background image

General installation

Phases of installation
The installation of the RADION system is achieved by following the sequential process as
defined in this chapter. Overall, there are four main phases;

Planning

Physical installation of the devices

System enrollment/configuration

System testing (walk test, pattern test)

It is essential that these steps or phases are adhered to in the order mentioned above for
proper functionality and operation.
When installing a RADION system, you must plan your installation based on the control panel
and RADION device specifications, and the radio-frequency signal strength (RFSS) between
devices, receivers, and control panels.
Installation considerations

RADION devices are intended only for indoor, dry applications.

Mount RADION devices on flat, rigid surfaces. Some devices can be optionally corner
mounted as indicated in the installation instructions.

Avoid mounting RADION devices in areas with large, metallic objects, electrical panels, or
electric motors. They might reduce the radio-frequency (RF) range of a RADION device.

Avoid installing the devices where excessive humidity, moisture, or temperatures outside
of the acceptable operating range exist.

Wire all objects according to their specifications.

RADION devices use batteries of varying types. When installing batteries, observe safety
and polarity recommendations as indicated in the documentation for those products.

Installation workflow

To install, configure, and test the system, use the workflow below and follow in sequential
order, from top to bottom, checking each box as you complete a step.

Notice!
Always power down the control panel when connecting modules, or other wiring. Power
down the control panel by unplugging the transformer and disconnecting the battery

 Plan the installation of the RADION system

 Install the RADION components (refer to the graphical installation guides and this system

reference guide for details)

 Program wireless points in the control panel

 Enroll point RF ID for wireless points

 Verify LED responses on devices

 Perform a local walk test for installed detectors

 Review signal strength and margin of each point

 Complete the installation

 

2

2.1

 

RADION receiver OP

General installation | en

7

Bosch Security Systems, Inc

Reference Guide

02.2014 | 01 | F.01U.261.835

Содержание radion rfrc-opt

Страница 1: ...RADION receiver OP RFRC OPT en Reference Guide ...

Страница 2: ......

Страница 3: ... 2 6 Walk test 14 3 2 7 Complete the installation 15 3 2 8 RFRC OPT system test 15 3 3 External LED states 15 3 4 Specifications RFRC OPT 16 3 4 1 Battery requirements 17 4 RADION repeater 19 4 1 Installation considerations 19 4 2 Wiring considerations 19 4 3 Specifications 20 4 4 LEDs 20 5 RADION glassbreak 21 5 1 Installation considerations 21 5 2 Testing 22 5 2 1 Test the sensor 22 5 2 2 Hand c...

Страница 4: ...tact RM 38 11 1 Installation considerations 38 12 RADION specialty 40 12 1 Applications for this product 40 12 2 Installation consideration 41 13 RADION universal transmitter 42 13 1 Installation considerations 43 13 2 Reed switch settings 43 14 RADION keyfob 45 14 1 RADION keyfob FB 45 14 2 RADION keyfob TB 46 15 RADION panic 48 16 Appendices 50 4 en Table of Contents RADION receiver OP 02 2014 0...

Страница 5: ...used within the RADION documentation Icons and symbols When you see the following logo in the RADION graphical installation guides listed in Table 3 1 refer to the appropriate section in this document Additional icons and symbols which appear in the RADION graphical installation guides are explained in the appendix section of this guide Refer to the Appendices page 50 for more information About do...

Страница 6: ...6 en Introduction RADION receiver OP 02 2014 01 F 01U 261 835 Reference Guide Bosch Security Systems Inc ...

Страница 7: ... RADION device Avoid installing the devices where excessive humidity moisture or temperatures outside of the acceptable operating range exist Wire all objects according to their specifications RADION devices use batteries of varying types When installing batteries observe safety and polarity recommendations as indicated in the documentation for those products Installation workflow To install confi...

Страница 8: ...he wall tamper slot prevents the wall tamper feature from generating a tamper signal when the transmitter is pulled away from a wall Magnet cover installation During the installation of the plastic magnet cover the cover is not designed to be separated from the base after the base and cover are snapped together Damage to the plastics may occur if separated Complete installation Testing the entire ...

Страница 9: ... Magnet testing can be performed by opening or closing the door window in which the magnet is installed on Maintenance It is recommended to check the battery of each device annually This will ensure proper operation and functionality of the devices Battery Life Extension feature PIR and TriTech In the normal operating mode an alarm can be transmitted only after three 3 minutes have passed since th...

Страница 10: ...l installation guide P N F01U291208 RFDW SM RADION contact SM Graphical installation guide P N F01U261817 RFKF TB RFKF FB RADION keyfob Graphical installation guide P N F01U261820 RFPB SB RFPB TB RADION panic TB Graphical installation guide P N F01U261821 RFPR 12 RADION PIR Graphical installation guide P N F01U261822 RFPR C12 RADION PIR C Graphical installation guide P N F01U261823 RFRP RADION rep...

Страница 11: ...epeaters Notice Mount the receiver in a location away from metal objects Metal objects duct work wire mesh screens boxes reduce RF range RFRC OPT configuration RADION Wireless System operates on a radio frequency of 433 42 MHz Configuring the address switch The address switch determines the receiver s numeric address value which the receiver will use to report receiver status information to the co...

Страница 12: ...he base of the receiver onto the desired surface The base must be mounted in such a way that provides plenty of accessible space to insert a flat headed screwdriver and remove the receiver cover when maintenance and troubleshooting scenarios occur Because of the location of the opening mechanism on the side of the device you will need approximately 254 mm 10 in of clearance on one side of the base...

Страница 13: ...ystem and the supported Option bus control panel This can be accomplished by using one of two methods Using remote programming software on a supported laptop computer or Compatible keypad devices to enable your points A point can be a detection device or a group of devices connected to your security system The first step to enable communication is to verify that the RADION transmitter is programme...

Страница 14: ...l of the compatible control panel on enrolling RF ID s Walk test Use the following pattern testing procedure to test the detector range and functionality Motion walk test Remove and replace cover to activate a 90 sec Walk Test Mode During this Test Mode any activity in the sensor s coverage pattern will cause a transmitted alarm and LED activation Each alarm will also extend the Test Mode for an a...

Страница 15: ...eceiver utilizes the External LED to show various states of the receiver These states fall into the following three categories Normal state Communication error state Trouble state Maintenance state Off state Normal state The receiver enters a normal state when it has passed all power self tests and has established a communication link with the control panel The receiver remains in this state as lo...

Страница 16: ...D condition State description Continuous fast flash A continuous pulse between On and Off states Trouble state Indicates the receiver is in a trouble state experiencing a radio frequency interference failure A communication failure with internal hardware components within the receiver Maintenance state The receiver enters a maintenance state when the address switch settings are set between switch ...

Страница 17: ...e Battery Type Cell Voltage Quantity Cells RFPR 12 PIR motion detector CR123A Lithium 3 VDC 1 RFPR C12 PIR motion detector curtain CR123A Lithium 3 VDC 1 RFRP repeater Non replaceable Lithium polymer 3 7 VDC nominal 1 RFSM smoke detector CR123A Lithium 3 VDC 2 RFUN universal transmitter CR123A Lithium 3 VDC 1 RFBT bill trap AAA Lithium 1 5 VDC 1 RFDL 11 TriTech detector AA Alkaline 1 5 VDC 4 RFDW ...

Страница 18: ...B key fob RFKF FB key fob CR2032 coin cell Lithium 3 VDC 1 RFPB SB panic button RFPB TB panic button CR2032 coin cell Lithium 3 VDC 1 Table 3 4 Battery Requirements 18 en RADION receiver OP RADION receiver OP 02 2014 01 F 01U 261 835 Reference Guide Bosch Security Systems Inc ...

Страница 19: ...le for the repeater Do not connect power supply to a receptacle controlled by a switch Installation considerations Use the provided anchors and screws to mount the repeater in locations accessible for future maintenance Mount the repeater onto a wall Notice Mount the repeater in a location removed from metal Metal objects duct work wire mesh screens boxes reduce RF range Wiring considerations Noti...

Страница 20: ... 1 Specifications LEDs The repeater utilizes an external LED indicator to status the operation of the repeater Refer to the table below for LED descriptions LED Condition Pattern Description On Normal Indicates the repeater is functioning normally Off Indicates there is a power failure to the repeater or that the receiver is not wired correctly Continuous Flash 1 sec rate for 5 sec Indicates the r...

Страница 21: ... mm to 6 4 mm 3 32 in to 1 4 in Tempered 3 2 mm to 6 4 mm 1 8 in to 1 4 in Laminated 3 2 mm to 6 4 mm 1 8 in to 1 4 in Wired 6 4 mm 1 4 in Minimum pane size for all types of glass 1 2 m 4 ft Microphone Omni directional 360゚ electret Operating Temperature Functional range 10 C to 49 C 14 F to 120 F UL only 0゚C to 49゚C 32゚F to 120゚F EN 50130 5 Class II only 10゚C to 40゚C 14゚F to 104゚F Relative Humidi...

Страница 22: ...break detectors are intended only as a component of a perimeter protection system They should always be used in conjunction with motion sensors Testing Test the detector at least once each year Test the detector with the Sentrol 5709C hand held tester to set the sensor into test mode Set the tester to tempered glass hold the speaker directly on top of the sensor and activate the tester The sensor ...

Страница 23: ... LED does not stay in a solid state momentarily but continues to blink adjust the positioning of the sensor so that it is closer to the window and re test Also check the battery strength of the hand held testing device Figure 5 1 Testing behind curtains The sensor switches from test mode to normal mode when there is at least 1 min of silence from the hand held tester Notice When the detector is in...

Страница 24: ...ng the hand clap 1 Hand clap loudly under the sensor The LED blinks twice 2 Verify that the LED blinks twice 3 Performing this simple test verifies that the microphone is operating and that there is power to the sensor Low battery When a low battery state is detected the detector measures the battery and sends a report to the receiver control panel Wall Tamper Tab Use the wall tamper tab to activa...

Страница 25: ...ivity selection Field selectable for standard or intermediate sensitivity Power voltage Four AA Alkaline batteries 1 5 VDC 1 5 VDC x 4 6 VDC total Battery replacement Duracell MN1500 Panasonic AM 3PIX Check your battery yearly to ensure proper functionality Battery life Up to 5 years Device testing To ensure proper functionality the device must be tested at least once every year by an installer Wa...

Страница 26: ...daily operation instruct the end user to walk through the far end of the coverage pattern This ensures an alarm output prior to arming the system Start Walk Test mode from the detector Insert a slotted screwdriver to open the detector cover and then close the detector cover to start a 90 sec Walk Test mode Notice In the normal operating mode an alarm can be transmitted only after three 3 minutes h...

Страница 27: ... as low a setting as possible for proper catch performance Figure 6 1 Sensitivity settings 1 ᅳ Alarm LED blue green or red 2 ᅳ Microwave Range Adjustment Potentiometer 3 At each pass observe the color on the Alarm LED refer to the Sensitivity settings figure above 4 Walk test from the opposite direction to determine the coverage pattern boundaries from both sides 5 When walk test is completed the ...

Страница 28: ...ity Battery life Up to 5 years Device testing To ensure proper functionality the device must be tested at least once every year by an installer Wall and cover tamper switch Transmits a tamper signal when someone removes the device from its base or pulls it away from the wall Frequency 433 42 MHz Table 7 1 Specifications Walk testing Perform a walk test to determine the boundaries of the coverage a...

Страница 29: ...lk across the pattern moving closer to the detector refer to the Walk test figure above 2 While the detector is in the Walk Test Mode turn ON all heating and air conditioning sources which would normally be active during the protection period Stay away from the sensor and outside the coverage pattern and watch for alarms 3 The LED flashes at the completion of a 90 sec span of time indicating that ...

Страница 30: ...nyo CR123A Check your battery yearly to ensure proper functionality Battery life Up to 5 years Device testing To ensure proper functionality the device must be tested at least once every year by an installer Wall and cover tamper switch Transmits a tamper signal when someone removes the device from its base or pulls it away from the wall Frequency 433 42 MHz Table 8 1 Specifications Walk testing P...

Страница 31: ...k across the pattern moving closer to the detector refer to the Walk test figure above 2 While the detector is in the Walk Test Mode turn ON all heating and air conditioning sources which would normally be active during the protection period Stay away from the sensor and outside the coverage pattern and watch for alarms 3 The LED flashes at the completion of a 90 sec span of time indicating that t...

Страница 32: ... CR123A or Sanyo CR123A Check your batteries yearly to ensure proper functionality Battery life Minimum of 5 years or greater Device testing To ensure proper functionality the device must be tested at least once every year Sensitivity 0 14 0 04 bM m 0 97 2 99 ft obscuration RFSM A only Temperature operating 0゚C to 49゚C 32゚F to 120゚F Relative humidity 0 to 93 non condensing Cover and wall tamper sw...

Страница 33: ...e system into Test mode before activating the detector using this method Sensitivity test Notice The control panel recognizes Test Mode as a test It does not send an alarm The detector includes a Sensitivity Level Test mode for determining the detector s sensitivity 1 Press and hold the Test Silence button for 4 sec The LED flashes 1 to 9 times 2 Count the number of LED flashes and use the Smoke d...

Страница 34: ...this test LED LED Status Flashing Flashes every 8 sec under normal operation ON Detects smoke sending an alarm OFF Malfunction replace the batteries clean the detector or replace the optical chamber as required Table 9 3 LED Clean the detector and replace the optical chamber Clean the detector cover with a dry or damp cloth as needed to keep it free from dust and dirt Clean the detector interior a...

Страница 35: ...p with the detector press the cap onto the detector and turn clockwise to snap it firmly into place 8 Observing the proper polarity install the batteries and the battery cover If the batteries are not installed properly the detector will not fit onto the mounting base Ensure that the batteries are properly installed 9 Mount the detector onto the mounting base 10 Test the detector s sensitivity RAD...

Страница 36: ... or pulls it away from the wall Frequency 433 42 MHz Table 10 1 Specifications Installation considerations You have a variety of installation options to consider when installing the device You must acknowledge the unique installation approach prior to installation Some installation considerations include Suitable surfaces for installation include wood steel and aluminum The location of the magnet ...

Страница 37: ...al table found in the graphical Installation and Operation Guide when installing the magnet adjacent to the transmitter How to read the Graphical Magnet Distances table Contained in the RADION contact SM Installation Guide is a graphical table along with the X ᅳ Y ᅳ Z coordinates graphic Use the table in conjunction with the graphic to determine desired distances between the magnet and the transmi...

Страница 38: ...nsiderations You have a variety of installation options to consider when installing the device You must acknowledge the unique installation approach prior to installation Some installation considerations include The installation of this device is suitable for wood surfaces This device is not suitable for steel surfaces The transmitter housing was designed to be open with a coin Using a screwdriver...

Страница 39: ...a graphical table along with the X ᅳ Y coordinates graphic Use the table in conjunction with the graphic to determine desired distances between the magnet and the transmitter based on the type of installation RADION receiver OP RADION contact RM en 39 Bosch Security Systems Inc Reference Guide 02 2014 01 F 01U 261 835 ...

Страница 40: ...sure proper functionality Battery life Up to 5 years Device testing To ensure proper functionality the device must be tested at least once every year Relative humidity Up to 93 non condensing Temperature operating Functional range 10 C to 49 C 14 F to 120 F UL only 0゚C to 49゚C 32゚F to 120゚F EN 50130 5 Class II only 10゚C to 40゚C 14゚F to 104゚F Frequency 433 42 MHz Table 12 1 Specifications Figure 12...

Страница 41: ...on consideration During the installation process use the self adhesive Velcro strips located on the bottom of the bill trap base to secure and stabilize the bill trap in the cash drawer This is achieved by performing the following 1 Separate the Velcro strips from one another 2 Peel off the protective backing of the Velcro strips 3 Press the two bottom sections of the Velcro onto the bottom of the...

Страница 42: ...nality the device must be tested at least once every year by an installer Temperature operating 0゚C to 49゚C 32゚F to 120゚F Relative Humidity 0 to 93 non condensing Terminal block For connecting other dry contact devices such as another magnetic reed switch Wall and cover tamper switch Transmits a tamper signal when someone removes the device from its base or pulls it away from the wall Frequency 43...

Страница 43: ...nsmitter do not function effectively When installing the magnet base install the face of the magnet base flush to the surface edge of the installation location This prevents damage to the magnet plastic base whenever a window or door is opened The minimum cable length between the initiating device and the transmitter terminal is 6 21 m 25 ft 22 AWG Adhere to the distances prescribed in the graphic...

Страница 44: ...ion 1 ᅳ No jumper disables the internal reed switch 2 ᅳ Jumper on enables the internal reed switch 44 en RADION universal transmitter RADION receiver OP 02 2014 01 F 01U 261 835 Reference Guide Bosch Security Systems Inc ...

Страница 45: ...pecification table for the correct battery type when replacing an old battery Keyfob buttons Refer to your control panel s documentation to program the functions of the programmable buttons Pressing either the arm or disarm button causes the LED to flash for about 2 sec indicating the keyfob sent commands to the control panel Notice Pressing the Arm and Disarm buttons in unison for 1 sec transmits...

Страница 46: ...FKF TB two button keyfob is designed for arming lock icon and disarming unlock icon the system remotely To operate these buttons simply press and hold either button for at least one sec in order for the desired feature to work Uniquely coded arm and disarm buttons Panic alarm LED indicator 14 2 46 en RADION keyfob RADION receiver OP 02 2014 01 F 01U 261 835 Reference Guide Bosch Security Systems I...

Страница 47: ...Figure 14 2 Keyfob buttons and LED 1 ᅳ Arm button 2 ᅳ LED 3 ᅳ Disarm button RADION receiver OP RADION keyfob en 47 Bosch Security Systems Inc Reference Guide 02 2014 01 F 01U 261 835 ...

Страница 48: ... button versions LED indicator Optional accessories 2 1 1 2 Figure 15 1 Panic Buttons 1 ᅳ Panic buttons 2 ᅳ LED Relative humidity 0 to 93 non condensing Temperature operating Functional range 10 C to 49 C 14 F to 120 F UL only 0゚C to 49゚C 32゚F to 120゚F EN 50130 5 Class II only 10゚C to 40゚C 14゚F to 104゚F Dimensions 63 70 mm x 35 50 mm x 13 00 mm 2 51 in x 1 40 in x 0 51 in Power voltage One CR2032 ...

Страница 49: ...l to meet the needs of patrolling guards bank employees and retail store employees Belt Clip Belt Clip transmitters provide single or two button activation confirmed by emitting LED flashes with all transmissions to clearly show users when the unit is operating The single button design is ideal for assisted living installations whereas the two button design reduces accidental activation Wrist Stra...

Страница 50: ...choice selection or location Pet friendly appropriate height and weights below graphic Point away from rotating machines Point away from objects that rapidly change temperature Do not mount the device that has direct exposure to sunlight Do not point toward window Intended for indoor use only 16 50 en Appendices RADION receiver OP 02 2014 01 F 01U 261 835 Reference Guide Bosch Security Systems Inc...

Страница 51: ...emperature range Frequency range Duration of time Questions are answered in the reference guide Universal sign for connecting or disconnecting power Universal sign for connecting to a power source RADION receiver OP Appendices en 51 Bosch Security Systems Inc Reference Guide 02 2014 01 F 01U 261 835 ...

Страница 52: ...tery related information Perform a walk test Walk test has concluded Device has wall tamper detection 52 en Appendices RADION receiver OP 02 2014 01 F 01U 261 835 Reference Guide Bosch Security Systems Inc ...

Страница 53: ......

Страница 54: ...Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 USA www boschsecurity com Bosch Security Systems Inc 2014 ...

Отзывы: