68/83 ctrlX
SAFETY
| Device type SAFEX-C.15
R911405651, Bosch Rexroth AG, DOK-XSAFE*-SAFEX-C.1XC-IT03-EN-P, Edition 03
10.3.1
Ethernet 1 interface:
Tabelle 62:
LED Ethernet 1-LINK / LAN
LINK / LAN
Ethernet
Color
Flashing pattern
Meaning
- Off
No
connection
Green
Permanently illuminated
A connection to the network
is available
Yellow
Flashing
A connection to the network
is available with telegram
traffic (Ethernet
communication active)
L/A
EtherCAT
Color
Flashing pattern
Meaning
Yellow
Off
No link to EtherCAT
master is available
Yellow
On
Link to EtherCAT master is
available, no activity on the
bus
Yellow Flashing
Link to EtherCAT master is
available with active data
transmission
EtherCAT - Diagnostics
Tabelle 63:
LED Ethernet status - EtherCAT, combination of RUN and Error LED
Fieldbus
status
(NET ST)
Color
Flashing pattern
Meaning
- Off
Initialization
Green Flashing
PRE-OPERATIONAL
Green Flashes
once SAFE-OPERATIONAL
Green Permanently
illuminated
OPERATIONAL
- Off
No
error
Red Flashing
Invalid
configuration
Red
Flashes once
Local error
Red
Flashes twice
Watchdog timeout