Rexroth IndraDrive
Electrical Installation
7-7
DOK-INDRV*-HMV-*******-PR01-EN-P
7.3 Electrical
Data
HMV01.1E-W0030, -W0075, -W0120
Designation
Symbol
Unit
HMV01.1E-W0030
HMV01.1E-W0075
HMV01.1E-W0120
kind of connection (mode of operation at
the mains)
-
-
3-phase
mains input voltage (rated voltage)
U
LN
V
380 -10% to 480 +10%
transient overvoltage limit values
U
L trans max
V
1200
mains frequency
f
LN
Hz
48 to 62
Maximum mains frequency change per
time unit
df
LN
/t
Hz/s
2% * f
LN
mains input continuous current (r.m.s.
value)
I
LN cont
A
50
125
200
connected mains power without DC bus
choke (at max. DC bus power)
1)
S
LN
kW
18
45
72
connected mains power with DC bus
choke (at max. DC bus power)
S
LN (L_DC)
kW
30
75
120
power factor (cos
ϕ
)
cos
ϕ
-
1
DC bus voltage (range)
U
DC
V
435 to 710
upper DC bus voltage limit (shutdown
threshold)
2)
U
DC limit (max)
V
900
lower DC bus voltage limit (shutdown
threshold)
3)
U
DC limit (min)
V
0,75 *
¥
2 * U
LN
continuous DC bus power (at U
LN
=400V)
with choke
4)
P
DC cont
kW
30
75
120
continuous DC bus power (at U
LN
=400V)
without choke
P
DC cont
kW
18
45
72
continuous DC bus power depending on
mains input voltage
at U
LN
< 400 V: 1% power reduction per 4 V
at U
LN
> 400 V: 1% power increasing per 4 V
peak DC bus power
(for max. 0,3 s with a preload of
0,6 x I
LN cont
and 40 °C ambient
temperature)
P
DC peak
kW
45
112
180
braking resistor switch-on threshold
U
DC (R_DC On)
V
constant 820V or
variable 80V +
¥
2 * U
LN
continuous brake power
kW
1,5
2
2,5
maximum brake power
kW
36
90
130
brake energy absorption
kWs
100
250
500
DC bus capacity
C
DC
µ
F
1410
3760
5640
overload capacity
factor / duration
I
out_max1/
I
out_cont1
A
factor 2,5
(related to rated power without DC bus choke)
power dissipation
P
Diss
W
150
340
500
1)
These data refer to a supply impedance of 40
µ
H.
2)
When the upper DC bus voltage limit has been reached, the supply unit does
not switch off. The display shows a warning message. The output stages of
the drive controllers are locked.
3)
When the lower DC bus voltage limit has been reached, the supply unit does
not switch off. The display shows a warning message. At an undervoltage of
0,75 * U
LN
the supply unit switches off.
4)
Inductance of the choke:
HMV01.1E-W0030: 400
µ
H
HMV01.1E-W0075: 200
µ
H
HMV01.1E-W0120: 100
µ
H
Fig. 7-3:
Technical data
Содержание Rexroth IndraDrive HMV01.1E-W0030
Страница 24: ...3 12 Safety Instructions for Electric Drives and Controls Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Страница 28: ...4 4 Identifying and Checking the Delivered Components Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Страница 30: ...5 2 Transport and Storage Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Страница 40: ...6 10 Mechanical Mounting Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Страница 88: ...9 8 Control Mains Contactor Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Страница 121: ...Rexroth IndraDrive Appendix 13 21 DOK INDRV HMV PR01 EN P Dimensions Fig 13 24 HFD0x 2 480 0065 ...
Страница 122: ...13 22 Appendix Rexroth IndraDrive DOK INDRV HMV PR01 EN P Fig 13 25 HFD01 2 480 0026 ...
Страница 123: ...Rexroth IndraDrive Appendix 13 23 DOK INDRV HMV PR01 EN P Fig 13 26 HFD02 2 480 0026 ...
Страница 129: ...Rexroth IndraDrive Index 14 5 DOK INDRV HMV PR01 EN P X14 7 30 X2 7 22 X3 7 23 X31 7 25 X32 7 27 X33 7 29 ...
Страница 130: ...14 6 Index Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Страница 131: ......