Electric Drives
and Controls
5−37
Bosch Rexroth AG
RhoMotion
1070072367 / 04
CAN-Bus peripheral equipment
D
IOKind Block n
:
1
D
1stAdr.Block n
:
0
D
Length Block n
:
8
D
Ident. Block n
:
643
D
Bus-no.Block n
:
2
The block number n is obtained from the whole configuration of CAN mo-
dules (n=1..40).
1stAddr must be matched with other analog inputs channels. If for exam-
ple a B~IO analog input module is used simultaneously with 4 analog in-
puts, for which the initial address is set =0, the value 8 must be set as the
initial address of the SR-CAN analog inputs.
The adjustment of the initial addresses depends on which one of the two
CAN busses the I/O module is driven at. It must be ensured that there is
no overlap for the address assignment.
In the machine parameter P407, the 8 byte data block is assigned to the
4 input channels. See also 5−38, assignment of the analog input chan-
nels (P407).
Identifier depends on the adjusted node-ID (Offset address) of the SR-
CAN module :
Identifier = 640 + Node-ID
2. Digital-input block
D
IOKind Block n
:
0
D
1stAdr.Block n
:
(212)
D
Length Block n
:
1
D
Ident. Block n
:
387
D
Bus-no.Block n
:
2
The block number n is obtained from the whole configuration of CAN-
modules (n = 1..40).
1stAddr gives the initial address in the rho4 interface and must be mat-
ched with other digital input channels.
Identifier depends on the adjusted Node-ID (Offset address) of the SR-
CAN module :
Identifier = 384 + Node-ID
Содержание Rexroth Rho 4.0
Страница 12: ...XII Electric Drives and Controls Bosch Rexroth AG RhoMotion 1070072367 04 Contents Notes ...
Страница 22: ...2 2 Electric Drives and Controls Bosch Rexroth AG RhoMotion 1070072367 04 System overview Notes ...
Страница 78: ...4 14 Electric Drives and Controls Bosch Rexroth AG RhoMotion 1070072367 04 PCLrho4 0 Notes ...
Страница 168: ...A 4 Electric Drives and Controls Bosch Rexroth AG RhoMotion 1070072367 04 Appendix Notes ...