VFD (Variable frequency drive)
51/80
Hägglunds DOb, RE 15327-WA/05.2017, Installation and maintenance manual,
Bosch Rexroth AB
9.3.3 System Parameters
9.3.3.1 b0: Basic system parameters
This function is used to set parameters or read parameter settings fast. Five access
modes are available with parameter b0.00.
Code
Name
Setting range
Min.
Attri.
b0.00
Access authority setting
0…..4
-
Run
•
0: Basic parameters
ONLY parameters in group b0, d0, C0, E0, U0, U1 are visible.
•
1: Standard parameters
Parameters in group C1, C2, C3, E5, E8 are ADDITIONALLY visible.
•
2: Advanced parameters
Parameters in group E1, E2, E3, E4, E9, H0, H1, H8, and H9 are ADDITIONALLY
visible.
•
3: Start-up parameters
Parameters in group b0, d0 and Monitoring Parameters are always visible.
•
4: Modified parameters
This option provides the possibility for users to view or modify the parameter
settings which have been modified and different than default settings.
9.3.4 Group C: Power Parameters
The Group C: Power Parameters is divided in:
C0: Power Control parameters
C1: Motor and system parameters
C2: V/F control parameters
C3: Vector control parameters.
9.3.4.1 C0: Power Control parameters
Code
Name
Setting range
Default
Min
Attri.
C0.01
Normal/ Heavy
Duty setting
0: Normal Duty
1: Heavy Duty
1
-
Stop
This function is used for switching the duty mode of a frequency converter according
to the load type of the actual application.
•
0: ND (Normal duty)
Code
Name
Setting range
Default
Min.
Attri.
C1.75
Low speed
derating frequency
0.10...300,00
25.00
0.01
Run
Change the duty mode to 'Normal duty' by modifying the parameter setting from '1'
to '0' according to the actual application.
•
1: HD (Heavy duty). This mode is set by default.