78
|
Gas type conversion
Copyright (optional information)
6 720 643 068 (2011/06)
11.4 Dynamic gas pressure test
B
Switch the appliance OFF and close the gas shut-off
valve.
B
Loosen the screw in the test port for gas inlet pressure
(
Æ
Fig. 72, [1]) and connect a pressure gauge
(
Æ
Fig. 74).
Fig. 74 Dynamic gas pressure test port
B
Turn on the gas cock and switch the appliance ON.
B
Press and hold the emissions test button until it
lights up.
The display shows the supply temperature alternating
with
=
maximum set output in heating mode
.
B
Briefly press the emissions test button .
The display shows the supply temperature in
alternation with
=
maximum nominal output
.
B
Check the required inlet gas pressure according to
table 31.
B
Repeatedly press the emissions test button
until the
light goes out.
The display returns to the supply temperature.
B
Switch the appliance OFF, turn off the gas cock, remove
the pressure gauge and tighten the screw in the test
port for gas inlet pressure.
B
Reinstall the cover.
6 720 614 090-34.1O
Gas type
Nominal
pressure
" W.C.
(mbar)
Permissible pressure
range for maximum
nominal output
" W.C. (mbar)
NG
7 (17.4)
3.5-10.5 (8.7-26.1)
LPG (propane)
11 (27.4)
8-13 (19.9-32.3)
Tab. 31 Inlet gas pressure
Do not operate the appliance if the measured
value is below or above these values.
Determine the cause and eliminate the fault. If
this is not possible, block the appliance on the
gas side and notify the gas supplier.