Configuration
IRIS-Net
IRIS-Net PC software is used to configure and operate the PAVIRO system. It enables the
overall configuration of the controller and connected devices to be performed off-line using a
PC (i.e., without establishing a connection between the PC and controller). The configuration
can then be transferred by establishing a connection between the PC and controller via
Ethernet. In addition to configurations, IRIS-Net can also be used for comprehensive checking
and monitoring of a system. For more information about installing IRIS-Net on your PC, see the
file “iris_readme.pdf”. During the installation, the IRIS-Net user manual is automatically copied
to the PC.
Network configuration
The controller can be connected to a TCP/IP network via the Ethernet interface on the rear
panel. The controller has the following network configuration by default:
Parameter
Value
IP address
192.168.1.100
Subnet mask
255.255.255.0
Gateway
192.168.1.1
DHCP
Disabled
Table 7.1: Factory setting for Ethernet interface
An IP address must be unique, i.e., it must only be assigned to one device (host) in a network.
If a new Ethernet is established for operating the controller, we recommend retaining the
default network ID and subnet mask. When integrating the controller into an existing Ethernet,
the network configuration of the controller must be adjusted. The default IP address of the
controller can be retained if
–
only one single controller is connected with the default network configuration via
Ethernet, and
–
the network ID 192.168.1 can be retained, and
–
no other device has the host ID 100.
If at least one of these three conditions is not met, the default IP address of the controller
must be changed.
Displaying the CAN baud rate
To display the CAN baud rate, press the Recessed button and keep the button pressed down
for at least one second. Three front panel indicator lights then display the set baud rate for
two seconds. Please refer to the following table for details.
Baud rate (in kbit/s)
Zone status indicator
light of zone 11
Zone status indicator
light of zone 12
Network indicator
light
10
Off
Off
On
20
Off
On
Off
62.5
Off
On
On
125
On
Off
Off
7
7.1
7.2
PAVIRO Controller
Configuration | en
35
Operation manual
08-May-2017 | 04 | F01U306900