Inspection and maintenance
Copyright (optional information)
6 720 643 068 (2011/06)
14.1 Description of various steps
14.1.1 Calling up the latest fault (service function 6.A)
B
Select service function
6.A
(
Æ
page 71).
14.1.2 Fresh water filter (only combi boiler ZWB..-3A)
B
Close cold water tap.
B
Depressurize the cold water pipe.
B
To access the filter remove the safety clip (step 1), pull
out the pipe (step 2), and remove the filter from the
pipe (step 3).
B
If necessary, clean with plastic brush under running
water.
Fig. 76 Filter in fresh water pipe
(combi boiler ZWB..-3A only)
14.1.3 Plate type heat exchanger
(only combi boiler ZWB..-3A)
If the DHW output on the combi boiler is significantly
reduced:
B
Check filter in the cold water pipe for contamination
(
Æ
Fig. 82).
B
Depressurize the appliance.
B
Remove plate type heat exchanger and replace
-or-
B
Descale with descaling agent approved for stainless
steel (Grade 316-1.4401).
To remove the plate type heat exchanger:
B
Unplug electrical connections.
B
Remove hose from safety relief valve.
Fig. 77 Unplugging electrical connections / removing hose
from safety relief valve
B
Loosen/remove pipe connections.
Fig. 78 Removing pipe connections
An overview of the faults can be found on
page 91.