Badly grounded control cabinet doors act as antennas. Therefore, connect the
control cabinet doors to the cabinet on top, in the middle and on the bottom via
short equipment grounding conductors with a cross section of at least 6 mm
2
or, even better, via grounding straps with the same cross section. Make sure
connection points have good contact.
6.2.3
Control Cabinet Mounting According to Interference Areas - Exemplary
Arrangements
Supply Units With Regeneration
Do not operate any additional loads at the mains filter!
Do not operate any other loads at the connection from the mains
filter output to the mains connection of the supply unit.
For motor blowers and power supply units, for example, use sepa‐
rate mains filters.
DOK-INDRV*-HMS02*UL***-IB03-EN-P
Rexroth IndraDrive Drive Controllers Power Sections HMS02
Bosch Rexroth AG
47/67
EMC Measures for Design and Installation