Errors: Messages and Removal
58
Bosch Rexroth AG
DOK-CONTRL-ILPSDO8****-AW04-EN-P
Rexroth Inline Module with Safe Digital Outputs R-IB IL 24 PSDO 8-PAC
9.2
Supply Voltage Errors
Acknowledgment: Yes (1)
Acknowledging the diagnostic message deletes the message and activates the
outputs.
Undervoltage at U
M
Supply voltage U
M
is measured. If U
M
< 17 V, a diagnostic message is generated.
Error cause
Error code
(hex)
LED
Remark
Effect
Remedy
Acknow-
ledgment
Undervoltage
U
M
01F0
UM
flashing
U
M
below the
permissible voltage
range
All module outputs
are in the safe state
Check and supply
voltage level
Check supply line
length and load
Yes (1)
Fig. 9-2
Supply voltage U
M
errors