RM2-DP12

Module Description

CL200

Edition

Содержание RM2-DP12

Страница 1: ...RM2 DP12 Module Description CL200 Edition ...

Страница 2: ...070 072 449 102 01 12 GB 2000 2001 by Robert Bosch GmbH Germany All rights reserved including applications for protective rights Reproduction or distribution by any means is subject to our prior written permission Discretionary charge 6 ...

Страница 3: ......

Страница 4: ...he RM2 DP12 System 2 1 3 Power Supply 3 1 4 PROFIBUS DP 4 1 4 1 Connection 4 1 4 2 Setting of Bus Address 4 2 4 3 Baud Rate 4 2 5 Status Display 5 1 5 1 Static Display 5 1 5 2 Flashing Display 5 3 5 3 Alternating Display with Starting Signal F 5 4 5 4 Alternating Display with Starting Signal H 5 5 6 I O Modules 6 1 6 1 Supply 6 1 6 2 Addressing 6 2 6 3 Additional Information regarding the I O Modu...

Страница 5: ...1070 072 449 102 01 12 GB II Contents ...

Страница 6: ...ration in industrial environments Class A emissions i e no direct connection to the public low voltage power supply connection to the medium or high voltage system via a trans former The following applies to the usage in residential environments in business and commercial areas and in small enterprises Installation in a switch cabinet or an enclosure with high shield attenuation Lines that exit th...

Страница 7: ...Tampering with the hardware or software ignoring warning signs attached to the components or non compliance with the warning notes given in this manual can result in serious bodily injury or property damage Only electrotechnicians as recognized under IEV 826 09 1 modified who are familiar with the contents of this manual may install and service the described products Such personnel is due to their...

Страница 8: ...ducts Warning of dangerous electrical voltage Warning of danger caused by batteries Components sensitive to electrostatic discharge Disconnect from mains before opening PE protective earth conductor Functional earthing or low noise earth only Connection of shield conductor only ...

Страница 9: ...in whole or in part may result in personal injuries DANGER This symbol is used whenever insufficient or lacking compliance with instructions may result in personal injury CAUTION This symbol is used wherever insufficient or lacking compliance with instructions may result in damage to equipment or data files Þ Þ Þ Þ This symbol is used to alert the user to an item of special interest This symbol is...

Страница 10: ... personal injury damage to equipment or environmental hazards Therefore possible retrofits or modifications to the system using third party equipment have to be approved by Bosch DANGEROUS ELECTRICAL VOLTAGE Unless described otherwise maintenance work must be performed on inactive systems During this process the system must be protected against unauthorized or accidental restart Measuring or testi...

Страница 11: ...e prescribed protective packaging ESD sensitive components may only be handled at special ESD workplaces Personnel working surfaces as well as all equipment and tools which may come into contact with ESD sensitive components must have the same potential e g by grounding Wear an approved grounding bracelet The grounding bracelet must be connected to the working surface via a cable with an integrate...

Страница 12: ...o the previous edition are marked by black vertical bars in the margin Trademarks Upon delivery all trademarks of software installed on Bosch products are the property of the respective manufacturer Upon delivery all installed software is copyright protected The software may only be reproduced with the approval of Bosch or in accordance with the license agreement of the respective manufacturer PRO...

Страница 13: ...1070 072 449 102 01 12 GB 1 8 Safety Instructions ...

Страница 14: ...B System Introduction 2 1 2 Introduction to the RM2 DP12 System The RM2 DP12 module provides you with the possibility to create at the PROFIBUS DP a modular slave node with modules of the CL200 PLC module range Fig 1 RM2 DP12 ...

Страница 15: ... plugged into a CL200 mounting rack It is supplied with a 24 V voltage and provides the internal 7 5 V supply voltage 1 2 A for the in and output modules The module is provided with a singular module width and must be operated on slot 1 Fig 2 RM2 DP12 with mounting rack ...

Страница 16: ... RM2 DP12 module provides the internal 7 5 V power supply for the in and output modules so that an additional power supply unit for the internal supply of the modules is not necessary also refer to I O modules CAUTION Do not operate the RM2 DP12 module together with an NT200 power supply unit or with a ZE200 central unit X10 pin assignment Pin Designation 1 24 V 2 0 V Fig 3 X10 power supply ...

Страница 17: ...1070 072 449 102 01 12 GB Power Supply 3 2 ...

Страница 18: ...s located on the front panel The pin assignment corresponds to the PROFIBUS standard PROFIBUS DP X71 connection Pin Name Significance 1 n c 2 n c 3 B_LTG Receiving sending data P 4 RTS_SIG Repeater control signal 5 GND_ISO Data ground 6 P5V_ISO Supply voltage 7 n c 8 A_LTG Receiving sending data N 9 GND_ISO Repeater control signal Fig 4 Pin assignment PROFIBUS DP At the PROFIBUS DP X71 connection ...

Страница 19: ...set by means of the S1 DIP switch Þ Þ Þ Þ The set bus address will only be scanned during run up i e when the supply voltage is applied to the X10 connection Switch 8 7 6 5 4 3 2 1 Significance 2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 0 Value 128 64 32 16 8 4 2 1 Fig 5 DIP Switch S1 4 3 Baud Rate The module adapts itself automatically to the PROFIBUS DP s baud rate 9600 Baud 12 Mbaud ...

Страница 20: ...splay with starting signal F Alternating display with starting signal H 7 segment display SEG_A SEG_F SEG_B SEG_G SEG_E SEG_C SEG_D decimal point 5 1 Static Display Display Status Normal operation Operate Mode r Remote Test SEG_A SYNC Mode SEG_D FREEZE Mode SEG_A SEG_D SYNC FREEZE Mode 0 CLEAR Mode 1 I O diagnostic message 2 LEAVE Master 3 Offline 4 5 Parameterization error 6 Configuration error 7...

Страница 21: ...ate an error LEAVE Master The slave is at the bus i e that it is synchronous to the baud rate and waits for the parameterization and configuration by a master Reasons for this indication are Slave is not addressed by a master wrong node address The address monitoring function for the master has become inactive Wrong ID number in the parameterization message Parameterization data length too large O...

Страница 22: ...ransmitted via the PROFIBUS DP Overflow of DP input data buffer The number of the input data bytes recognized at the peripheral bus is higher than the number that can be transmitted via the PROFIBUS DP Overflow of DP output data buffer The number of the output data bytes recognized at the peripheral bus is higher than the number that can be transmitted via the PROFIBUS DP No I O assignment found N...

Страница 23: ...odule number Module number of an input module lies outside of the permissible range i e 47 F b Module number Module number of an output module lies outside of the permissible range i e 47 F d Module number In and output module have been given the same module number F C Module number A module is logically located in the wrong area i e An output module is logically located in the input area An input...

Страница 24: ...1070 072 449 102 01 12 GB Status Display 5 5 5 4 Alternating Display with Starting Signal H Internal hard or software error ...

Страница 25: ...1070 072 449 102 01 12 GB Status Display 5 6 ...

Страница 26: ...5 mA A24V 0 5A 16 outputs 075098 2 O 60 mA A24V 0 5A 32 outputs 078917 4 O 68 mA A24V 2A 8 outputs 077418 1 O 40 mA Relay 8 outputs 077200 1 O 38 mA E16 A8 081376 2 I 2 O 45 mA E16 A16 081661 2 I 2 O 57 mA Aana analog output 077138 4 O 80 mA A20 ana 4 078914 8 O 70 mA A10 ana 4 078507 8 O 60 mA A10 ana 8 078295 16 O 60 mA Eana analog input 077141 32 I 80 mA E20 ana 078911 32 I 80 mA POS SA1 077100...

Страница 27: ...d byte per byte For special applications the E24V 16fold input module and the A24V 0 5A 16fold output module can transmit the data entirely consistently while the E24V 32fold input module can transmit the data word consis tently If you want to use this function the following conditions must be fulfilled Enter the module as consistent in the configuration software Plug the jumper on the module onto...

Страница 28: ...values exist for the modular DP station Please observe the limit value of the current The I O modules maximum current input from the peripheral bus supply 7 5 V must not exceed 1 2 A For inputs a maximum of 244 bytes is supported For outputs a maximum of 244 bytes is supported The sum of all possible in and outputs is 384 bytes A maximum of 38 I O modules ...

Страница 29: ...1070 072 449 102 01 12 GB I O Modules 6 4 ...

Страница 30: ...ge of the RM2 DP12 module please comply with the following The ambient temperature must not exceed 55 C Ensure sufficient air circulation in order to avoid heat accumulation Expansions are possible but keep the distances between the mounting racks defined for the CL200 In a multiple tier construction the module can only be operated in the lower tier ...

Страница 31: ...1070 072 449 102 01 12 GB Ambient Temperature 7 2 ...

Страница 32: ...ass 2 e g for display on the DP monitor via the PROFIBUS DP In addition status 1 will be displayed on the 7 segment display as a group message for diagnosis is pending Diagnostic information overview Byte Function 0 Station_Status_1 1 Station_Status_2 2 Station_Status_3 3 Master_Add 4 Ident_High 5 Ident_Low 6 Header for external diagnosis 7 12 6 bytes external diagnosis Coding of the identifier re...

Страница 33: ...1070 072 449 102 01 12 GB DP Diagnostic Information 8 2 ...

Страница 34: ...pply of bus interface X71 P5VISO GNDISO 5 externally 100 mA max RS485 electrically isolated Degree of protection IP20 as per DIN VDE 0470 1 incorporated in the housing Class of protection 1 as per VDE 0106 T1 or VDE 0160 IEC 536 Insulation test 350 VAC 500 VDC Atmospheric pressure Operation up to 2000 m above sea level as per IEC 1131 2 Humidity rating RH 2 5 95 as per IEC 1131 2 F as per DIN 4004...

Страница 35: ... as per EN 50081 2 Frequency 30 230 mHz limit value 30 dB mV m in 30 m frequency 230 1000 mHz limit value 37 dB mV m in 30 m EMI resistance High frequency electromagnetic fields as per IEC 1131 2 Test field strength 10 V m Frequency range 27 to 500 MHz Sweep rate 0 0015 dec s Electrostatic discharges on accessible housing parts as per EN 50082 2 ESD resistance 4 for humidity rating RH 2 Air discha...

Страница 36: ...1070 072 449 102 01 12 GB HB SP BRC EP Printed in Germany ...