Interfering AC voltage components such as resulting from an uncontrolled 3-
phase current bridge connection without smoothing with a ripple factor (see DIN
40110/10.75, section 1.2) of 5 % are permissible.
It follows from the above that as upper voltage limit the greatest absolute value
is 30.2 V and as lower voltage limit the lowest absolute value is 18.5 V.
Fig.7-18:
Illustration of the limit values for the 24 VDC voltage
Project Planning Manual | Rexroth IndraControl VPP 21.2