range

660

1000

2000

PK range

1000

1500

3000

RK range

1400

2150

4300

 

       3.2    General information

        

It is essential that the following instructions are followed to prevent premature  

      

failure of the Charge Air Cooler due to erosion or corrosion.

      

a)  Always maintain the water pH to correct levels. The ideal water pH    

      

 

should be kept within 7.4 to 7.6. On no account should it fall below 7.2 or  

      

 

rise above 7.8. 

 

      

b)  The table above gives the maximum fluid velocities through the cooler  

      

 

and must not be exceeded. If in doubt contact our technical sales team  

        

 

for guidance. 

 

      

c)  Minimum water velocity of 1m/s should be used.  

      

d)  Ensure compliance with water quality and maximum permissible  

 

        

 

pressure requirements.

      

e)  Air must be adequately vented from the water circuit.

      

f)  Stagnant water should not be allowed to accumulate in the cooler.  If   

      

 

it is not in use for any period of time the water should be drained. During  

      

 

commissioning, shutdown and standby periods, if the cooler has not   

      

 

been used over a 4-6 day period, it should be drained, cleaned and kept  

      

 

dry. Where this procedure is not possible, drain the stagnant water and  

      

 

refill the cooler with clean sea or fresh water, which should be replaced 

       

 

with oxygenated sea water every 2-3 days to avoid further decomposition.

 

Take Care

3-Pass

2-Pass

1-Pass

Cooler

3-Pass

2-Pass

1-Pass

Cooler

Sea Water Application (Maximum 2 m/s)

Fresh water Application (Maximum 3 m/s)

Содержание EC120

Страница 1: ...Heat Exchanger Technology by Installation Operation Maintenance Guide CHARGE AIR COOLERS BOWMAN 1 0 0 Y E A R S O F H E AT T R A N S F E R T E C H N O LO G Y ...

Страница 2: ...er Should you require additional advice or assistance please contact your Bowman stockist or distributor Installation Operation Maintenance guides are also available in If you require a copy of this guide in one of these languages visit https www ej bowman com downloads where copies are available to freely download Introduction 2 2 All rights reserved E J Bowman Birmingham Ltd reserve the right to...

Страница 3: ... 7 3 Operation 7 3 1 Maximum flow rates 7 3 1 General information 7 4 Commissioning 8 5 Maintenance Repair 8 5 1 Winter shut down in areas exposed to frost 8 5 2 General Maintenance 9 5 3 Cleaning 9 5 4 End cover screw tightening sequence 9 5 5 Draining any condensate in the body of the cooler 10 6 Potential Service Issues 10 6 1 Tube failures 10 6 2 End covers 10 7 Warranty 10 8 Spare Parts 11 9 ...

Страница 4: ... danger to health Failure to comply with this instruction may result in severe injury This symbol indicates a possible danger to health Failure to comply with this instruction may result in severe injury This symbol indicates a possible risk to health Failure to comply with this instruction may result in injury or damage to property This symbol indicates important information about correct handlin...

Страница 5: ...site directions as shown in the illustration below A filter with a maximum permeability of 2 0mm should be used in the water circuit of the cooler Nothing should be welded to any part of the cooler Each unit has threaded mounting holes on its underside Mounting brackets must be designed to protect the cooler from the vibration generated during engine operation RIGID MOUNTING SHOULD BE AVOIDED The ...

Страница 6: ...nlet and outlet are designed to have hose connections using hose clamps apart from the PK and RK cooler sizes which have flange connection faces Please ensure that the connection flow area is maintained into the cooler and avoid tight bends to prevent excessive pressure loss Type Connection Type Size Water Connections EC120 Hose 52 mm 3 4 BSP FC100 Hose 52 mm 1 BSP FG100 Hose 76 mm 11 4 BSP GL140 ...

Страница 7: ... to correct levels The ideal water pH should be kept within 7 4 to 7 6 On no account should it fall below 7 2 or rise above 7 8 b The table above gives the maximum fluid velocities through the cooler and must not be exceeded If in doubt contact our technical sales team for guidance c Minimum water velocity of 1m s should be used d Ensure compliance with water quality and maximum permissible pressu...

Страница 8: ...ckish brown thin film layer The process of ensuring that copper alloy receives an effective oxide coating prior to service is known as conditioning which is a very important stage for the alloy Ferrous sulphate can be used if commissioning in clean sea water is not possible Schedule cleaning may help to reduce the risk possibly with non metallic brushes Please refer to Copper Alliance webpage for ...

Страница 9: ...al cleaner to work before hosing down with plenty of water Please refer to the spare parts list for details of the tube materials e The tube stack should be flushed through with clean water to remove all traces of cleaning chemicals detergents If necessary the cleaning fluid should be neutralised f When refitting the end covers after cleaning new O seals must be used 5 4 End cover screw tightening...

Страница 10: ...lease avoid extended exposure to stagnant water which can encourage sulphate reducing bacteria and in the presence of deposits pitting corrosion will take place under the deposits Titanium tube stacks Titanium tube stacks are available as a replacement for standard cupro nickel tube stacks for applications where corrosion issues are being experienced Titanium provides a highly durable long life so...

Страница 11: ...e the BOWMAN Conditions of Sale A copy of which is available on request or via download from the website www ej bowman com 8 Spare Parts List A comprehensive stock of spare parts is always available Please contact either your nearest stockist or our sales office for price and availability 9 CE Marking Documentation Charge Air Coolers are covered by the Pressure Equipment Directive 2014 68 EU which...

Страница 12: ...e the right to change specifications without prior notice K Header Tank Heat Exchangers Engine Oil Coolers Stainless Steel Heat Exchangers Transmission Coolers Swimming Pool Heat Exchangers Exhaust Gas Heat Exchangers Hydraulic Oil Coolers Plate Heat Exchangers FM38224 BOWMAN 1 0 0 Y E A R S O F H E AT T R A N S F E R T E C H N O LO G Y EJ Bowman Birmingham Ltd Chester Street Birmingham B6 4AP UK ...

Отзывы: