Startup and Parameterization
82
Bosch Rexroth AG
DOK-CONTRL-ILPSDO8****-AW04-EN-P
Rexroth Inline Module with Safe Digital Outputs R-IB IL 24 PSDO 8-PAC
14.3
Startup and Parameterization
Checklist for startup and parameterization of the safety module
Device type/equipment identification
Version: HW/FW/FW
Date
Editor
Test engineer
Remark
No. Requirement (mandatory)
Yes
Remark
1
Was startup completed according to the specifications (specifications
from the planning phase or according to the application description)?
2
During startup, is it ensured that any person starting hazardous
movements intentionally can only do so with a direct view of the danger
zone?
3
Are all parameters parameterized for the outputs?
4
For outputs that are parameterized for two-channel operation, are both
channels parameterized correctly for each other?
5
Are the output test pulses parameterized according to the actuator to be
connected?
6
Has the switch-off delay for stop category 1 been observed in the
calculation of the total response time for the machine/system?
No. Requirement (optional)
Yes
No
Remark
7
Are safety distances that must be observed calculated according to the
response and delay times implemented?
Date
Signature (editor)
Date
Signature (test engineer)