13-20
Appendix
Rexroth IndraDrive
DOK-INDRV*-HMV-*******-PR01-EN-P
Versions
Filter
Type Supply Unit/
Frequency Converter
Mains current
[A
eff
]
Limit Values
EN61800-3
1)
HFD01.2-480-0026
1
HMV01.1R-W0018
26
class A, group 2 (curve 2.1/2.2)
HFD01.2-480-0065
1
HMV01.1R-W0045; HMV01.1E-
W0030
65
class A, group 2 (curve 2.1/2.2)
HFD01.2-480-0098
1
HMV01.1R-W0065
94
class A, group 2 (curve 2.1/2.2)
HFD01.2-480-0125
1
HMV01.1E-W0075
125
class A, group 2 (curve 1.1/1.2)
HFD01.2-480-0202
1
HMV01.1E-W0120
202
class A, group 2 (curve 1.1/1.2)
HFD02.2-480-0026
2
HMV01.1R-W0018
26
class A, group 2 (curve 2.1/2.2)
HFD02.2-480-0065
2
HMV01.1R-W0045; HMV01.1E-
W0030
65
class A, group 2 (curve 2.1/2.2)
HFD02.2-480-0094
2
HMV01.1R-W0065
94
class A, group 2 (curve 2.1/2.2)
HFD02.2-480-0125
2
HMV01.1E-W0075
125
class A, group 2 (curve 1.1/1.2)
HFD02.2-480-0202
2
HMV01.1E-W0120
202
class A, group 2 (curve 1.1/1.2)
HFD03.2-480-0026
3
HMV01.1R-W0018
26
class B, group 1 (curve 4.1/4.2)
HFD03.2-480-0065
3
HMV01.1R-W0045; HMV01.1E-
W0030
65
class B, group 1 (curve 4.1/4.2)
HFD03.2-480-0094
3
HMV01.1R-W0065
94
class B, group 1 (curve 4.1/4.2)
1)
see following figure
Fig. 13-22: Versions
Limit values for line-based disturbances (DIN EN 55011 / DIN EN 61800-3/A11)
1.1
1.2
2.1
3.1
4.1
2.2
3.2
4.2
1.1
1.2
2.1
2.2
3.1
3.2
4.1
4.2
130
120
100
90
79
66
56
125
115
86
76
60
56
46
115
105
73
50
60
70
class A, group 2 , QSP, I > 100A
(second environment)
class A, group 2 , AV, I < 100A
(second environment)
class A, group 1 , QSP,
(first environment, restricted
distribution, first environment also if
source of interference in second
environment)
class A, group 1 , AV,
(first environment, restricted
distribution, first environment also if
source of interference in second
environment)
class B, group 1 , QSP,
(first environment, general
distribution, first environment also if
source of interference in second
environment)
class B, group 1 , AV,
(first environment, general
distribution, first environment also if
source of interference in second
environment)
class A, group 2 , AV, I > 100A
(second environment)
class A, group 2 , QSP, I < 100A
(second environment)
QSP:
quasi peak value
AV:
average value
Fig. 13-23: Limit values for line-based disturbances (DIN 55011/DIN 61800-
3/A11)
Содержание Rexroth IndraDrive HMV01.1E-W0030
Страница 24: ...3 12 Safety Instructions for Electric Drives and Controls Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Страница 28: ...4 4 Identifying and Checking the Delivered Components Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Страница 30: ...5 2 Transport and Storage Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Страница 40: ...6 10 Mechanical Mounting Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Страница 88: ...9 8 Control Mains Contactor Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Страница 121: ...Rexroth IndraDrive Appendix 13 21 DOK INDRV HMV PR01 EN P Dimensions Fig 13 24 HFD0x 2 480 0065 ...
Страница 122: ...13 22 Appendix Rexroth IndraDrive DOK INDRV HMV PR01 EN P Fig 13 25 HFD01 2 480 0026 ...
Страница 123: ...Rexroth IndraDrive Appendix 13 23 DOK INDRV HMV PR01 EN P Fig 13 26 HFD02 2 480 0026 ...
Страница 129: ...Rexroth IndraDrive Index 14 5 DOK INDRV HMV PR01 EN P X14 7 30 X2 7 22 X3 7 23 X31 7 25 X32 7 27 X33 7 29 ...
Страница 130: ...14 6 Index Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Страница 131: ......