Heatronic boiler control settings
|
65
6 720 643 068 (2011/06)
Copyright (optional information)
10 Heatronic boiler control settings
10.1 Guideline to service functions
The Heatronic allows easy setting and testing of many
appliance functions.
For an overview of service functions, see Chapter 10.2 on
page 66.
Fig. 66 Overview of the controls
1
Emissions test button
2
Service button
3
Display
4
ECO button, service functions “up”
5
Key pad lock, service functions “down”
Selecting a service function
The service functions are subdivided into two levels: The
1st level
includes service functions
up to 0.E
, the
2nd
level
includes service functions
starting with 8.A
.
B
Press and hold the service button
until it illuminates.
The display shows a code such as 1.A (first service
level).
B
Repeatedly press the key pad lock button or ECO
button to scroll to the desired service function.
B
Press and release the emissions test button .
The emissions test button will light up and the
display shows the setting for the selected service
function.
Adjust Value
B
Repeatedly press the key pad lock button or ECO
button to adjust the value up or down.
B
Record the value in the commissioning log (
Æ
page 97).
Saving the value
B
Press and hold the emissions test button until the
display shows
(value saved).
Exiting the service function without saving values
B
Briefly press the emissions test button .
The light of the emissions test button will go out.
Restoring factory settings
In order to reset all values for the service levels 1 and 2 to
the factory setting:
B
Press and hold the service button until it illuminates.
The display shows a code such as 1.A (first service
level). Press the ECO button and key pad lock button
simultaneously until e.g. 8.A appears (second service
level).
B
On the second service level, select the service function
8.E and value
00
. The appliance restarts with the default
settings.
max
1
2
3
4
e
6
max
1
2
3
4
5
6
1
2
3
4
5
6 720 641 933-52.1O
reset
eco
min
The unit automatically exits the service level if
no button is pressed for 15 minutes.