Dimensions
139.70 mm x 209.60 mm x 31.80 mm
(5.50 in x 8.25 in x 1.25 in)
Power/Voltage
(Standby battery)
16.5 VAC, 40VA (~)
Rated 3.7 VDC, 3050mAH EVE ENERGY CO Part No P0046-LF (Not user
replaceable). For standby battery to be operative, the tamper switch is
required to be engaged.
Transformer power/voltage
Must meet country specific requirements
Current Draw
60 mA
Wire Gauge
0.65 mm (22 AWG) to 2.0 mm (18 AWG)
Temperature (operating)
0
゚
C to +49
゚
C (+32
゚
F to+120
゚
F)
Relative Humidity
0% to 93% (non-condensing)
Device testing
To ensure proper functionality, the device must be tested at least once
every year by an installer.
Wall and Cover Tamper Switch Transmits a tamper signal when someone removes the device from its
base or pulls it away from the wall.
Frequency
433.42 MHz
Table 4.1: Specifications
LEDs
The repeater utilizes an external LED indicator to status the operation of the repeater. Refer to
the table below for LED descriptions.
LED Condition
Pattern Description
On (Normal)
–
Indicates the repeater is functioning normally.
Off
–
Indicates there is a power failure to the repeater, or that the
receiver is not wired correctly.
Continuous Flash: 1 sec
rate for 5 sec
–
Indicates the repeater is being powered up, and conduction
manufacturing test initializations.
Continuous Flash: A 3-
pulse signal, followed by
a short delay after the 3
rd
pulse
–
Indicates the repeater has experienced a low battery
condition.
Continuous Flash: A 2
flash pattern continuous
pulse between On and
Off states with a short
delay after the 2
nd
pulse
–
Indicates an AC power failure is detected.
–
A communication failure within internal hardware
components inside the receiver
4.3
4.4
20
en | RADION repeater
RADION receiver OP
02.2014 | 01 | F.01U.261.835